Plan Review Stops For Permit 00070639 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-08-24 |
Time |
14:22 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-08-24 |
Time |
14:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-08-16 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-08-16 |
Time |
12:33 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-08-16 |
Time |
12:33 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1.SUBMIT PRODUCT APPROVAL FOR WINDOWS & | | DOORS IMPACT RESISTANT GLAZING FOR | | STOREFRONT. METRO DADE COUNTY OR SBCCI | | 2.SUBMIT LETTER FROM SPECIAL INSPECTOR | | RELEASING SPACE. | | 3. SIGN UNDER SEPERATE PERMIT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-08-08 |
Time |
10:25 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-08-08 |
Time |
10:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | 1. SUBMIT DETAILS ON DEMIZING WALL | | SHOWING FIRE RATING AND UL#. TENANT | | FIRE RESISTANT SEPERATION TO BE | | COMPLETED PRIOR TO C.O. BEING ISSUED. | | 2. SUBMIT PRODUCT APPROVAL FOR WINDOW & | | DOOR IMPACT RESISTANT GLAZING FOR | | STOREFRONT. METRO DADE COUNTY OR SBCCI | | 3. SUBMIT LETTER FROM SPECIAL INSPECTOR | | RELEASING SPACE. | | 4. SIGNS TO BE UNDER SEPERATE PERMIT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-08-22 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-08-22 |
Time |
09:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
N |
Date |
2000-08-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-08-15 |
Time |
16:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NO E-SHEETS |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-07-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-07-24 |
Time |
06:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-07-24 |
Time |
06:58 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************** UNSAT ************** | | | | 1)NOTE PLEASE GIVE MORE DETAIL ON LOCAT- | | -ION OF TRANSFORMER. NOTE 450-13 OF THE | | NEC. | | | | 2)NOTE PLEASE SHOW GRND. FOR TRANSFORMER | | ASGROUNDING ELECTRODE AND SIZE PER | | 250-66 OF THE NEC. | | | | PLEASE SUBMIT THE ABOVE IUNFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESITONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-08-16 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-08-16 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-08-08 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-07-28 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) FIRE SPRINKLER PLANS ALREADY HAVE | | REVIEWED AND APPROVED BY FIRE RESCUE. | | 2) INTERIOR FINISH SHALL BE CLASS A OR | | B. | | 3) EXITING PERMITTED THROUGH STOCKROOM | | IF THE FOLLOWING CONDITIONS EXIST: | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | IS PROVIDED THROUGH STOCKROOM, AISLE OF | | AT LEAST 44" WIDE IS PRESENT, AISLE IS | | KEPT AT 44" WIDE, STOCKROOM NOT SUBJECT | | TO LOCKING. | | 4) PORTABLE FIRE EXTINGUISHER(S) | | REQUIRED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
14:29 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-08-21 |
Time |
14:29 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISIONS ACCEPTED AS CORRECTING PRIOR | | PLAN REVIEW COMMENTS DATED 8/14/00 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2000-07-24 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-07-24 |
Time |
11:23 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-07-24 |
Time |
11:14 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED: | | 1.PROVIDE AIR BALANCE SCHEDULE AS PER | | 1997 SMC 501.2... | | 2.REQUIRE DUCT MATERIAL SCHEDULE. | | 3.EXHAUST FAN DETAIL REQUIRED ON PLANS. | | 4.PROVIDE ENERGY EFFFICIENCY RATING OF | | THE AHU-1 AS PER FLORIDA ENERGY EFFICI- | | ENCY CODE. | | 5.PROVDE CFM VALUE OF AHU TO MATCH THE | | TOTAL OF CFM ON THE PLANS 6550 CFM... |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-24 |
Time |
13:57 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-08-24 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2000-08-17 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-17 |
Time |
18:07 |
Rev Time |
0.75 |
Received By |
tlarge |
Date |
2000-08-17 |
Time |
18:07 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ADDITIONAL LAV.NOT REQUIRED IN WOMEN'S | | RESTROOM PER SPC SEC.407.3.2. | | | | | | | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-07-28 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2000-07-28 |
Time |
09:05 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PLUMBING PLAN REVIEW REF SPC 94 | | (1) SHT A-1 ACCESS TO H/C REST RM'S | | THRU A STORAGE ROOM IS NOT ACCESSIBLE | | TO THE PUBLIC, AS REQUIRED. | | COMPLY WITH W/FACBC 4.1.3 (11). | | (2) SHT A-1 1 DRINKING FOUNTAIN REQUIRED | | TAB 407, TO COMPLY W/FACBC 4.1.3 (10), | | PROVISIONS SHALL BE MADE FOR PEOPLE WHO | | HAVE TROUBLE BENDING OR STOOPING. | | (3) SHT A-1 BREAK RM KITCHEN SINK TO | | COMPLY W/FACBC 4.24.1 COUNTER 34'AFF, | | KNEE CLEARANCE. | | END OF COMMENTS |
|
|