Plan Review Stops For Permit 00070815 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-09-11 |
Time |
15:09 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-09-11 |
Time |
15:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** PROVISO **************** | | STOREFRONT UNDER SEPERATE PERMIT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-08-30 |
Time |
14:12 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-08-30 |
Time |
12:57 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1.SUBMIT FIRE SPRINKLER PLANS ADN PERMIT | | APPLICATION. | | | | *****************PROVISO**************** | | STOREFRONT TO BE ISSUED UNDER SEPERATE | | PERMIT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-07-31 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
drunnels |
Date |
2000-07-31 |
Time |
09:19 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | | | | | | | | | 1. PROVIDE LETTER FROM SPECIAL INSPECTOR | | 2. PROVIDE PRODUCT APPROVAL SHEETS ON | | EXTERIOR GLAZING AS PER METRO DADE | | COUNTY OR 1997 SSTD 12-97 | | 3. FIRE SPRINKLER PERMIT MUST BE ISSURED | | PRIOR TO ISSURANCE OF BUILDING PERMIT | | 4. 1997 SBC | | A)ALL LUMBER IN FRAMING MUST BE FIRE | | RETARDANT TREATED WOOD CHAPTERS 6&7 | | B)SHEET 1D-8 REMOVE STEP-UP TO SEATING | | OR MAKE HANDICAP ACCESSIBLE. | | C)NO SECOND EXIT, EXIT THROUGH KITCHEN | | NOT ALLOWED | | 5. 1997 FLORIDA HANDICAP CODE | | A)PROVIDE DETAILS SHOWING TURNING | | RADIUS IN RESTROOMS | | B)PROVIDE DETAIL SHOWING SLOPE ON ALL | | RAMPS | | 6. ADDRESS FOR BUILDING "B" IS 700 | | SOUTH ROSEMARY NOT 701S. ROSEMARY |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-07-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-07-24 |
Time |
06:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-07-24 |
Time |
06:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** PROVISO *************** | | | | 1)NOTE: PLEASE SEE THE REQ`MENTS PER NEC | | FOR INSTALLATION OF TRANSFORMER. 450-21 | | | | | | | | | | | | | | | | | | PLEASE SUBMIT FOR REVIEW BEFORE ANY | | ROUGH ELECTRICAL INSPECTION IS CALLED IN | | IF THERE ARE ANY QUESITONS PLEASE CALL | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2000-09-05 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-09-05 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-09-05 |
Time |
09:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-08-10 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | THIS REVIEW OCCURRED AFTER DEAN RUNNELS | | OF BUILDING AND ZONING MET WITH | | REPRESENTATIVES FOR MARKS ON THE PARK, | | AUGUST 10, 2000. | | 1) OCCUPANT LOAD TO BE DETERMINED BY | | THIS OFFICE. | | 2) DURING THE MEETING THEY ADVISED THAT | | CITY PLACE PARTNERS IS GOING TO | | PROVIDE INFORMATION SO THAT FIRE ALARM | | EQUIPMENT CAN BE INSTALLED WITHIN THE | | SPACE. | | 3) AN ADDITIONAL ILLUMINATED EXIT SIGN | | TO BE INSTALLED TO DIRECT PERSONS TO | | THE NEW FIRE RATED EXIT HALLWAY. | | 4) PORTABLE FIRE EXTINGUISHERS SHOWN ON | | RED-LINED DRAWING TO BE AT LEAST 5LBS | | WITH A MINIMUM OF 2A10BC FIRE RATING. | | 5) PROVIDE SEPARATE PLANS AND PERMIT FOR | | HOOD, DUCT AND EXTINGUISHING SYSTEM. | | 6) ACCORDING TO THE