Plan Review Details - Permit 00090067
Plan Review Stops For Permit 00090067 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2001-01-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2001-01-26 |
Time |
14:22 |
Rev Time |
2.00 |
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-26 00:00:00 | TRUSSES | | | | TRUSS SUBMITTAL DENIED. | | | | TRUSS S3 ON THE TRUSS ENGINEERING LAYOUT | | IS NOT INDICATED ON THE ARCHITECTURAL | | DRAWINGS. IT HAS THREE BEARING POINTS. | | NO ANCHOR HAS BEEN SPECIFIED FOR THE | | INTERIOR BEARING POINT, WHICH HAS AN | | INDICATED UPLIFT OF 1907#. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)659-8096 EXT.8202 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-09-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-09-21 |
Time |
23:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-09-21 |
Time |
23:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-09-16 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-09-16 |
Time |
10:32 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2000-09-16 |
Time |
10:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2001-04-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2001-04-14 |
Time |
08:41 |
Rev Time |
0.33 |
Received By |
kstevens |
Date |
2001-04-14 |
Time |
08:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-10-21 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-10-21 |
Time |
05:01 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-10-21 |
Time |
05:01 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************PROVISO***************** | | | | 1)MIN.SIZE SANITARY DRAIN U/G SHALL BE | | 2".SPC SEC.714.4. | | | | 2)LAYOUT OF FIXTURES ON SANITARY RISER | | SHALL CORRELATE W/THE FLOOR PLAN. | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | CALL IF YOU HAVE QUESTIONS. | | 561-659-8096,EXT.8377. | | | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-09-13 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-13 |
Time |
11:20 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-09-13 |
Time |
11:20 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ******************PROVISO*************** | | MIN.SIZE DRAIN U/G SHALL BE 2"PER SPC | | SEC.714.4. | | | | LOCATION OF THE FIXTURES ON THE SANITARY | | RISER DO NOT CORRELATE W/THE FLOOR PLAN. | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2000-10-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2000-10-20 |
Time |
13:51 |
Rev Time |
3.00 |
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO | | | | 1)STRUCTURE LOCATED IN "AO" FLOOD ZONE | | ELEVATION CERTIFICATE IS REQUIRED. | | | | 2)PROVIDE SOIL COMPACTION TEST REPORT AT | | FIRST INSPECTION. | | | | 3)PLEASE PROVIDE JOB/SITE LOCATION ON | | SPACE PROVIDED WHEN SUBMITTING SITE | | SPECIFIC PRODUCT APPROVAL FORMS AND HAVE | | ENGINEER/ARCHITECT PROVIDE THEIR NAME, | | ADDRESS AND REGISTRATION NUMBER LEGIBLY | | PRINTED ON FORM ALONG WITH WET SIGNATURE | | DATE AND RAISED SEAL. | | | | 4)PROVIDE PRODUCT APPROVALS FOR SLIDING | | GLASS DOORS. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2000-10-04 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2000-10-04 |
Time |
12:32 |
Rev Time |
4.00 |
Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED | | SEE PLAN REVIEW FOR PERMIT # 00090066 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-09-11 |
Time |
10:15 |
Rev Time |
0.15 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|