Plan Review Details - Permit 00090107
Plan Review Stops For Permit 00090107
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-12-18 Cont ID  
Sent By dpalmer Date 2001-12-18 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2001-12-18 Time 08:59 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-11-13 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2001-11-13 Time 13:45 Sent To P
Notes
2001-11-13 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT THE PLANS
 SUBMITTED FOR GUEST/GARAGE DO NOT
 CORRELATE WITH PLANS FORMAIN HOUSE
 SERVICE. TWO PLANS /TWO SERVICES?
  
 2)NOTE: PLEASE CLARFIY SIZE OF METERCAN,
 SHOWN AS EXISTING? LOAD SHOWN AT 269.9A
  
 3)NOTE: PLEASE NOTE THAT ON GUEST HOUSE
 METER AND TWO DISCONNECTS ARE SHOWN, BUT
 DOES NOT SHOW WHERE PANEL IS ON PLANS?
 NOTE NEXT TO SERVICE SAYS, "GUEST HOUSE
 PANEL" , THEN WHERE IS MAIN DISCONNECT
 SHOWN ON RISER DIAGRAM?
  
 4)NOTE: PLEASE NOTE MISSING GROUNDING
 AT DETACHED MAIN HOUSE. 250-32.
  
 5)NOTE: PLEASE INDICATE MCB FOR PANEL
 AT MAIN HOUSE DETACHED FROM GUEST HOUSE
 SERVICE. 225-31
  
 6)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS BETWEEN MAIN DISC`S
 AND PANELS. 250-122
  
 7)NOTE: PLEASE CLARIFY 2/0`S SHOWN FOR
 100A EQUIPMENT?
  
 8) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 ARE THE GFI CIRCUITS THAT ARE SHOWN ON
 PANEL SCHEDULE FOR THIS?
  
 9)NOTE: PLEASE SHOW GARAGE ON THE
 ELECTRICAL PLAN AND SHOW REQ`D ELEC.
 FOR GARAGE. PLAN SHOW GARAGE AS DETACHED
 ?? PLEASE CLARIFY.
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT THE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-10-19 Cont ID  
Sent By dpalmer Date 2000-10-19 Time 21:46 Rev Time 0.00
Received By dpalmer Date 2000-10-19 Time 21:46 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY PLANS, YOU SHOW
 GARAGE AS FUTURE BUT ARE SHOWING AS NEW
 ROOF ETC??? ELECTRIC REQ`D IF NEW?
  
 2)NOTE: PLEASE SHOW NEW CU FOR A/C
 DISCONNECT PER 440-11 AND WP GFI.
  
 3)NOTE: PLEASE NOTE PER FIRST REVIEW,
 MISSING GFI FOR REAR OF BLDG. 210-52E
  
 4)NOTE: PLEASE SHOW WINDOW A/C BEING TAK
 -EN OUT? IS A/C ON FIRST FLOOR FEEDING
 SECONG FLOOR?
  
 5)NOTE: LOAD CALCULATIONS (SQ FT) DOES-
 -NOT MATCHFLOOR SQ FT.?? IS FIRST
 FLOOR AND SECOND FLOOR ON SAME PANEL?
  
 6)NOTE: SINCE FIRST REVIEW A NEW SERVICE
 IS BEING SHOWN.. 100AMP PANEL W/ 2/0
 WIRE? IS THIS CORRECT?
 PLEASE SUBMIT AIC RATING OF NEW MAIN
 DISCONNECT AND PANEL. MUST BE RATED FOR
 AVAILABLE FAULT CURRENT PER 110-9 AND
 215-5.
  
 7)NOTE: PLEASE SHOW BATH(S) CIRCUIT(S)
 REQ`D PER 210-11-C-3 AND 210-52D. #12 AN
 20AMP.
  
 8)NOTE: PLEASE NOTE;YOU SHOW DISCONNECTS
 ON AHU AND WATER HEATER? NOTE 110-26 FOR
 DISC CLEARENCE. PANEL IS WITHIN SIGHT
 ACCROSS HALL?S
  
 9)NOTE: PLEASE CHECK LOAD SHOWN FOR
 WATER HEATER ON #12 AND 20AMP BRKR?
 PLEASE NOTE THAT OCP FOR A 4500W WATER
 HEATER MUST BE 125%. 4500W EXCEEDS 80%
 OF BRKR.
  
 10)NOTE: PLEASE SEE 250-122 AND SIZE
 EQUIPMENT GROUNDING CONDUCTOR FROM
 MAIN TO PANEL.
  
