Plan Review Details - Permit 00070034
Plan Review Stops For Permit 00070034
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By bstaples Date 2000-07-05 Time 16:19 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-09 Cont ID  
Sent By dpalmer Date 2000-08-09 Time 15:14 Rev Time 0.00
Received By dpalmer Date 2000-08-09 Time 15:14 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ***************
  
 1)NOTE: PLEASE SEE ARTS:225-31/225-32
 AND ART 250 FOR REQ`MENTS FOR FOUNTAIN
 ELECTRICAL FEEDS/CIRCUITS.
 DISCONNECTS ARE REQ`D AND SEPARATE
 GROUNDING. PLEASE INCLUDE ALL STRUCTUAL
 STEEL AS PART OF GROUNDING.
 PLEASE GIVE FINAL DISTANCE AND/OR VOLT-
 -AGE DROP CALCS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE "ANY" INSPECTION IS
 CALLED IN!!!
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 18:33 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT ONLY E-SHEET
 SUBMITTED FOR REVIEW WAS W5.0 ?
  
 PLEASE SUBMIT COMPLETE ELECTRICAL SHEETS
 FOR COMPLETE REVIEW OF WORK. IF THERE
 ARE ANY QUESTIONS PLEASE CALL.
 561-659-8096 EXT 8372
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-08-08 Cont ID  
Sent By dlauderm Date 2000-08-08 Time 15:54 Rev Time 1.00
Received By dlauderm Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS:
 WE NEED TO KNOW METER SIZE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-07-13 Cont ID  
Sent By mgonzale Date 2000-07-13 Time 13:51 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED
 1.0
 DRAWINGS SUBMITTED DO NOT SHOW TIE IN
 OFF OKEECHOBEE BLVD FOR WATER AND SEWER.
 2.0
 PVC PIPINGAND CONDUITS MUST BE GROUPED
 &SLEEVED TOGETHER WHEN CROSSING ROSEMARY
 AVENUE.MUST KEEP 1O'MIN AWAY FROM EX. WM
 3.0
 DISCHARGE FROM THE SYSTEM SHALL BE TIED
 TO SANITARY SEWER AND NOT TO THE DRAINGE
 AS CALLED OUT.
 4.0
 NO METERS OR BACKFLOWS ARE SHOWN IN ANY
 DRAWING.
 5.0
 ALL WORK PERFORMED ALONG OKEECHOBEE
 BLVD MUST BE DONE UNDER A PERMIT FROM
 FDOT.
 6.0
 PLEASE PROVIDE LOCATION OF ALL UTILITES
 WHERE TAPPING WILL OCCUR OR ALONG ANY
 CITY ROW WHERE WORK WILL BE PERFORM.
 THIS WILL AVOID ANY CONFLICTS IN THE
 FIELD.
 7.0
 TWO SETS OF PRINTS OF THE TAP WILL HAVE
 TO BE SUBMITTED TO MANNY GONZALEZ
 CITY OF WEST PALM BEACH 1000 45TH ST
 WEST PALM BEACH, FL 33409
 561-659-8040.
 8.0
 SHOPDRAWINGS WILL BE REQUIRED ON ANY
 ITEMS INSTALLED OUT IN THE ROW. SUBMITT
 2 COPIES FOR APPROVAL.
 9.0
 FOR SANITARY SEWER SERVICES A CLEAN-OUT
 IS REQUIRED EVERY 75L.F. AND ONE MUST
 BE PROVIDED JUST INSIDE OF THE R.O.W.
 LINE ON PRIVATE PROPERTY.
 10.0
 PLEASE PROVIDE MORE DETAIL OF WHERE THE
 FOUNTAINS FALL WITHIN THE ROW AND EXIST.
 UTILIES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-14 Cont ID  
Sent By fknapp Date 2000-07-14 Time 12:38 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVIEWED OK PER M. CARSILLO

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-07-14 Cont ID  
Sent By fknapp Date 2000-07-14 Time 12:43 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-26 Cont ID  
Sent By tlarge Date 2000-07-26 Time 21:46 Rev Time 1.00
Received By pschmitz Date 2000-07-26 Time 21:45 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 1)OVERFLOW LINE SHALL DISCHARGE TO
 STORM.
  
 2)SUBMIT ALL SECTION DETAILS NOTED ON
 SHEET W1.3.
  
 3)PIPE SIZES SHOWN ON SHT.W1.3 DON'T
 CORRELATE W/SIZES NOTED IN DETAIL "C"
 ON W4.8.
  
 4)SIZE ALL PIPNG ON SHT.W2.2 AND SIZE
 PIPING ON ALL DETAILS.
  
 5)SUBMIT ALL APPLICABLE SHEETS FOR
 REVIEW.SOME NOTED DETAILS ARE NOT ON THE
 PLANS.SUBMIT ALL DETAILS FOR REVIEW ON
 AS-BUILTS.
  
 6)INDICATE MAKE,MODEL AND TYPE OF
 BACKFLOW PREVENTION DEVICE SHOWN IN WET
 WALL FOUNTAIN ROOM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-07 Cont ID  
Sent By tlarge Date 2000-07-07 Time 12:46 Rev Time 2.00
Received By tlarge Date 2000-07-07 Time 12:46 Sent To  
Notes
2001-01-08 00:00:00SUBMIT ALL LISTED SHEETS FOR PLAN REVIEW
 THAT PERTAIN TO THE WET WALL FOUNTAINS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SHT.W0.0-NOTE (5)(G),SHT.W6.0-(C)(3)-
 DELETE REFERENCE TO UNIFORM PLUMBING
 CODE AND INSERT STANDARD PLUMBING CODE.
 COMPLY W/SPC SEC.101.1,101.2.
  
 SIZE ALL PIPING TO VAULT ON SHT.W2.2.
 AND SIZE PIPING ON ALL DETAILS.
  
 PIPE SIZES SHOWN ON SHT.W1.3 DON'T
 CORRELATE W/SIZES SHOWN IN DETAIL "C"
 ON W4.8.
  
 INDICATE MAKE,MODEL AND TYPE OF BFP
 DEVICE SHOWN IN WET WALL FOUNTAIN
 EQUIPMENT ROOM.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-07-06 Cont ID  
Sent By gjoyce Date 2000-07-06 Time 09:24 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***