LETTER WRITTEN TO | | DEAN RUNNELS OF B&Z, FIRE SPRINKLER | | DRAWINGS ARE EXPECTED WITHIN THE WEEK. | | APPROVED PROVISO |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-07-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-07-27 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR | | HYDRAULIC CALCULATIONS PROVIDED IN | | DRAWINGS. | | 2) GAS INSTALLATION TO COMPLY WITH | | NFPA 54. | | 3) PROVIDE COMPLETE SHOP DRAWINGS FOR | | THE INSTALLATION OF THE HOOD, DUCT | | AND EXTINGUISHING SYSTEM. WET CHEMICAL | | EXTINGUISHING SYSTEMS ARE ONLY SYSTEMS | | PERMITTED. | | 4) ALL DOORS USED FOR EXITING TO BE | | EQUIPPED WITH PANIC HARDWARE. FIRE EXIT | | HARDWARE TO BE INSTALLED ON FIRE DOORS. | | 5) PROVISIONS TO BE MADE FOR AT LEAST | | TWO HANDICAPPED PERSONS. | | 6) DEFINE WAITING AREA. WAITING AREAS | | CANNOT INTERFERE WITH EXITING. | | 7) MAIN ENTRY MUST BE CAPABLE OF | | PROVIDING EXITING FOR AT LEAST 50 | | PERCENT OF OCCUPANT LOAD. | | 8) DEFINE RAMPS AND STAIRS. ANY CHANGE | | IN ELEVATION LESS THAN 21" SHALL BE BY | | RAMPS. | | 9) EXPLAIN EXITING ROUTES. | | 10) PROVIDE FLAMESPREAD DOCUMENTATION ON | | BOOTHS AND BRANCHES. | | 11) SEAT COUNTS ON PAGE ID-1 AND ID-8 | | DO NOT MATCH. | | 12) EXPLAIN PLATFORMS. | | 13) HOW IS THE BASE BUILDING FIRE ALARM | | SYSTEM HEARD IN TENANT SPACE. | | 14) PORTABLE FIRE EXTINGUISHERS REQUIRED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-08-11 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-08-11 |
Time |
08:55 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-08-11 |
Time |
08:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-07-21 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-07-21 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-07-21 |
Time |
10:43 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO:******************************** | | 1.DUCT MATERIAL SCHEDULE REQUIRED. | | 2.PROVIDE ENERGY EFFICIENCY RATING PER | | FLORIDA EFFICIENCY CODE. | | 3.CLEARANCE OF EXHAUST AIR FROM OUTSIDE | | AIR INTAKE MIN. 10FT. PER 1997 SMC 506.1 | | NOTE:*********************************** | | SEPERATE PERMIT REQUIRED FOR HOOD, GAS, | | FIRE-SUPPRESSION SYSTEM, WALK-IN COOLER/ | | FREEZERS. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2000-09-11 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-11 |
Time |
14:46 |
Rev Time |
1.00 |
Received By |
tlarge |
Date |
2000-09-11 |
Time |
13:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2000-09-08 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-08 |
Time |
17:45 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-09-08 |
Time |
17:45 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)GAS SYSTEM SHALL BE SIZED ACCORDING TO | | THE APPLICABLE TABLE SHOWN ON THE PLANS. | | SGC 305.4. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
N |
Date |
2000-09-07 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-06 |
Time |
18:29 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-09-06 |
Time |
18:21 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | THIS REVIEW STEP IS NOT APPLICABLE. | | ENTERED IN ERROR.9/7/00.TKL. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2000-08-25 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-25 |
