Plan Review Details - Permit 00081067
Plan Review Stops For Permit 00081067
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2001-02-06 Cont ID  
Sent By jwitmer Date 2001-02-05 Time 12:10 Rev Time 0.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-02-05 00:00:00IMPACT FEES TO BE PAID BEFORE ISSUANCE
 02/05/01 JIM WITMER, SEND TO ZONING FOR
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2001-01-22 Cont ID  
Sent By jwitmer Date 2001-01-22 Time 10:49 Rev Time 2.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-22 00:00:00BUILDING PLAN REVIEW:
 1)-FL. S.S. 481 TO HAVE ARCHITEECT TO
 SIGN/ SEAL & DATE DRAWINGS.
 2)- 1997 FL ENERGY EFFICIENCY CODE 400.0
 REQUIRES ENERGY CODE COMPLIANCE DOCUMENT
 3)- SBC 1804.2 SOILS REPORT MINIMUM
 SOIL BEARING.
 4)- SHEET A-3 DETAIL A REQUIRES A VAPOR
 BARRIER AT SLAB.SBC 103.7..3.7 TREATED
 SOIL SHALL BE COMPLETELY COVERED WITH A
 VAPOR BARRIER FROM THE SUN & RAIN WITHIN
 2 HRS. OF CHEMICAL APPLICATION.
 5)- SHEET A-3 DETAIL B WILL ALSO REQUIRE
 ADDITIONAL TERMITE CHEMICAL SOIL TREAT-
 MENTS SHALL BE APPLIED UNDER ALL EXTER-
 IOR CONCRETE ON GRADE THAT ARE WITHIN ON
 ONE FOOT OF THE PRIMARY STRUCTURE SIDE-
 WALLS.SBC 103.7.3.5
 6)- SBC 1606.2.6.2- COMPONENTS & CLAD-
 DING, ALL GLAZED OPENINGS WILL REQUIRE
 TESTING 16606.4.1/1707.4.1 FOR LARGE
 MISSLE RESISTANCE, IF THE PRODUCT WASN'T
 TESTED STORM SHUTTERS WILL BE REQUIRED
 MEETING THIS REQUIREMENT. A SHUTTER
 SCHEDULE FOR ATTACHMENT AND A DIAGRAM OF
 OPENINGS TYING THE 2 TOGETHER.ALL EXTER-
 IOR DOOR OPENINGS WUOLD ALSO HAVE TO
 HAVE PROOF OF TESTING.
 7)- ROOFING SBC 1606.2.6.2- WILL ALSO
 REQUIRE TESTING REPORTS, DADE COUNTY OR
 SBCCI REPORT WILL BE REQUIRED,2 COPIES.
 8)- SBC 104.2.2- ADDITIONAL INFORMATION
 WILL BE REQUIRED FOR THE CUPOLA, IS THIS
 MEETING THE REQUIREMENTS OF 1606.2D FOR
 WIND? TEST RESULTS SHOWING POSITIVE &
 NEGATIVE PRESSURES TESTED FOR?
 9)- AWNINGS REQUIRE A SEPERATE PERMIT,
 THEY WILL HAVE TO HAVE PROOF OF FIRE
 RETARDANT FABRIC, FRAMES TO HAVE ENGIN-
 EERING.
 10)- FIRESTOPPING- SBC 2305.1.4.1-
 FIRE STOPPING WILL BE REQUIRED AT FLOOR
 AND CEILING LINE.
 11)-SBC 2309.6 ATTIC ACCESS REQUIRED.
 12)- SBC 803.3 REQUIRES A MINIMUM FINISH
 ROOM SCHEDULE IN ACCORDANCE WITH ASTM -
 E-84, WITH FLAMESPREAD & SMOKE DEVELOP-
 MENT.
 13)- SBC 104.2.2- ADD. INFORMATION RE-
 QUIRED, DROPPED CEILING, WHAT MATERIAL
 IS THE DROPPED CEILING MADE OF? HOW
 OFTEN IS THE CEILING SUPPORTED AND BY
 WHAT MEANS IS THE CEILING SUPPORTED?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659- 8096 EX 8412

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2001-02-02 Cont ID  
Sent By dpalmer Date 2001-02-02 Time 07:07 Rev Time 0.00
Received By dpalmer Date 2001-02-02 Time 07:07 Sent To  
Notes
2001-02-02 00:00:00*********** NOT REVIEWED ***************
  
 1)NOTE: ELECTRICAL PLANS WERE NOT
 CORRETED AND PER REQUEST BY
 ARCH/CONTRACTOR
 ELECTRICAL DRAWING ARE TO BE PULLED
 FROMREVIEW.
 ALL NEW ELECTRICAL PLANS ARE TO BE
 SUBMITTED BY ELECTRICAL CONTRACTOR BEFOR
 E ANY ELECTRICAL PERMIT IS ISSUED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2001-01-19 Cont ID  
Sent By dpalmer Date 2001-01-19 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2001-01-19 Time 15:23 Sent To  
Notes
2001-01-19 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION ON
 RISER DIAGRAM. WHERE IS THIS SERVICE
 LOCATED? WHAT IS THE FEED FROM PANEL
 SHOWN AS 1 1/2 CONDUIT W/3-#2`S??
 PLEASE CLARIFY EQUIPMENT GROUND BETWEEN
 MAIN AND PANEL.
  
 2)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANSAND CORRELATE WITH
 SUBMITTED PANEL SCHEDULE.
  
 3)NOTE: PLEASE SHOW A/C UNIT LOCATIONS
 WITH REQ`D DISCONNECT.
  
 4)NOTE: PLEASE NOTE THAT NEW BLDG. STEEL
 NEEDS TO BE SHOWN AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. PER 250-50
  
 PLEASE SUBMTI THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2001-02-05 Cont ID  
Sent By mcarsill Date 2001-02-05 Time 09:21 Rev Time 0.00
Received By mcarsill Date 2001-02-05 Time 09:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2001-01-18 Cont ID  
Sent By mcarsill Date 2001-01-18 Time 11:15 Rev Time 0.00
Received By mcarsill Date 2001-01-18 Time 11:15 Sent To  
Notes
2001-01-18 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 2) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS.
 3) STORAGE ROOM TO BE AT LEAST ONE HOUR
 FIRE RATED AND BE EQUIPPED WITH A 45
 MINUTE FIRE DOOR. A DOOR CLOSER IS
 REQUIRED.
 4) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 5) INTERIOR DOOR TO MEETING ROOM TO
 SWING TOWARDS STORAGE ROOM WALL.
 6) AWNINGS ARE TO BE FIRE RETARDANT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2001-01-19 Cont ID  
Sent By ndenmark Date 2001-01-19 Time 10:58 Rev Time 0.25
Received By ndenmark Date 2001-01-19 Time 10:58 Sent To  
Notes
2001-01-19 00:00:00NO MECHANICAL INFORMATION INCLUDED,
 PROVIDE MECHANICAL PLANS AT TIME OF
 PERMIT APPLICATION PRIOR TO ANY MECH
 WORK BEING STARTED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2001-01-17 Cont ID  
Sent By jleech Date 2001-01-17 Time 13:48 Rev Time 0.50
Received By jleech Date 2001-01-17 Time 13:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2001-02-06 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 09:21 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED LEVEL 1 SITE PLAN REVIEW