Plan Review Details - Permit 00081232
Plan Review Stops For Permit 00081232
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2001-03-07 Cont ID  
Sent By jwitmer Date 2001-03-07 Time 14:31 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-07 00:00:00REVISIONS FEB 23/01:
 THE REVISION OF THE PARKING PLAN INDI-
 CATES THE RELOCATED HANDICAPPED PARKING.
 THE FL ACCESSIBILITY CODE 4.6.3: EACH
 PARKING SPACE MUST BE NO LESS THAN 12
 FEET WIDE. PARKING ACCESS AISLES MUST BE
 5'-0" WIDE, AND MUST BE PART OF THE
 ACCESSIBLE ROUTE TO THE BUILDING OR
 FACILITY ENTRANCE. TWO ACCESSIBLE
 SPACES MAY SHARE A COMMON ACCESS AISLE.
 THE ACCESS AISLE SHALL BE DIAGONALLY
 STRIPED TO DESIGNATE IT AS A NON-PARKING
 ZONE.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2001-03-01 Cont ID  
Sent By lmartine Date 2001-03-01 Time 11:37 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-02 00:00:00REVISION COMMENTS
  
 WATER HEATER SHED REVISION NOT APPROVED.
 TYPE VI CONSTRUCTION IS NOT PERMITTED
 INTHE CITY FIRE DISTRICT.
 HISTORICAL APPROVAL IS REQUIRED FOR ANY
 EXTERIOR CHANGES TO THE APPROVED PLANS.
 VERIFY ROOF COVER SHALL BE CLASS A OR B
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2001-02-09 Cont ID  
Sent By hpiskura Date 2001-02-09 Time 14:13 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-02-09 00:00:00STAIR SHOP DWG OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2001-01-22 Cont ID  
Sent By hpiskura Date 2001-01-22 Time 09:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-22 00:00:00THE STAIR SHOP DRAWINGS BY AA GARGIULO
 DATED 1/12/01 DO NOT COMPLY WITH SBC
 1015.2 AND SBC 1015.3 GUARD RAILS, AS
 TO HEIGHT AND RAIL INTERMEDIATE SPACING.
  
 ALSO, THE 7 - 11 RISE RUN RATIO WILL NOT
 WORK IN THE 9' - 6" RUN SHOWN FOR THE
 FLIGHT.PLEASE REVISE AS NECESSARY.
  
