Plan Review Details - Permit 00080968
Plan Review Stops For Permit 00080968
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-31 Cont ID  
Sent By mcarsill Date 2000-08-31 Time 11:10 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00RECEIVED INFORMATION FROM LANGER
 ELECTRIC EMPLOYEE GENE FLATAU.
 1) FIRE ALARM SYSTEM WHEN ACTIVATED
 IS TO BE AUDIBLE THROUGHOUT SPACE.
 2) FIRE ALARM SYSTEM TO BE CLASS A OR
 ADDRESSABLE.
 3) FIRE ALARM SYSTEM WHEN ACTIVATED IN
 CHEESECAKE FACTORY IS TO ACTIVATE BASE
 BUILDINGS FIRE ALARM SYSTEM.
 4) HOOD FIRE EXTINGUISHING SYSTEM WHEN
 ACTIVATED IS ALERT THE FIRE ALARM SYSTEM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-22 Cont ID  
Sent By mcarsill Date 2000-08-22 Time 12:46 Rev Time 0.00
Received By mcarsill Date 2000-08-22 Time 12:45 Sent To  
Notes
2001-01-08 00:00:001) MANUAL PULL STATION IN CUT SHEETS
 MAY NOT MEET CITY PLACE STANDARDS FOR
 DEVICE TYPE AND STYLE.
 2) NO FLOOR PLAN WITH FIRE ALARM DEVICES
 SHOWN IN SUBMITTAL PACKAGE.
 3) WHEN ACTIVATED THE FIRE ALARM SYSTEM
 IS TO BE AUDIBLE THROUGHOUT.
 4) FIRE ALARM SYSTEM TO BE MONITORED BY
 A LICENSED UL LISTED FIRE ALARM COMPANY
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 5) FIRE ALARM SYSTEM FOR CHEESECAKE
 FACTORY IS TO BE CONNECTED TO THE BASE
 BUILDING FIRE ALARM SYSTEM IN A RETAIL.
 6) PLEASE PROVIDE FLOOR PLAN WITH
 FIRE ALARM DEVICES SHOWN FOR REVIEW
 PURPOSES.