Plan Review Details - Permit 00070815
Plan Review Stops For Permit 00070815
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-09-11 Cont ID  
Sent By drunnels Date 2000-09-11 Time 15:09 Rev Time 1.00
Received By drunnels Date 2000-09-11 Time 15:09 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
 STOREFRONT UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-08-30 Cont ID  
Sent By drunnels Date 2000-08-30 Time 14:12 Rev Time 1.00
Received By drunnels Date 2000-08-30 Time 12:57 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT FIRE SPRINKLER PLANS ADN PERMIT
 APPLICATION.
  
 *****************PROVISO****************
 STOREFRONT TO BE ISSUED UNDER SEPERATE
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-31 Cont ID  
Sent By drunnels Date 2000-07-31 Time 07:37 Rev Time 0.00
Received By drunnels Date 2000-07-31 Time 09:19 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
  
 1. PROVIDE LETTER FROM SPECIAL INSPECTOR
 2. PROVIDE PRODUCT APPROVAL SHEETS ON
 EXTERIOR GLAZING AS PER METRO DADE
 COUNTY OR 1997 SSTD 12-97
 3. FIRE SPRINKLER PERMIT MUST BE ISSURED
 PRIOR TO ISSURANCE OF BUILDING PERMIT
 4. 1997 SBC
 A)ALL LUMBER IN FRAMING MUST BE FIRE
 RETARDANT TREATED WOOD CHAPTERS 6&7
 B)SHEET 1D-8 REMOVE STEP-UP TO SEATING
 OR MAKE HANDICAP ACCESSIBLE.
 C)NO SECOND EXIT, EXIT THROUGH KITCHEN
 NOT ALLOWED
 5. 1997 FLORIDA HANDICAP CODE
 A)PROVIDE DETAILS SHOWING TURNING
 RADIUS IN RESTROOMS
 B)PROVIDE DETAIL SHOWING SLOPE ON ALL
 RAMPS
 6. ADDRESS FOR BUILDING "B" IS 700
 SOUTH ROSEMARY NOT 701S. ROSEMARY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-24 Cont ID  
Sent By dpalmer Date 2000-07-24 Time 06:08 Rev Time 0.00
Received By dpalmer Date 2000-07-24 Time 06:08 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE SEE THE REQ`MENTS PER NEC
 FOR INSTALLATION OF TRANSFORMER. 450-21
  
  
  
  
  
  
  
