Plan Review Details - Permit 00061630
Plan Review Stops For Permit 00061630
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 20:49 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 20:49 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO ****************
  
 1)NOTE: AS REQ`D BY NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE TO BE INSTALLED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
  
 2)NOTE: PLEASE SEE 373-8 FOR REQ`MENTS
 FOR SERVICE DISCONNECTS.
  
 PLEASE REVISE PLANS ACC. AND SUBMIT FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
 561-659-8096 EXT 8372
 DEWEY PALMER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2001-08-16 Cont ID  
Sent By hmoser Date 2001-08-16 Time 17:15 Rev Time 0.33
Received By hmoser Date 2001-08-16 Time 17:15 Sent To  
Notes
2001-08-16 00:00:00REVISION DENIED
 #1 NO ENERGY CALC
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT.8390

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-03 Cont ID  
Sent By cthirben Date 2000-07-03 Time 12:44 Rev Time 1.00
Received By cthirben Date 2000-07-03 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-06 Cont ID  
Sent By tlarge Date 2000-07-06 Time 10:02 Rev Time 0.50
Received By tlarge Date 2000-07-06 Time 10:02 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 GAS WATER HEATER SHALL BE PROVIDED W/
 COMBUSTION AIR.SUBMIT CALCULATIONS PRIOR
 TO GAS INSPECTION.COMPLY W/SGC SEC.402.4