 HAROLD PISKURA PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-01-03 Cont ID  
Sent By jwitmer Date 2001-01-03 Time 13:41 Rev Time 0.15
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS: PASSED COMMENTS FOR REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2001-01-03 Cont ID  
Sent By jwitmer Date 2000-12-22 Time 15:55 Rev Time 0.15
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1:HANDICAPPED ACCESSABLE ROOMS BUILD "B"
 SHEET A4: FLORIDA ACCESSABLITY CODE
 A:9.1.3 SLEEPING ACCOMMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS SHALL
 COMPLY WITH 9.3 VISUAL ALARMS, NOTIF-
 ICATION DEVICES & TELEPHONES.
 B:9.1.5 IN ADDITION TO THE REQUIRED
 SLEEPING ROOMS REQUIRED 9.1.5 REQUIRES
 AT LEAST ONE SLEEPING ROOM OR SUITE
 THAT COMPLIES WITH THE REQIUREMENTS OF
 9.3 VISUAL ALARMS,NOTIFICATION DEVISES
 & TELEPHONES.
 C:4.13.5 DOORS/CLEAR WIDTH: DOORWAYS
 SHALL HAVE A CLEAR OPENING OF 32" WITH
 THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE
 OPPOSITE STOP.
 D:4.13.6 DOORS MANEUVERING CLEARENCES AT
 DOORS.MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE SHOWN IN FIG.
 25. THE FLOOR OR GROUND AREA WITHIN
 THE REQUIRED CLEARENCES SHALL BE LEVEL
 AND CLEAR.
 E:9.2.2REQUIREMENTS FOR ACCESIBLE UNITS,
 SLEEPING ROOMS AND SUITES.MINIMUM
 REQUIREMENTS:AN ACCESIBLE UNIT SHALL
 BE ON AN ACCESIBLEROUTE COMPLYING
 WITH 4.3, SHOW ON THE FLOOR PLAN THE
 ELEMENTS (BED, CABINETS,DRAWER SPACE
 CLOSETS & TELEPHONES).
 2:BEVERAGE AREA : 5.2 COUNTERS & BARS;
 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34" IN HEIGTH FOR
 CONSUMPTION BY THE CUSTOMERS SEATED ON
 STOOLS OR STANDING AT TTHE COUNTER, A
 PORTION OF THE MAIN COUNTER WHIICH IS
 60" IN LENGTH MINIMUM SHALLBE PROVIDED
 IN COMPLIANCE WITH 4.32OR SERVICE
 SHALL BE AVAILABLE AT ACCESSIBLE TABLE
 WITH IN THE SAME AREA.
 3:LOBBY TELEPHONE TO COMPLY WITH FL. ACC
 CODE 4.31 TELEEPHONES.
 4:LOBBY DOORS CLOUDED AREA: SHALL COMPLY
 WITH FL ACC CODE 4.13.5 CLEAR WIDTH OF
 32".PLAN CALLS FOR2'-8" DOOR (2).
 NONCOMPLIANCE.
 5:LOBBY DOORS AND GLAZED OPENING. SBC
 2405.2 SAFETY GLASS REQUIRED.
 6:SBC 1006.2.4 EXTERIOR STAIRS SHALL BE
 SEPERATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE RESIS-
 TANCE RATING OF NOT LESS THAN 1 HR.
 WITH FIXED OR SELF CLOSING OPENING PRO
 TECTIVES AS REQUIRED FOR ENCLOSED
 STAIRS. THIS PROTECTION SHALL EXTEND
 VERTICALLY FROM THE GROUND TO A POINT
 10 FT ABOVE THE TOPMOST LANDING OR THE
 ROOF LINE, WHICHEVER IS LOWER, AND
 HORIZONTALLY 10 FT FROM EACH SIDE OF
 THE STAIRWAY. OPENINGS WITHIN THE 10
 FT HORIZONTAL EXTENSION OF THE PRO-
 TECTED WALLS BEYOND THE STAIRWAY SHALL
 BE EQUIPPED WITH FIXED 3/4-HOUR
 ASSEMBLIES. THE GAS HEATER /METER MUST
 NOT BE LOCATED BENEATH THE STAIRWELL.
 7:STANDARD BUILD CODE:1606.4/1707.4.1
 W.P.B. AMENDMENTS-EXTERIOR WINDOWS AND
 DODR ASEMBLIES REPLACED WILL REQUIRE
 PRODUCT APPROVAL REPORTS(2) FOR IMPACT
 FROM WIND BORN DEBRIS, LARGE MISSLE
 IMPACT TESTING. GLAZED OPENINGS THAT
 DO NOT MEET THIS TESTING WILL NEED
 TESTED SHUTTERS THAT DO HAVE APPROVED
 TESTING AND ACCOMPINING REPORTS. WE
 ACCEPT DADE COUNTY PRODUCT APP. OR
 S.B.C.C.I. REPORT.
 WE WILL ALSO NEED INFORMATION ON THE
 1-HR RAED WINDOW, AND ON THE 2ND FL
 DOOR AS WELL AS THE 1ST FLOOR DOOR
 DIRECTLY BELOW THE 2ND FLOOR LANDING.
 8:104.2.2: ON THE 2ND FLOOR PLAN THERE
 IS A BEDROOM THAT HAS NO MEANS OF
 EGRESS NOR DOES IT SHOW THE WINDOW,
 THIS MAY ALSO REQUIRE A 1-HR FIRE
 RATING IF LOCATED ON THE WALL OF THE
 EXTERIOR STAIRS.
 9:104.2.2: THE PLANS DO NOT SHOW WHERE
 THE HANDICAPPED PARKING AND PASSENGER
 LOADING ZONES WILL BE?
  
 BUILDING PLAN REVIEW:
 JIM WITMER
 (561) 659-8096 EX 8412
 NOTES:
 IF YOU HAVE ANY QUESTIONS,PLEASE CALL.
 PLEASE RETURN THE REVIEWED PAGES WITH
 THE CORRECTIONS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.THANK YOU!

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-28 Cont ID  
Sent By hpiskura Date 2000-09-28 Time 10:03 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-03-01 Cont ID  
Sent By dpalmer Date 2001-03-01 Time 17:44 Rev Time 0.00
Received By dpalmer Date 2001-03-01 Time 17:42 Sent To  
Notes
2001-03-01 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 COMING IN SHOWING NEW SERVICE?
 PLEASE NOTE THAT THE VALUE ON PERMIT
 APPLICATION FOR ELECTRICAL MUST BE
 INCREASED TO ACCOMADATE.
  
 2)NOTE: PLEASE NOTE THERE IS NOT ENOUGH
 INFORMATION FOR REVIEW OF NEW SERVICE.
 PLEASE SUBMIT A ONE LINE DIAGRAM/ ELEC
 RISER DIAGRAM. NEED ALOT MORE DETAIL ON
 EQUIPMENT. WIRE SIZES/CONDUIT SIZES
 ECT ECT.PANEL SCHEDULES?
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE NOTE LIGHT FIXTURE IN
 CLOSET
 NOT PERMITTED AS SHOWN PER 410-8.
  
