Plan Review Details - Permit 00070248
Plan Review Stops For Permit 00070248
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-26 Cont ID  
Sent By dpalmer Date 2000-09-26 Time 19:35 Rev Time 0.00
Received By dpalmer Date 2000-09-26 Time 19:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-12 Cont ID  
Sent By dpalmer Date 2000-07-12 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2000-07-12 Time 12:25 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO ****************
  
 1)NOTE:PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS/PANELS. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9
  
 2)NOTE: PLEASE NOTE THAT MAIN PANEL IS
 SHOWN AS 8 CIRCUIT? IS THERE GOING TO BE
 ANOTHER PANEL OR IS THIS PANEL HAVE MORE
 CIRCUITS?
  
 3)NOTE: PLEASE SUBMIT A REVISED PANEL
 SCHEDULE AND INCLUDED THE REQ`D DEDICAT-
 -ED BATH(S) CIRCUIT(S). PER 210-11-C-3
  
 4)NOTE: PLEASE NOTE THAT ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. 210-8-A-6.
 PLEASE SHOW.
  
 5)NOTE: PLEASE NOTE THE REQ`MENTS FOR
 GFI OUTLETS FRONT AND BACK OF DWELLING
 AS PER 210-52E
  
 6)NOTE: PLEASE NOTE THE MISSING OUTLET
 IN BEDROOM. AS PER 210-52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 561-659-8096 EXT
 8372.