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2000-11-28 Cont ID  
Sent By jgomez Date 2000-11-28 Time 12:07 Rev Time 2.50
Received By jgomez Date 2000-11-28 Time 12:07 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE CONSTRUCTION DETAILS
 FOR AL ARCHED OPENINGS. SEC. 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 2-SOIL TEST REPORT IS MISSING ATTACHMENT
 "A". PLEASE SUBMIT IT.
 -BORING TESTS SHOW TRACES OF ROOTS AND
 ORGANIC MATERIALS. THE AREA UNDER THE
 FOOTINGS, FOUNDATIONS AND CONCRETE
 SLABS ON GRADE SHALL HAVE ALL STUMPS,
 VEGETATION, ROOTS AND FOREIGN MATERIAL
 REMOVED. SEC. 1804.1.8 SBC 1997.
 3-PROVIDE COMPLETE CONSTRUCTION DETAILS
 FOR INSTALLATION OF EXTERIOR POCKET
 SLIDING GLASS DOORS. SECTION 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 4-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
 5-PRODUCT APPROVALS FOR SITE SPECIFIC
 INSTALLATIONS NEED TO BE SIGNED,SEALED
 AND DATED BY BOTH, THE MANUFACTURER'S
 ENGINEER AND THE ARCHITECT OF RECORD.
 -USE CITY SAMPLE FORM FOR SITE SPECIFIC
 INSTALLATIONS AND COMPLETELY FILL IN
 ALL THE INFORMATION.
 -ENGINEER AND ARCHITECT TO LEGIBLY
 INCLUDE THEIR NAME, ADDRESS, LICENSE #
 AS REQUIRED BY 471 AND 481 OF FLORIDA
 STATUTES WHEN SUBMITTING INFORMATION
 FOR PUBLIC RECORDS.
 -CLEARLY SPECIFY THE ADDRESS OF THIS
 SPECIFIC INSTALLATION.
 -PROVIDE ALL ENGINEERED DRAWINGS.
 6-PROVIDE PRODUCT APPROVAL FOR:
 -COMPLETE BUTT GLAZING SYSTEM SHOWN ON
 ARCHITECTURAL DRAWINGS.
 -WINDOW MULLIONS
 -10' HIGH ENTRY DOORS.
 7-ORIGINAL PERMIT APPLICATION WAS NOT
 SIGNED BY THE PLUMBING SUBCONTRACTOR.
 THEREFORE, A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE PLUMBING WORK.
 8-SEE PLANS FOR ADDITIONAL COMMENTS.
 9-REVISE/CLARIFY INSTALLATION OF PRECAST
 CANTILEVERED BEAM AT MASTER BEDROOM.
 HOW IS THE BEAM TRANSFERING THE LOADS
 TO THE SIDE COLUMNS. SEE PLANS.
 10-SEE COMMENTS ON PRODUCT APPROVALS.
 NOTES:
 -ITEMS REQUESTED ON THIS PROVISO SHALL
 BE SUBMITTED TO THIS OFFICE PRIOR TO
 CONSTRUCTION OR INSTALLATION TO AVOID
 UNNECESSARY DELAYS OR CONFLICTS.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2000-10-27 Cont ID  
Sent By jgomez Date 2000-10-27 Time 11:05 Rev Time 2.50
Received By jgomez Date 2000-10-27 Time 11:05 Sent To  
Notes
2001-01-08 00:00:00THIRD CHECKLIST:
 1-THIS IS THE THIRD TIME THAT I HAVE ASK
 TO PAY THE IMPACT FEES TO PALM BEACH
 COUNTY. STILL NOT DONE. PLEASE TAKE
 DRAWINGS TO BE STAMPED AND BRING THE
 PAID RECEIPT.
 2-PROVIDE COMPLETE SPECIFICATIONS/DETAIL
 FOR CEILING CONTRUCTION AT ENTRY AND
 REAR PORCHES. INCLUDE FASTENER TYPES
 AND SPACING. SECTION 2504 SBC 1997.
 3-PROVIDE COMPLETE CONSTRUCTION DETAILS
 FOR ALL ARCHED OPENINGS.
 SECTION 104.2.2 CITY AMENDMENTS TO SBC
 4-SOIL TEST REPORT IS MISSING ATTACHMENT
 "A".
 -BORING TESTS SHOW TRACES OF ROOTS AND
 ORGANIC MATERIAL. THE AREA UNDER
 FOOTINGS, FOUNDATIONS AND CONCRETE
 SLABS ON GRADE SHALL HAVE ALL
 VEGETATION, STUMPS, ROOTS AND FOREIGN
 MATERIALS REMOVED. SECTION 1804.1.8
 SBC 1997.
 5-PROVIDE COMPLETE BUCK DETAIL FOR
 INSTALLATION OF POCKET SLIDING GLASS
 DOORS. SEC 104.2.2 CITY AMENDMENTS.
 6-PROVIDE COMPLETE INFORMATION FOR
 STORM PANELS UNDER A SEPARATE PERMIT.
 7-PRODUCT APPROVALS FOR SITE SPECIFIC
 INSTALLATIONS NEED TO BE SIGNED,SEALED
 AND DATED BY BOTH, THE MANUFACTURER'S
 ENGINEER AND THE ARCHITECT OF RECORD.
 -USE CITY SAMPLE FORM FOR SITE SPECIFIC
 INSTALLATIONS AND COMPLETELY FILL IN
 ALL THE INFORMATION.
 -ENGINEERARCHITECT TO INCLUDE THEIR
 LICENSE # AND ADDRESS AS REQUIRED BY
 CHAPTER 471/481 FLORIDA STATUTES WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORD
 -CLEARLY SPECIFY THE ADDRESS OF THIS
 SITE SPECIFIC INSTALLATION.
 -PROVIDE ALL ENGINEERED DRAWINGS.
 8-PROVIDE PRODUCT APPROVALS FOR:
 -BUTT GLAZING SYSTEM. INCLUDING FRAME.
 -WINDOW MULLIONS
 -ENTRY DOORS
 9-ORIGINAL PERMIT APPLICATION WAS NOT
 SIGNED BY THE PLUMBING SUBCONTRACTOR.
 THEREFORE, A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE PLUMBING WORK.
 10-CONTRACTOR NEEDS TO UPDATE THE CITY'S
 OCCUPATIONAL LICENSE.
 11-ADDITIONAL FEES MAY BE DUE BECAUSE OF
 MULTIPLE SUBMITTALS.
  
 NOTE:
  
 -MOST OF THE ITEMS REQUESTED ABOVE MAY
 BE TURNED IN AT A LATER DATE UNDER A
 PERMIT WITH PROVISO IF CONTRACTOR
 AGREES TO PROVIDE SUCH INFORMATION
 PRIOR TO INSTALLATION OR CONSTRUCTION.
 -IMPACT FEES MUST BE PAID BEFORE ISSUING
 THE PERMIT.
 -IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-10-02 Cont ID  
Sent By jgomez Date 2000-10-02 Time 12:15 Rev Time 2.00
Received By jgomez Date 2000-10-02 Time 12:15 Sent To  
Notes
2001-01-08 00:00:00SECOND CHECKLIST:
 (SAME ITEMS REQUESTED ON 1ST CHECKLIST)
  