 5)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH PANEL
 SCHEDULS.215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-12-29 Cont ID  
Sent By dpalmer Date 2000-12-29 Time 15:56 Rev Time 0.00
Received By dpalmer Date 2000-12-29 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 10:48 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 10:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-02-27 Cont ID  
Sent By mcarsill Date 2001-02-27 Time 16:10 Rev Time 0.00
Received By mcarsill Date 2001-02-27 Time 16:10 Sent To  
Notes
2001-02-27 00:00:001) ALL WINDOWS WITHIN 10 FEET OF THE
 REQUIRED EXTERIOR EXIT STAIR FROM THE
 SECOND FLOOR MUST BE FIRE RATED.
 ACCORDING TO NFPA 80, THE STANDARD FOR
 FIRE DOORS AND WINDOWS, THE FOLLOWING
 REQUIREMENTS ARE TO BE MET FOR
 INSTALLATION.
 A) FIRE WINDOW FRAMES SHALL BE LABELED.
 B) ONLY LABELED FIRE PROTECTION RATED
 GLAZING MATERIAL SHALL BE USED IN
 WINDOWS.
 C) EACH INDIVIDUAL GLAZING UNIT SHALL
 BE IDENTIFIED WITH A LABEL. THE LABEL
 SHALL BE VISIBLE AFTER INSTALLATION.
 2) PLEASE PROVIDE A DRAWING OF THE
 STAIRS IN RELATION TO THE WINDOWS THAT
 WILL BE FIRE RATED. ALSO PLEASE PROVIDE
 INFORMATION ON WINDOW SIZES THAT WILL
 BE PROTECTED BY FIRE RATED GLASS.
 PLEASE BE ADVISED THAT GLASS BLOCKS MAY
 BE USED BUT THAT THEY MUST BE LABELED.
  
 APPROVED PROVISO:
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-12-28 Cont ID  
Sent By mcarsill Date 2000-12-28 Time 14:22 Rev Time 0.00
Received By mcarsill Date 2000-12-28 Time 14:22 Sent To  
Notes
2001-01-08 00:00:001) THE SECOND FLOOR EXIT STAIR LOCATED
 AT THE WEST BUILDING IS TO BE PROPERLY
 FIRE SEPARATED IN ACCORDANCE WITH FIRE
 CODE REQUIREMENTS. THIS PROTECTION SHALL
 EXTEND AT LEAST 10 FEET UPWARD OR TO THE
 ROOFLINE, WHICHEVER IS LOWER, AT LEAST
 10 FEET HORIZONTALLY AND DOWNWARD AT
 GROUND LEVEL. (FIRE ESCAPE STAIR)
 2) EACH SLEEPING ROOM SHALL BE PROVIDED
 WITH AN ELECTRIC POWERED SMOKE DETECTOR.
 3) BUILDINGS ARE TO BE INSPECTED BY
 FIRE RESCUE BEFORE ANY APPROVALS ARE
 GRANTED FOR OCCUPANCY.
  
 CAPATIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910
  
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-25 Cont ID  
Sent By mcarsill Date 2000-08-25 Time 09:23 Rev Time 0.00
Received By mcarsill Date 2000-08-25 Time 09:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-03-19 Cont ID  
Sent By pkrauss Date 2001-03-19 Time 13:08 Rev Time 0.33
Received By pkrauss Date 2001-03-19 Time 13:07 Sent To  
Notes
2001-03-19 00:00:00****************PROVISO*****************
  
