Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-13 Cont ID  
Sent By mcarsill Date 2000-09-13 Time 08:19 Rev Time 0.00
Received By mcarsill Date 2000-09-13 Time 08:19 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE MANUAL MEANS TO
 ACTIVATE THE DRY-CHEMICAL SYSTEM AS
 PER NFPA 17, SECTION 3-7.1.
 2) ENTIRE SYSTEM TO COMPLY WITH NFPA 17,
 THE STANDARD FOR DRY-CHEMICAL
 EXTINGUISHING SYSTEMS.
 APPROVED PROVISO:

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-13 Cont ID  
Sent By ndenmark Date 2000-09-13 Time 14:55 Rev Time 0.33
Received By ndenmark Date 2000-09-13 Time 14:55 Sent To  
Notes
***NONE***