  
 PLEASE SUBMIT FOR REVIEW BEFORE ANY
 ROUGH ELECTRICAL INSPECTION IS CALLED IN
 IF THERE ARE ANY QUESITONS PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-09-05 Cont ID  
Sent By mcarsill Date 2000-09-05 Time 09:57 Rev Time 0.00
Received By mcarsill Date 2000-09-05 Time 09:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By mcarsill Date 2000-08-10 Time 13:11 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00THIS REVIEW OCCURRED AFTER DEAN RUNNELS
 OF BUILDING AND ZONING MET WITH
 REPRESENTATIVES FOR MARKS ON THE PARK,
 AUGUST 10, 2000.
 1) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 2) DURING THE MEETING THEY ADVISED THAT
 CITY PLACE PARTNERS IS GOING TO
 PROVIDE INFORMATION SO THAT FIRE ALARM
 EQUIPMENT CAN BE INSTALLED WITHIN THE
 SPACE.
 3) AN ADDITIONAL ILLUMINATED EXIT SIGN
 TO BE INSTALLED TO DIRECT PERSONS TO
 THE NEW FIRE RATED EXIT HALLWAY.
 4) PORTABLE FIRE EXTINGUISHERS SHOWN ON
 RED-LINED DRAWING TO BE AT LEAST 5LBS
 WITH A MINIMUM OF 2A10BC FIRE RATING.
 5) PROVIDE SEPARATE PLANS AND PERMIT FOR
 HOOD, DUCT AND EXTINGUISHING SYSTEM.
 6) ACCORDING TO THE LETTER WRITTEN TO
 DEAN RUNNELS OF B&Z, FIRE SPRINKLER
 DRAWINGS ARE EXPECTED WITHIN THE WEEK.
 APPROVED PROVISO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By mcarsill Date 2000-07-27 Time 09:39 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER PLANS OR
 HYDRAULIC CALCULATIONS PROVIDED IN
 DRAWINGS.
 2) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 3) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF THE HOOD, DUCT
 AND EXTINGUISHING SYSTEM. WET CHEMICAL
 EXTINGUISHING SYSTEMS ARE ONLY SYSTEMS
 PERMITTED.
 4) ALL DOORS USED FOR EXITING TO BE
 EQUIPPED WITH PANIC HARDWARE. FIRE EXIT
 HARDWARE TO BE INSTALLED ON FIRE DOORS.
 5) PROVISIONS TO BE MADE FOR AT LEAST
 TWO HANDICAPPED PERSONS.
 6) DEFINE WAITING AREA. WAITING AREAS
 CANNOT INTERFERE WITH EXITING.
 7) MAIN ENTRY MUST BE CAPABLE OF
 PROVIDING EXITING FOR AT LEAST 50
 PERCENT OF OCCUPANT LOAD.
 8) DEFINE RAMPS AND STAIRS. ANY CHANGE
 IN ELEVATION LESS THAN 21" SHALL BE BY
 RAMPS.
 9) EXPLAIN EXITING ROUTES.
 10) PROVIDE FLAMESPREAD DOCUMENTATION ON
 BOOTHS AND BRANCHES.
 11) SEAT COUNTS ON PAGE ID-1 AND ID-8
 DO NOT MATCH.
 12) EXPLAIN PLATFORMS.
 13) HOW IS THE BASE BUILDING FIRE ALARM
 SYSTEM HEARD IN TENANT SPACE.
 14) PORTABLE FIRE EXTINGUISHERS REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-11 Cont ID  
Sent By cthirben Date 2000-08-11 Time 08:55 Rev Time 0.00
Received By cthirben Date 2000-08-11 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-21 Cont ID  
Sent By cthirben Date 2000-07-21 Time 08:36 Rev Time 0.00
Received By cthirben Date 2000-07-21 Time 10:43 Sent To  
Notes
2001-01-08 00:00:00PROVISO:********************************
 1.DUCT MATERIAL SCHEDULE REQUIRED.
 2.PROVIDE ENERGY EFFICIENCY RATING PER
 FLORIDA EFFICIENCY CODE.
 3.CLEARANCE OF EXHAUST AIR FROM OUTSIDE
 AIR INTAKE MIN. 10FT. PER 1997 SMC 506.1
 NOTE:***********************************
 SEPERATE PERMIT REQUIRED FOR HOOD, GAS,
 FIRE-SUPPRESSION SYSTEM, WALK-IN COOLER/
 FREEZERS.

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-09-11 Cont ID  
Sent By tlarge Date 2000-09-11 Time 14:46 Rev Time 1.00
Received By tlarge Date 2000-09-11 Time 13:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-09-08 Cont ID  
Sent By tlarge Date 2000-09-08 Time 17:45 Rev Time 1.50
Received By tlarge Date 2000-09-08 Time 17:45 Sent To  
Notes
2001-01-08 00:00:001)GAS SYSTEM SHALL BE SIZED ACCORDING TO
 THE APPLICABLE TABLE SHOWN ON THE PLANS.
 SGC 305.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status N Date 2000-09-07 Cont ID  
Sent By tlarge Date 2000-09-06 Time 18:29 Rev Time 0.50
Received By tlarge Date 2000-09-06 Time 18:21 Sent To  
Notes
2001-01-08 00:00:00THIS REVIEW STEP IS NOT APPLICABLE.
 ENTERED IN ERROR.9/7/00.TKL.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-25 Time 18:18 Rev Time 2.00
Received By tlarge Date 2000-08-25 Time 17:08 Sent To  
Notes
2001-01-08 00:00:001)SANITARY SYSTEM SHALL COMPLY W/SPC
 SEC.914.1 FOR CIRCUIT AND LOOP SYSTEM.
  