 AS PER NFPA 90A 4-4.4.3, FAN SHUTDOWN
 BY DUCT SMOKE DETECTOR SHALL HAVE
 NOTIFICATION TO HORN/STROBE ALARM IN
 NORMALLY OCCUPIED AREAS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-11-17 Cont ID  
Sent By ndenmark Date 2000-11-17 Time 15:16 Rev Time 0.50
Received By ndenmark Date 2000-11-17 Time 15:16 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.DUCT RETURN AIR COMPLETELY TO UNITS
 2. NFPA 90 A 4-4.4 REQUIRES FAN SHUT
 DOWN BY DUCT SMOKE DETECTOR TO BE TIED
 TO BLDG FIRE ALARM SYSTEM IF ONE EXISTS
 OR TIED TO HORN AND STROBE FOR NOTIFICA-
 TION IF NO BLDG FIR ALARM EXISTS.
 ALL AHU EQUIPMENT UNDER 2000CFM BUT
 SERVING AREAS USED FOR EGRESS SHALL
 HAVE FAN SHUT DOWN BY DUCT SMOKE DETECTO
 PER 1997 SMC 406.2
 3. BATHROOM EXHAUST TO COMPLY WITH 1997
 SMC 503.3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-11-07 Cont ID  
Sent By ndenmark Date 2000-11-07 Time 06:50 Rev Time 0.50
Received By ndenmark Date 2000-11-07 Time 06:50 Sent To  
Notes
2001-01-08 00:00:00************DENIED**********************
 1. 1997 SMC 609.1.1 REQUIRES PUBLIC EXIT
 CORRIDORS IN HOTELS, HOSPITALS, INSTITU-
 TIONS, AND SIMILAR OCCUPANCIES SHALL NOT
 BE USED AS PLENUMS FOR ADJOINING AREAS.
 PROVIDE INFORMATION ON RETURN AIR PATH
 TO AIR HANDLING EQUIPMENT TO COMPLY WITH
 THIS REQUIREMENT.
  
 NOTE: NFPA 90A 4-4.4 REQUIRES FAN SHUT
 DOWN BY DUCT SMOKE DETECTOR TO BE TIED
 TO BUILDING FIRE ALARM SYSTEM IF ONE
 EXISTS OR TIED TO HORN AND STROBE FOR
 NOTIFICATION IF NO BUILDING FIRE ALARM
 SYSTEM EXISTS.
 ALL AIR HANDLING EQUIPMENT OVER 2000 CFM
 WILL REQUIRE FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR AND 1997 SMC 406.2 REQUIRES ALL
 EQUIPMENT SERVING AREAS USED FOR EGRESS
 EVEN IF LESS THAN 2000 CFM HAVE FAN SHUT
 DOWN BY DUCT SMOKE DETECTOR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-09-09 Cont ID  
Sent By ndenmark Date 2000-09-09 Time 08:34 Rev Time 0.25
Received By ndenmark Date 2000-09-09 Time 08:24 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 BATHROOM EXHAUST TO MEET STANDARD MECH
 CODE (1997) 503.3

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-01-02 Cont ID  
Sent By jleech Date 2001-01-02 Time 15:27 Rev Time 0.75
Received By jleech Date 2001-01-02 Time 15:27 Sent To  
Notes
2001-01-08 00:00:00PROVISO;
  
 1.PAGE A-5 (HOT WATER HEATER AT WEST
 BUILDING) SHOW CALCULATIONS FOR
 COMBUSTION AIR AS REQUIRED BY STANDARD
 GAS CODE.
  
 2.SHOW TYPE LOCATION,SIZE AND TERMINA-
 TION OF GAS VENT AS REQUIRED BY SMC.
  
 3.SEPARATE PERMIT REQUIRED FOR GAS WORK.
 DRAWINGS REQUIRED WITH APPLICATION
 SHOWING LONGEST RUN AND BTU'S FOR
 EACH APPLIANCE.
  
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-29 Cont ID  
Sent By tlarge Date 2000-10-29 Time 08:12 Rev Time 0.33
Received By tlarge Date 2000-10-29 Time 07:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-20 Cont ID  
Sent By tlarge Date 2000-10-20 Time 18:59 Rev Time 0.75
Received By tlarge Date 2000-10-20 Time 18:59 Sent To  
Notes
2001-01-08 00:00:001)COMPLY W/ALL PREVIOUS COMMENTS.THE
 CORRECTIONS SHALL BE SHOWN ON THE PLANS.
 !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 RUN NEW BLUEPRINTS.
 CALL IF YOU HAVE QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-28 Cont ID  
Sent By tlarge Date 2000-08-28 Time 12:28 Rev Time 0.75
Received By tlarge Date 2000-08-28 Time 11:22 Sent To  
Notes
2001-01-08 00:00:00MIN.SIZE OF H.C.SHOWERS SHALL COMPLY W/
 FACBC SEC.9.1.2,FIG.#57.
  
 2)PIPES UNDER H.C.LAV.SHALL BE INSULATE
 -ED PER FACBC SEC.4.19.4.
  
 3)SUBMIT DETAILS/MOUNTING HEIGHTS FOR
 ALL HANDICAP FIXTURES/APPURTENANCES.
 INCLUDE BENCH. OCT.1997 EDITION.
  
 4)INDICATE IF ANY RENOVATIONS WILL BE
 DONE ON THE EAST BUILDING AND IF SO,
 SUBMIT PLANS.
  
 5)THE INDIRECT WASTE IN THE BAR AREA
 SHALL DISCHARGE ABOVE THE FLOOR SINK
 PER SPC SEC.804.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.