Plan Review Details - Permit 00090067
Plan Review Stops For Permit 00090067
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-26 Cont ID  
Sent By rmcdouga Date 2001-01-26 Time 14:22 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-26 00:00:00TRUSSES
  
 TRUSS SUBMITTAL DENIED.
  
 TRUSS S3 ON THE TRUSS ENGINEERING LAYOUT
 IS NOT INDICATED ON THE ARCHITECTURAL
 DRAWINGS. IT HAS THREE BEARING POINTS.
 NO ANCHOR HAS BEEN SPECIFIED FOR THE
 INTERIOR BEARING POINT, WHICH HAS AN
 INDICATED UPLIFT OF 1907#.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-09-21 Cont ID  
Sent By dpalmer Date 2000-09-21 Time 23:02 Rev Time 0.00
Received By dpalmer Date 2000-09-21 Time 23:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-16 Cont ID  
Sent By jleech Date 2000-09-16 Time 10:32 Rev Time 0.33
Received By jleech Date 2000-09-16 Time 10:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-04-14 Cont ID  
Sent By kstevens Date 2001-04-14 Time 08:41 Rev Time 0.33
Received By kstevens Date 2001-04-14 Time 08:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 05:01 Rev Time 0.50
Received By tlarge Date 2000-10-21 Time 05:01 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
  
 1)MIN.SIZE SANITARY DRAIN U/G SHALL BE
 2".SPC SEC.714.4.
  
 2)LAYOUT OF FIXTURES ON SANITARY RISER
 SHALL CORRELATE W/THE FLOOR PLAN.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-09-13 Cont ID  
Sent By tlarge Date 2000-09-13 Time 11:20 Rev Time 0.50
Received By tlarge Date 2000-09-13 Time 11:20 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 MIN.SIZE DRAIN U/G SHALL BE 2"PER SPC
 SEC.714.4.
  
 LOCATION OF THE FIXTURES ON THE SANITARY
 RISER DO NOT CORRELATE W/THE FLOOR PLAN.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-10-27 Cont ID  
Sent By rmcdouga Date 2000-10-20 Time 13:51 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO
  
 1)STRUCTURE LOCATED IN "AO" FLOOD ZONE
 ELEVATION CERTIFICATE IS REQUIRED.
  
 2)PROVIDE SOIL COMPACTION TEST REPORT AT
 FIRST INSPECTION.
  
 3)PLEASE PROVIDE JOB/SITE LOCATION ON
 SPACE PROVIDED WHEN SUBMITTING SITE
 SPECIFIC PRODUCT APPROVAL FORMS AND HAVE
 ENGINEER/ARCHITECT PROVIDE THEIR NAME,
 ADDRESS AND REGISTRATION NUMBER LEGIBLY
 PRINTED ON FORM ALONG WITH WET SIGNATURE
 DATE AND RAISED SEAL.
  
 4)PROVIDE PRODUCT APPROVALS FOR SLIDING
 GLASS DOORS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-10-04 Cont ID  
Sent By rmcdouga Date 2000-10-04 Time 12:32 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
 SEE PLAN REVIEW FOR PERMIT # 00090066

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-11 Cont ID  
Sent By gjoyce Date 2000-09-11 Time 10:15 Rev Time 0.15
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***