Plan Review Details - Permit 00070639
Plan Review Stops For Permit 00070639
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-24 Cont ID  
Sent By drunnels Date 2000-08-24 Time 14:22 Rev Time 1.00
Received By drunnels Date 2000-08-24 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-16 Cont ID  
Sent By drunnels Date 2000-08-16 Time 12:33 Rev Time 1.00
Received By drunnels Date 2000-08-16 Time 12:33 Sent To  
Notes
2001-01-08 00:00:001.SUBMIT PRODUCT APPROVAL FOR WINDOWS &
 DOORS IMPACT RESISTANT GLAZING FOR
 STOREFRONT. METRO DADE COUNTY OR SBCCI
 2.SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 3. SIGN UNDER SEPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By drunnels Date 2000-08-08 Time 10:25 Rev Time 1.00
Received By drunnels Date 2000-08-08 Time 10:25 Sent To  
Notes
2001-01-08 00:00:00 
  
 1. SUBMIT DETAILS ON DEMIZING WALL
 SHOWING FIRE RATING AND UL#. TENANT
 FIRE RESISTANT SEPERATION TO BE
 COMPLETED PRIOR TO C.O. BEING ISSUED.
 2. SUBMIT PRODUCT APPROVAL FOR WINDOW &
 DOOR IMPACT RESISTANT GLAZING FOR
 STOREFRONT. METRO DADE COUNTY OR SBCCI
 3. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 4. SIGNS TO BE UNDER SEPERATE PERMIT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-22 Cont ID  
Sent By dpalmer Date 2000-08-22 Time 09:48 Rev Time 0.00
Received By dpalmer Date 2000-08-22 Time 09:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 16:09 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 16:09 Sent To  
Notes
2001-01-08 00:00:00NO E-SHEETS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By dpalmer Date 2000-07-24 Time 06:58 Rev Time 0.00
Received By dpalmer Date 2000-07-24 Time 06:58 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT **************
  
 1)NOTE PLEASE GIVE MORE DETAIL ON LOCAT-
 -ION OF TRANSFORMER. NOTE 450-13 OF THE
 NEC.
  
 2)NOTE PLEASE SHOW GRND. FOR TRANSFORMER
 ASGROUNDING ELECTRODE AND SIZE PER
 250-66 OF THE NEC.
  
 PLEASE SUBMIT THE ABOVE IUNFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESITONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By mcarsill Date 2000-08-16 Time 09:54 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-07-28 Time 15:39 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FIRE SPRINKLER PLANS ALREADY HAVE
 REVIEWED AND APPROVED BY FIRE RESCUE.
 2) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 3) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST:
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 IS PROVIDED THROUGH STOCKROOM, AISLE OF
 AT LEAST 44" WIDE IS PRESENT, AISLE IS
 KEPT AT 44" WIDE, STOCKROOM NOT SUBJECT
 TO LOCKING.
 4) PORTABLE FIRE EXTINGUISHER(S)
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 14:29 Rev Time 0.33
Received By ndenmark Date 2000-08-21 Time 14:29 Sent To  
Notes
2001-01-08 00:00:00REVISIONS ACCEPTED AS CORRECTING PRIOR
 PLAN REVIEW COMMENTS DATED 8/14/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By cthirben Date 2000-07-24 Time 11:23 Rev Time 1.00
Received By cthirben Date 2000-07-24 Time 11:14 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2...
 2.REQUIRE DUCT MATERIAL SCHEDULE.
 3.EXHAUST FAN DETAIL REQUIRED ON PLANS.
 4.PROVIDE ENERGY EFFFICIENCY RATING OF
 THE AHU-1 AS PER FLORIDA ENERGY EFFICI-
 ENCY CODE.
 5.PROVDE CFM VALUE OF AHU TO MATCH THE
 TOTAL OF CFM ON THE PLANS 6550 CFM...

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-24 Cont ID  
Sent By tlarge Date 2000-08-24 Time 13:57 Rev Time 0.50
Received By tlarge Date 2000-08-24 Time 13:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 18:07 Rev Time 0.75
Received By tlarge Date 2000-08-17 Time 18:07 Sent To  
Notes
2001-01-08 00:00:00ADDITIONAL LAV.NOT REQUIRED IN WOMEN'S
 RESTROOM PER SPC SEC.407.3.2.
  
  
  
  
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-28 Cont ID  
Sent By pschmitz Date 2000-07-28 Time 09:05 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW REF SPC 94
 (1) SHT A-1 ACCESS TO H/C REST RM'S
 THRU A STORAGE ROOM IS NOT ACCESSIBLE
 TO THE PUBLIC, AS REQUIRED.
 COMPLY WITH W/FACBC 4.1.3 (11).
 (2) SHT A-1 1 DRINKING FOUNTAIN REQUIRED
 TAB 407, TO COMPLY W/FACBC 4.1.3 (10),
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
 (3) SHT A-1 BREAK RM KITCHEN SINK TO
 COMPLY W/FACBC 4.24.1 COUNTER 34'AFF,
 KNEE CLEARANCE.
 END OF COMMENTS