Time |
18:18 |
Rev Time |
2.00 |
Received By |
tlarge |
Date |
2000-08-25 |
Time |
17:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)SANITARY SYSTEM SHALL COMPLY W/SPC | | SEC.914.1 FOR CIRCUIT AND LOOP SYSTEM. | | | | 2)COMPLY W/SPC SEC.921 FOR HORIZONTAL | | COMBINATION WASTE AND VENT SYSTEM. | | | | 3)AN EMERGENCY SHUT-OFF VALVE IS REQD. | | ON THE GAS SYSTEM PER NFPA 96. | | | | | | 4)SUBMIT COPY OF GAS SIZING TABLE | | UTILIZED IN THE DESIGN OF THE GAS SYSTEM | | SGC SEC.301. | | | | 5)SUBMIT BTU LOAD OF EACH PIECE OF | | EQUIPMENT AND TOTAL BTU LOAD ON THE | | SYSTEM.A PROPER PLAN REVIEW CANNOT BE | | PERFORMED W/O THIS INFORMATION.SGC 301. | | | | SUBMIT PLUMBING AND KITCHEN PLAN FOR | | REVIEW.COUNTYWIDE AMENDMENTS TO SPC | | SEC.104.2.1. | | | | 6)PLANS SHALL BE COMPILED INTO COMPLETE | | SETS FOR REVIEW.COUNTYWIDE AMENDMENTS TO | | SPC.104.2.1. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2000-08-14 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-14 |
Time |
08:50 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-08-14 |
Time |
07:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)LAVATORIES IN RESTROOMS INFRINGE ON | | CLEAR FLOOR SPACE FOR WATER CLOSET. | | COMPLY W/FACBC SEC.4.17.3.FIGURE 30(A). | | | | 2)PLANS SHALL BE ROUTED TO DEPT.OF | | BUSINESS REGULATION FOR REVIEW AND | | APPROVAL.COUNTYWIDE AMENDMENTS TO SPC | | SEC.101.4.7. | | | | 3)CLEANOUTS IN GREASY WASTE AND SANITARY | | SHALL COMPLY W/ SPC SEC.710.2. | | | | 4)UNION REQD.DOWNSTREAM OF MANUAL | | CONTROL VALVE FOR SYSTEM PER NFPA 54, | | SEC.5.5.4. | | | | 5)SANITARY SYSTEM FOR TOILET ROOMS SHALL | | COMPLY W/SPC SEC.914.1 FOR CIRCUIT AND | | LOOP SYSTEM. | | | | 6)WATER HEATER RELIEF LINE SHALL NOT | | DISCHARGE TO THE GREASE SYSTEM PER | | COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.4 | | | | 7)INDICATE TYPE OF MATERIAL USED FOR THE | | GAS SYSTEM.RECALCULATE YOUR BTU LOAD ON | | THE SYSTEM. | | | | 8)GAS SYSTEM IS NOT PROPERLY SIZED PER | | SGC SEC.305.4. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY COMMENTS. | | | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-07-25 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2000-07-25 |
Time |
14:34 |
Rev Time |
3.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PLUMBING PLAN REVIEW,BY 94 SPC | | (1) SHT A-1 PLANS TO BE REVIEWED BY | | DHBR BEFORE PLUMBING PLAN REVIEW. | | CONTACT 954-958-5520 FOR PLAN REVIEW. | | (2) SHT P-1 ALL INDIRECT WASTE TO FLR | | SINKS, SEC.802 | | (3) SHT P-1 DISH WASHER & WASTE GRINDER | | TO BY PASS G/W AND CONNECT TO SANITARY | | SEWER. LOCAL ORDINANCE #2938-96. | | (4) SHT P-1&2 PLUMBING FIXTURE & KITCHEN | | EQUIPMENT LEGEND & SPECIFICATIONS, REQ | | FOR PLAN REVIEW,SEC.104.2 | | (5) SHT P-4 CO'S IN GREASE WASTE & | | SANITARY SYSTEM AS REQ. SEC 710. | | (5) SHT P-5 EMERGENCY GAS SHUT OFF VALVE | | MANUAL SHUT OFF VALVE UP STREAM, UNION | | DOWN STREAM. NFPA-54 1996 SEC5.5.5.4 | | (6) SHT P-5 INCLUDE ALL PIPE SIZES ON | | THE WATER & GAS ISOMETRIC, NO MORE THAN | | 2 PLUMBING FIXTURES ON 1/2" COLD WATER. | | END OF COMMENTS |
|
|