Plan Review Details - Permit 00070085
Plan Review Stops For Permit 00070085
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By drunnels Date 2000-08-02 Time 18:01 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVAL FOR IMPACT RESISTANT
 WINDOW SYSTEM RECEIVED 8-2-00
 WINDOW PROVISO REMOVED FROM THIS PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-08-02 Cont ID  
Sent By drunnels Date 2000-08-02 Time 09:25 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
 "PROVISO"
  
 SUBMIT PRODUCT APPROVAL FOR WINDOW
 GLAZING PER METRO DADE COUNTY OR SBCCI
 SSTD12-96.
 STOREFRONT REQUIRES SEPRATE PERMIT
  
 NOTE: TENANT SEPERATION SHALL BE
 COMPLETED PRIOR TO C.O. BEING ISSURED

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-16 Cont ID  
Sent By dpalmer Date 2000-10-16 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2000-10-16 Time 18:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2000-09-28 Cont ID  
Sent By dpalmer Date 2000-09-28 Time 17:36 Rev Time 0.00
Received By dpalmer Date 2000-09-28 Time 17:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 16:40 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 16:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By mcarsill Date 2000-08-01 Time 09:49 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) TRANSFORMER MOUNTED ON WALL SHALL
 NOT INTERFERE WITH EXIT DISCHARGE FROM
 TENANT SPACE. PROPER HEADROOM SHALL BE
 MAINTAINED IN ACCORDANCE WITH THE
 LIFE SAFETY CODE.
 2) EXIT DOOR LEADING FROM SALES AREA
 SHOULD SWING IN THE DIRECTION OF EXIT
 TRAVEL. THE OCCUPANT LOAD OF THE
 TENANT SPACE IS LESS THAN 50, THE DOOR
 COULD SWING IN THE DIRECTION OF
 EXIT TRAVEL INTO THE EXIT HALLWAY.
 3) PROVIDE SHOP DRAWINGS FOR THE FIRE
 ALARM EQUIPMENT STORED WITHIN TENANT
 SPACE.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-21 Cont ID  
Sent By ndenmark Date 2000-09-21 Time 14:52 Rev Time 0.25
Received By ndenmark Date 2000-09-21 Time 14:52 Sent To  
Notes
2001-01-08 00:00:00MECH REVISION SHOWING DUCT SMOKE DETECTO
 IN PROPER POSITION IN R/A

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-28 Cont ID  
Sent By cthirben Date 2000-07-28 Time 07:46 Rev Time 2.00
Received By ndenmark Date 2000-07-28 Time 07:46 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. DUCT SMOKE DETECTOR SHALL BE LOCATED
 IN SUPPLY AIR STREAM PER NFPA 90A 4-4 OR
 IN THE RETURN AIR DUCT PRIOR TO ANY MIX-
 ING OF OUTSIDE AIR PER 1997 SMC THE
 DETAIL ON M-1 SHOWS DUCT DETECTOR NOT
 SENSING THE RETURN DROP FROM THE STORE
 ROOM AND THIS HAS TO BE PROTECTED BY THE
 DUCT DETECTOR ALSO

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-22 Cont ID  
Sent By tlarge Date 2000-09-22 Time 12:40 Rev Time 0.30
Received By tlarge Date 2000-09-22 Time 12:39 Sent To  
Notes
2001-01-08 00:00:00ADD POINT OF USE WATER HEATER

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-29 Cont ID  
Sent By tlarge Date 2000-07-29 Time 09:29 Rev Time 0.65
Received By tlarge Date 2000-07-29 Time 09:25 Sent To  
Notes
2001-01-08 00:00:00PROVISO:BENCH IN DRESSING ROOM SHALL BE
 LOCATED ALONG WALL W/LONGER DIMENSION
 PER FACBC SEC.4.35.4.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.SUBMIT REVISED SIGNED,SEALED AND
 DATED SANITARY RISER.
  
 WATER HEATER SHALL BE LISTED PER SPC SEC
 503.3.