Plan Review Details - Permit 00090413
Plan Review Stops For Permit 00090413
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-03-08 Cont ID  
Sent By hpiskura Date 2001-03-08 Time 15:34 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-03-08 00:00:00REV #3

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-12-20 Cont ID  
Sent By hpiskura Date 2000-12-20 Time 15:22 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-10-13 Cont ID  
Sent By drunnels Date 2000-10-13 Time 09:57 Rev Time 2.00
Received By drunnels Date 2000-10-13 Time 09:57 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT DETAILS SHOWING THAT COUNTERS
 COMPLY TO FLORIDA ACCESSIBILITY CODE
 2. SUBMIT DETAILS ON SKYLIGHT SHOWING
 COMPLIANCE WITH CHAPTER 24 SBC 1997 ED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 20:49 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 20:49 Sent To  
Notes
2001-04-05 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT NOTES FROM
 PREVIOUS REVIEW WERE NOT ADDRESSED.
 PLEASE SUBMIT THE INFORMATION NEEDED FRO
 M PREVIOUS NOTES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-03-07 Cont ID  
Sent By dpalmer Date 2001-03-07 Time 21:23 Rev Time 0.00
Received By dpalmer Date 2001-03-07 Time 21:17 Sent To  
Notes
2001-03-07 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW COMPLETED LOAD
 CALCULATIONS. ALL CONTINUOUS LOADS ARE
 TO BE SHOWN AT 125% PER 215-2&3 AND
 210-20
  
 2)NOTE: PLEASE PROVIDE KVA RATING OF
 TRANSFORMER. PLEASE PROVIDE
 CLARIFICATION ON INSTALLATION AT
 CEILING AS TO MEET 450-13
  
 3)NOTE: PLEASE PROVIDE NOTE ON PLAN
 UNDER LIGHTING FIXTURE SCHEDULE.
 " ALL FIXTURES AND FIXTURE COMPONETS
 ARE TO BE UL LISTED"
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-13 Cont ID  
Sent By dpalmer Date 2000-10-13 Time 10:04 Rev Time 0.00
Received By dpalmer Date 2000-10-13 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-03-13 Cont ID  
Sent By mcarsill Date 2001-03-13 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2001-03-13 Time 10:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-09-15 Cont ID  
Sent By mcarsill Date 2000-09-15 Time 09:16 Rev Time 0.00
Received By mcarsill Date 2000-09-15 Time 09:16 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE EMERGENCY LIGHTING
 EQUIPMENT IN TENANT SPACE.
 2) PROVIDE FIRE ALARM SYSTEM SHOP
 DRWAINGS FOR FIRE ALARM DEVICES SHOWN
 ON PLANS. CUT SHEETS ON FIRE ALARM
 DEVICES PLANNED FOR USE ARE REQUIRED.
 3) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B. INTERIOR FINISHES IN
 OFFICES SHALL BE CLASS A, B, OR C.
 APPROVED PROVISO:

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2001-03-15 Cont ID  
Sent By ndenmark Date 2001-03-15 Time 12:54 Rev Time 0.25
Received By ndenmark Date 2001-03-15 Time 12:54 Sent To  
Notes
2001-03-15 00:00:00NO MECH INCLUDED THIS REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-02-27 Cont ID  
Sent By pkrauss Date 2001-02-27 Time 12:18 Rev Time 0.40
Received By pkrauss Date 2001-02-27 Time 12:18 Sent To  
Notes
2001-02-27 00:00:00PROVISO:PIU 3-2 SHALL HAVE
 ACCESSIBILITY FOR SERVICE AND
 MAINTANIENCE AS PER 1997 SMC 304.2.1.
  
 NOTE: DRAWING FA0.1 - FIRE ALARM NOTES,
 NUMBER 14. DUCT SMOKE DETECTORS SHALL
 COMPLY WITH 1997 SMC 406.4 AND NFPA 90A
 CHAPTER 4, 4-4.4.2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-10-04 Cont ID  
Sent By ndenmark Date 2000-10-04 Time 17:42 Rev Time 0.50
Received By ndenmark Date 2000-10-04 Time 17:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-04-14 Cont ID  
Sent By jleech Date 2001-04-14 Time 10:34 Rev Time 1.00
Received By jleech Date 2001-04-14 Time 10:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2001-03-14 Cont ID  
Sent By jleech Date 2001-03-14 Time 16:27 Rev Time 1.00
Received By jleech Date 2001-03-14 Time 16:26 Sent To  
Notes
2001-03-14 00:00:00DENIED;
  
 1.FLOORSHALL BE USED INPLACE OF A HUB
 DRAIN. FLOOR DRAIN SHALL BE PRIMED.
  
 2.SHEET A-1 WATER HEATER IS IN A DIRRENT
 LOCATION THAN P-3.1 AND NOT SHOWD AT
 ALL ON P-2.1.
  
 3.P-5 FLOOR DRAIN IN BATHROOM IS MISSING
 FROM SANITARY RISER DIAGRAM.
  
 4.WHY IS A MECHANICAL VENT NEEDED? TEN
 FEET OF PIPE ABOVE THE CEILING AND THE
 PLUMBER COULD TIE INTO THE VENT SYSTEM
  
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-12-10 Cont ID  
Sent By pschmitz Date 2000-12-10 Time 11:54 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE NOTE BY ARCH. ON SHT A-4.SEAT SHO.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-16 Cont ID  
Sent By tlarge Date 2000-09-16 Time 07:26 Rev Time 1.25
Received By tlarge Date 2000-09-16 Time 06:28 Sent To  
Notes
2001-01-08 00:00:00SHOWER SEAT SHALL COMPLY W/FACBC SEC.
 4.21.3.