Plan Review Details - Permit 00081560
Plan Review Stops For Permit 00081560
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-29 Cont ID  
Sent By mcarsill Date 2000-08-29 Time 16:11 Rev Time 0.00
Received By mcarsill Date 2000-08-29 Time 16:11 Sent To  
Notes
2001-01-08 00:00:001) SMOKE DETECTORS TO BE INSTALLED A
 MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 2) WHEN ACTIVATED, THE FIRE ALARM SYSTEM
 IS TO BE AUDIBLE THROUGHOUT.
 3) IF BUILDING IS FIRE SPRINKLER
 PROTECTED, THEN FLOW AND TAMPER
 SWITCHES ARE TO BE SUPERVISED AND BE
 MONITORED.