Plan Review Details - Permit 00071187
Plan Review Stops For Permit 00071187
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-10-24 Cont ID  
Sent By drunnels Date 2000-10-24 Time 08:40 Rev Time 1.00
Received By drunnels Date 2000-10-24 Time 08:38 Sent To  
Notes
2001-01-08 00:00:00REVISION 10/18/2000

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-08-28 Cont ID  
Sent By drunnels Date 2000-08-28 Time 11:36 Rev Time 1.00
Received By drunnels Date 2000-08-28 Time 11:35 Sent To  
Notes
2001-01-08 00:00:00HOLD FOR FIRE SPRINKLER PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-25 Cont ID  
Sent By drunnels Date 2000-08-25 Time 09:23 Rev Time 1.00
Received By drunnels Date 2000-08-25 Time 09:23 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO******************
 1.STOREFRONT TO BE UNDER SEPERATE PERMIT
 2.SIGNS TO BE UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By drunnels Date 2000-08-08 Time 11:29 Rev Time 1.00
Received By drunnels Date 2000-08-08 Time 11:28 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT LETTER FROM SPECIAL CONTRACTOR
 RELEASING SPACE.
 2. SUBMIT PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR WINDOWS AND DOORS
 ON STOREFRONT.METRO DADE COUNTY OR SBCCI
 3. BUILDING IS TYPE 2 ALL WOOD USED IN
 FRAMING SHALL BE F.R.T. TO COMPLY WITH
 1997 SBC CHAPTER 6&7
 4. SUBMIT DETAIL ON DEMIZING WALLS
 SHOWING UL#.ALL FIRE RATED TENANT
 SEPERATION TO BE COMPLETE PRIOR TO C.O.
 BEING ISSUED.
 5. SHEET A-8 DETAIL REF.S.F.B.C.SHOULD
 REF. 1997 SBC
 6. SHEET A-9 REF. ADA, SHOULD REF.
 FLORIDA HANDICAP CODE.
 7. SIGNS TO BE UNDER SEPERATE PERMIT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 10:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By dpalmer Date 2000-08-04 Time 08:11 Rev Time 0.00
Received By dpalmer Date 2000-08-04 Time 08:11 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION ON
 FEEDER SIZES. ONE SHOWS 3/0 AND THE
 OTHER 1/0. PANEL "A"
  
 2)NOTE;PLEASE HAVE PANEL REFLECT MCB AS
 REQ` BY NEC.
  
 3)NOTE: PLEASE INCLUDE SHOW WINDOW OUT-
 -LETS AS PER 210-62 AND FIGURE THE LOAD
 INTO LOAD CALCS FROM 220-12B.
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (LIGHTING)
  
 4)NOTE: A DISCONNECT IS SHOWNBUT NO
 INFORMATION IS GIVEN? PLEASE PROVIDE
 INFORMATION ON THIS DISCONNECT ON
 RISER DIAGRAM.
  
 5)NOTE:PLEASE PROVIDE AIC RATING FOR
 THE DISCONNECT.110-9
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATIONB
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372
 ELECTRICAL PLAN REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-25 Cont ID  
Sent By mcarsill Date 2000-08-25 Time 09:56 Rev Time 0.00
Received By mcarsill Date 2000-08-25 Time 09:56 Sent To  
Notes
2001-01-08 00:00:001) PROVIDE FIRE ALARM SYSTEM PLANS
 FOR FIRE ALARM DEVICES SHOWN ON PLANS.
 A SEPARATE PLAN AND PERMIT IS REQUIRED.
 PROVIDE CUT SHEETS ON DEVICES PLANNED
 FOR USE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 12:40 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS.
 2) EXITING PERMITTED THROUGH STOCKROOM
 PROVIDED THE FOLLOWING CONDITIONS ARE
 MET, NOT MORE THAN 50 PERCENT OF THE
 EXIT ACCESS IS PROVIDED THROUGH
 STOCKROOM, AN AISLE OF AT LEAST 44"
 WIDE IS PRESENT, THIS 44" AISLE TO BE
 MAINTAINED, AND DOOR LEADING TO
 STOCKROOM CANNOT BE LOCKED.
 3) INTERIOR FINISH ON WALLS AND CEILINGS
 TO BE CLASS A OR B.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-24 Cont ID  
Sent By ndenmark Date 2000-08-24 Time 13:58 Rev Time 0.33
Received By ndenmark Date 2000-08-24 Time 13:58 Sent To  
Notes
2001-01-08 00:00:00MECH REVISIONS ADDRESS PRIOR COMMENTS
 ON MECH PLAN REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By ndenmark Date 2000-08-04 Time 10:14 Rev Time 0.50
Received By ndenmark Date 2000-08-04 Time 10:14 Sent To  
Notes
2001-01-08 00:00:00*************DENIED********************
 1. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2. DUCT SMOKE DETECTOR TO BE TIED TO
 BLDG FIRE ALARM PER 1996 NFPA 90A 4-4.4.
 3. SENSIBLE CAPACITY OF SELECTED AHU
 SHALL NOT EXCEED 20% OF THE CALCULATED
 SENSIBLE LOAD.(PGAL)
 4. SUBMIT ENERGY CALCULATION FORM 400B.
 (PGAL)
 5. INDICATE LOCATION OF REQUIRED FIRE
 DAMPERS PER 1997 SMC 610 (PLAN INDICATES
 RATED CEILING SEE SHEET A-8)

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-24 Cont ID  
Sent By tlarge Date 2000-08-24 Time 16:19 Rev Time 0.65
Received By tlarge Date 2000-08-24 Time 16:19 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 BENCH IN HANDICAP DRESSING ROOM SHALL BE
 LOCATED ALONG WALL W/LONGER DIMENSION.
 FACBC SEC.4.35.4.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By tlarge Date 2000-08-03 Time 18:18 Rev Time 0.50
Received By tlarge Date 2000-08-03 Time 18:09 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SQ.FOOTAGE OF SPACE TO ENSURE
 COMPLIANCE W/TABLE 407 OF SPC.
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A),4.15.
  
 3)HANDICAP DRESSING ROOM SHALL COMPLY W/
 FACBC 4.35.BENCH SHALL BE LOCATED ALONG
 WALL WITH THE LONGER DIMENSION.
  
 4)HANDICAP TOILET ROOM SHALL BE
 INDELIBLY POSTED FOR THE INTENDED USE
 PER FACBC SEC.4.1.2(7),4.1.3(16)(A).
  
 5)ACCESSIBLE TOILET ROOMS SHALL BE
 LOCATED ON AN ACCESSIBLE ROUTE.
 ACCESSIBLE ROUTE SHALL BE CLEARLY
 DEFINED ON THE PLANS.FACBC SECS.4.1.3
 (11),4.2.1,4.3.1,4.3.2(3),4.3.3.
  
 6)TOILET FACILITIES SHALL BE AVAILABLE
 TO PATRONS WITHOUT RESTRICTION DURING
 NORMAL OPERATING HOURS.SPC SEC.407.2.2.
  
 7)FLUSH CONTROLS FOR WATER CLOSET SHALL
 BE LOCATED ON THE WIDE SIDE OF THE
 TOILET.FACBC SEC.4.16.5.