Plan Review Details - Permit 00091222
Plan Review Stops For Permit 00091222 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-10-25 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-10-25 |
Time |
09:33 |
Rev Time |
1.50 |
Received By |
drunnels |
Date |
2000-10-25 |
Time |
09:33 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO | | 1.DOOR #12 SHALL COMPLY WITH SECTION | | 1012.1.5 1997 SBC |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-10-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-10-25 |
Time |
01:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-10-25 |
Time |
01:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2000-11-14 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-11-14 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-11-14 |
Time |
08:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2000-11-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-11-02 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-11-02 |
Time |
17:44 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | WITH FIRE SPRINKLER PLANS. | | 2) A FOLDED SET OF E2.1 PLANS HAS BEEN | | AMENDED BUT ARE NOT SIGNED AND SEALED | | LIKE THE PLANS. THE E2.1 PLANS DO NOT | | CORRELATE. ORIGINAL E2.1 MUST BE | | REVISED. PLEASE REFER TO FS 61G15-23.002 | | 471.025 | | 3) NO INTERIOR FINISH INFORMATION | | PROVIDED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-09-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-09-29 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-09-29 |
Time |
15:39 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) FIRE SPRINKLER DRAWINGS AND HYDRAULIC | | CALCULATIONS ARE TO BE PROVIDED WITH | | PLANS. ACCORDING TO THE PLANS THE FIRE | | SPRINKLERS WILL BE PERMITTED SEPARATELY | | NO BUILDING PERMIT WILL BE ISSUED | | WITHOUT SPRINKLER DRAWINGS. | | 2) DOORS 01 AND 12 ARE TO BE EQUIPPED | | WITH SELF-CLOSING DEVICES. WHEN CLOSED | | THESE DOORS ARE REQUIRED TO POSITIVELY | | LATCH | | 3) PLEASE INDICATE INTERIOR FINISHES | | FOR EXITS AND OFFICES. THE CURRENT FIRE | | CODE REQUIRES THAT INTERIOR FINISHES | | IN EXITS BE CLASS A OR B. INTERIOR | | FINISHES IN OFFICES CAN BE CLASS A,B, | | OR C. | | 4) THE FIRE ALARM NOTES SECTION OF THE | | PLAN INDICATES CLASS B, STYLE C | | CIRCUITS. ONLY CLASS A, STYLE D FIRE | | ALARM CIRCUITS ARE PERMITTED. | | 5) PLEASE SUBMIT FIRE ALARM SYSTEM | | SHOP DRAWINGS FOR NEW FIRE ALARM | | EQUIPMENT SHOWN ON PLANS. CUT SHEETS | | ARE TO BE PROVIDED WITH FIRE ALARM | | PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-10-21 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-10-21 |
Time |
09:36 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-10-21 |
Time |
09:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-12-04 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-04 |
Time |
07:17 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2000-12-04 |
Time |
07:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-09-30 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-30 |
Time |
07:03 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-09-30 |
Time |
06:52 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *****************PROVISO**************** | | LOUNGE SINK AND CABINET SHALL COMPLY W/ | | FACBC SEC.4.24.1.-4.24.7. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
|