 2)COMPLY W/SPC SEC.921 FOR HORIZONTAL
 COMBINATION WASTE AND VENT SYSTEM.
  
 3)AN EMERGENCY SHUT-OFF VALVE IS REQD.
 ON THE GAS SYSTEM PER NFPA 96.
  
  
 4)SUBMIT COPY OF GAS SIZING TABLE
 UTILIZED IN THE DESIGN OF THE GAS SYSTEM
 SGC SEC.301.
  
 5)SUBMIT BTU LOAD OF EACH PIECE OF
 EQUIPMENT AND TOTAL BTU LOAD ON THE
 SYSTEM.A PROPER PLAN REVIEW CANNOT BE
 PERFORMED W/O THIS INFORMATION.SGC 301.
  
 SUBMIT PLUMBING AND KITCHEN PLAN FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 6)PLANS SHALL BE COMPILED INTO COMPLETE
 SETS FOR REVIEW.COUNTYWIDE AMENDMENTS TO
 SPC.104.2.1.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-14 Cont ID  
Sent By tlarge Date 2000-08-14 Time 08:50 Rev Time 1.50
Received By tlarge Date 2000-08-14 Time 07:04 Sent To  
Notes
2001-01-08 00:00:001)LAVATORIES IN RESTROOMS INFRINGE ON
 CLEAR FLOOR SPACE FOR WATER CLOSET.
 COMPLY W/FACBC SEC.4.17.3.FIGURE 30(A).
  
 2)PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 3)CLEANOUTS IN GREASY WASTE AND SANITARY
 SHALL COMPLY W/ SPC SEC.710.2.
  
 4)UNION REQD.DOWNSTREAM OF MANUAL
 CONTROL VALVE FOR SYSTEM PER NFPA 54,
 SEC.5.5.4.
  
 5)SANITARY SYSTEM FOR TOILET ROOMS SHALL
 COMPLY W/SPC SEC.914.1 FOR CIRCUIT AND
 LOOP SYSTEM.
  
 6)WATER HEATER RELIEF LINE SHALL NOT
 DISCHARGE TO THE GREASE SYSTEM PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.4
  
 7)INDICATE TYPE OF MATERIAL USED FOR THE
 GAS SYSTEM.RECALCULATE YOUR BTU LOAD ON
 THE SYSTEM.
  
 8)GAS SYSTEM IS NOT PROPERLY SIZED PER
 SGC SEC.305.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY COMMENTS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By pschmitz Date 2000-07-25 Time 14:34 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW,BY 94 SPC
 (1) SHT A-1 PLANS TO BE REVIEWED BY
 DHBR BEFORE PLUMBING PLAN REVIEW.
 CONTACT 954-958-5520 FOR PLAN REVIEW.
 (2) SHT P-1 ALL INDIRECT WASTE TO FLR
 SINKS, SEC.802
 (3) SHT P-1 DISH WASHER & WASTE GRINDER
 TO BY PASS G/W AND CONNECT TO SANITARY
 SEWER. LOCAL ORDINANCE #2938-96.
 (4) SHT P-1&2 PLUMBING FIXTURE & KITCHEN
 EQUIPMENT LEGEND & SPECIFICATIONS, REQ
 FOR PLAN REVIEW,SEC.104.2
 (5) SHT P-4 CO'S IN GREASE WASTE &
 SANITARY SYSTEM AS REQ. SEC 710.
 (5) SHT P-5 EMERGENCY GAS SHUT OFF VALVE
 MANUAL SHUT OFF VALVE UP STREAM, UNION
 DOWN STREAM. NFPA-54 1996 SEC5.5.5.4
 (6) SHT P-5 INCLUDE ALL PIPE SIZES ON
 THE WATER & GAS ISOMETRIC, NO MORE THAN
 2 PLUMBING FIXTURES ON 1/2" COLD WATER.
 END OF COMMENTS