Plan Review Details - Permit 00080150
Plan Review Stops For Permit 00080150
Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-03 Cont ID  
Sent By cthirben Date 2000-08-03 Time 07:42 Rev Time 1.00
Received By cthirben Date 2000-08-04 Time 14:03 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 PROVIDE CFM VALUE FOR EACH DROP ON THE
 NEW SYSTEM.
 REQUIRE AN EXHAUST FAN AS PER 1997 SMC
 503.3.1....
 INDICATE THE CONDENSATE LINES AND CON-
 CRETE SLAB FOR CONDENSER UNIT..