 1)NOTE: PLEASE SHOW EGRESS LIGHTING FOR
 MAIN GUEST ROOM FIRST FLOOR. PER 210-70
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-09-11 Cont ID  
Sent By dpalmer Date 2000-09-11 Time 17:15 Rev Time 0.00
Received By dpalmer Date 2000-09-11 Time 17:14 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PANEL SCHEDULE
 AND LOAD CALCULATIONS FOR NEW REMODELED
 AREA.215-5
 THERE APPEARS TO BE TWO SEPARATE APART-
 -MENTS? HOW ARE THEY BEING FED? IS THERE
 SEPARATE PANELS FOR EACH FLOOR?
 PLEASE SHOW CLARIFICATION.MEANS OF DISC?
  
 2)NOTE: ALSO MORE THAN 50% OF THIS STRUC
 -TURE IS BEING REMODELED.?
 PLEASE INSTALL SMOKE DETECTOR ON 2ND
 FLOOR.WIRE INLINE
  
 3)NOTE: PLEASE ADD GFI OUTLETS PER 210-
 -52-E.
  
 4)NOTE: PLEASE SEE 210-52D AND 210-11-C-
 -3 FOR REQ`D BATH(S) CIRCUIT(S). MUST BE
 #12 AND 20AMP.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-11-21 Cont ID  
Sent By fknapp Date 2000-11-21 Time 10:35 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-11-14 Cont ID  
Sent By kstevens Date 2001-11-13 Time 19:37 Rev Time 0.50
Received By kstevens Date 2001-11-13 Time 19:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-10 Cont ID  
Sent By dpalmer Date 2001-11-13 Time 14:06 Rev Time 0.30
Received By tlarge Date 2000-09-10 Time 08:42 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 SUBMIT SANITARY AND WATER RISER DIAGRAMS
 PRIOR TO PLUMBING INSPECTION.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-12-18 Cont ID  
Sent By rmcdouga Date 2001-12-18 Time 18:34 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-18 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - CASEMENT WINDOWS
 - EXTERIOR DOORS
  
 2) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS PRIOR TO
 INSTALLATION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2001-11-15 Cont ID  
Sent By rmcdouga Date 2001-11-15 Time 13:09 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-11-16 00:00:00REVISION DENIED
  
 1) PROVIDE AN EMERGENCY ESCAPE AND
 RESCUE OPENING FOR THE SECOND FLOOR
 GUEST ROOM PER 97 SBC SEC. 1005.4.1.
 THE WINDOW MUST HAVE A MINIMUM NET CLEAR
 OPENING OF 5.7 SQ.FT. WITH A MINIMUM NET
 CLEAR OPENING HEIGHT OF 24" AND MINIMUM
 NET CLEAR OPENING WIDTH OF 20". THE SILL
 HEIGHT CAN NOT BE MORE THAN 44" PER 97
 SBC SEC.1005.4.4 AND 1005.4.3.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS
 - STORM PANELS OR IMPACT GLASS
  
 3) PROVIDE ACCESS TO ATTIC SPACE PER
 97 SBC SEC. 2309.6.
  
 4) EXTERIOR EXITWAY STAIRS:
 EXTERIOR STAIRS SHALL BE SEPARATED FROM
 THE INTERIOR OF THE BUILDING BY WALLS
 WITH A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR, WITH FIXED OR SELF-
 CLOSING OPENING PROTECTIVES AS REQUIRED
 FOR ENCLOSED STAIRS. PROTECTION SHALL
 EXTEND VERTICALLY FROM THE GROUND TO A
 POINT 10 FEET ABOVE THE TOPMOST LANDING
 OR THE ROOF LINE WHICHEVER IS LOWER AND
 HORIZONTALLY 10 FEET FROM EACH SIDE OF
 THE STAIRWAY. OPENINGS WITHIN THE 10
 FOOT HORIZONTAL EXTENSION OF THE
 PROTECTED WALLS BEYOND THE STAIRWAY
 SHALL BE EQUIPPED WITH FIXED 3/4- HOUR
 ASSEMBLIES. 97 SBC SEC. 1006.2.4 THE NEW
 DOORS AND WINDOWS IN THIS AREA MUST
 COMPLY. SEE 97 SBC SEC. 705.1.3 FOR
 APPROVED TYPES OF FIRE WINDOWS AND DOORS
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-09-27 Cont ID  
Sent By fknapp Date 2000-09-27 Time 11:06 Rev Time 2.00
Received By fknapp Date 2000-09-27 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 ************BUILDING PROVISO************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR NEW
 EXTERIOR DOORS AND WINDOWS.
  
 2)PROVIDE OWNER/AGENT SIGNATURE ON
 ENERGY CALCULATIONS.
  
 3)PROVIDE MECHANICAL DRAWINGS WITH
 MECHANICAL PERMIT APPLICATION.
  
 4)MUST OBTAIN ZONING APPROVAL.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-14 Cont ID  
Sent By gjoyce Date 2000-09-27 Time 09:56 Rev Time 0.10
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00CAN NOT DO 2 KITHCENS!!!