Plan Review Details - Permit 00091387
Plan Review Stops For Permit 00091387
Review Stop FS  
Rev No 2 Status P Date 2000-10-06 Cont ID  
Sent By mcarsill Date 2000-10-06 Time 07:28 Rev Time 0.00
Received By mcarsill Date 2000-10-06 Time 07:28 Sent To  
Notes
2001-01-08 00:00:001) FIRE DEPARTMENT CONNECTION TO BE
 WITHIN 150 FEET OF A FIRE HYDRANT.
 2) SPARE HEAD BOX AND WRENCH TO BE
 PROVIDED.
 3) CUT SHEETS FOR FIRE SPRINKLER HEADS
 PLANNED FOR USE WERE NOT PROVIDED.
 APPROVED PROVISO:

Review Stop FS  
Rev No 1 Status F Date 2000-09-27 Cont ID  
Sent By mcarsill Date 2000-09-27 Time 14:51 Rev Time 0.00
Received By mcarsill Date 2000-09-27 Time 14:51 Sent To  
Notes
2001-01-08 00:00:001) WHERE IS THE FIRE DEPARTMENT
 CONNECTION LOCATED.
 2) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL AND MECHANICAL ROOMS. ALL
 VERTICAL SHAFTS ARE ALSO TO BE
 PROTECTED.
 3) THE FRONT PORCH SHOWN ON THE FIRST
 FLOOR PLAN IF COMBUSTIBLE AND EXCEEDS
 FOUR FEET WIDE IS TO BE FIRE SPRINKLER
 PROTECTED.
 4) SPARE HEAD BOX AND WRENCH IS TO BE
 PROVIDED.
 5) SPRINKLER HEADS LOCATED ON BOTH SIDES
 OF THE WINDOWS ARE TO BE LOCATED NO
 FARTHER THAN 1 FOOT OF THE GLASS TO
 PREVENT CRACKING.
 6) PROVIDE CUT SHEETS ON FIRE SPRINKLER
 HEADS PLANNED FOR USE.