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING RECEIPT AND STAMPED DRAWINGS.
 2-REVISE LOAD REQUIREMENTS FOR ATTIC
 STORAGE. 30 PSF LIVE LOAD. SEE TABLE
 1604.1 SBC 1997.
 3-PROVIDE SAFETY GLASS AT FAMILY ROOM,
 LIVING ROOM AND MASTER BATH. SEE PLANS
 AND SECTION 2405.2 SBC 1997.
 4-PROVIDE COMPLETE AHU HANGING DETAILS.
 INCLUDE FASTENERS TYPES AND SIZES.
 DETAIL SHOWN ON SHEET A5 DOESN'T APPLY
 5-PROVIDE COMPLETE SPECIFICATIONS/DETAIL
 FOR CEILING CONSTRUCTION AT ENTRY AND
 REAR PORCHES. INCLUDE FASTENER TYPES
 AND SPACING. SECTION 2504 SBC 1997.
 6-FOOTING F2 TO HAVE 16" MINIMUM DEPTH
 AS PER SECTION 1804.1.9 OF CITY
 AMENDMENTS AND SEC 1804.1.3 SBC 1997.
 7-ROOF FRAMING PLAN: SOME TRUSS GIRDERS
 ARE SHOWN WITHOUT A SUPPORTING POST TO
 TRANSFER THE LOAD TO THE FOOTING.
 SPECIFY POSTS AND TOP AND BOTTOM
 CONNECTORS. ALSO, VERIFY IF CONCRETE
 PAD WILL BE REQUIRED TO SUPPORT THE
 LOAD. SEC 104.2.2 CITY AMENDMENTS.
 8-PROVIDE DETAIL/SPECS SHOWING HOW ARE
 OPENINGS DESIGNED TO RECEIVE STORM
 PANELS. DRAWINGS SHOW PRECAST LINTELS,
 BUT WHAT ABOUT WINDOW SILLS?
 THIS WILL DETERMINE THE TYPE OF ANCHOR
 AND SPACING REQUIRED TO INSTALL THE
 STORM PANEL.
 9-PROVIDE COMPLETE CONSTRUCTION DETAILS
 FOR ARCHED OPENINGS.
 SECTION 104.2.2 CITY AMENDMENTS.
 10-REVISE SOIL TEST REPORT. WE FOLLOW
 THE 1997 SBC, NOT 1994.
 -ALSO, PROVIDE COPIES OF THE TESTS
 PERFORMED AS PER TABLE 1804.2.7.3 OF
 CITY AMENDMENTS.
 11-PROVIDE COMPLETE BUCK DETAILS FOR
 INSTALLATION OF DOORS AND WINDOWS.
 INCLUDING THE STRUCTURAL BUCK DETAIL
 TO SUPPORT THE GARAGE DOORS AND THE
 POCKET TYPE SLIDING GLASS DOORS.
 NOTE: SEE PRODUCT APPROVALS FOR THE
 SIZE OF BUCK REQUIRED.
 12-STORM PANELS:
 -PROVIDE COMPLETE INFORMATION FOR THE
 INSTALLATION OF STORM PANELS,INCLUDING
 PRODUCT APPROVAL, ATTACHED SAMPLE OF
 INSTALLATION SCHEDULE AND KEY PLAN AND
 PROPER IDENTIFICATION OF MOUNTING
 CONDITIONS AND ANCHORS TO BE USED.
 NOTE:THIS INFORMATION MAY BE SUBMITTED
 LATER UNDER A SEPARATE APPLICATION.
 13-PROVIDE CURRENT PRODUCT APPROVAL FOR:
 -BUTT GLAZING SYSTEM AS SHOWN ON PLANS.
 -POCKET SLIDING GLASS DOORS.
 -FIXED WINDOWS OF SIZES AS SHOWN LIVING
 ROOM AND FAMILY ROOM.
 -WINDOW MULLIONS.
 -ARCHED WINDOWS.
 -ENTRY DOORS.
 14-SEE ADDITIONAL COMMENTS ON PLANS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 15-HIGHLIGHT FASTENING METHOD AND SYSTEM
 TO BE USED IN ROOF TILE PRODUCT
 APPROVAL.
 16-APPLICATION FOR PERMIT MUST BE FILLED
 COMPLETELY AND SIGNED BY THOSE SUBS
 WHO APPLY IN THE ORIGINAL APPLICATION.
 17-GENERAL CONTRACTOR TO UPDATE LICENSE
 AND INSURANCE.
  
 NOTES:
 -IT LOOKS LIKE THE ARCHITECT REVIEWED
 OUR MARKED SET AND EVEN MADE SOME
 COMMENTS. BUT, UNFORTUNATELY THE SETS
 THAT WERE RE-SUBMITTED AREN'T THE
 REVISED ONES. PLEASE RE-SUBMIT THOSE
 DRAWINGS AND DON'T FORGET TO INCLUDE
 THIS MARKED SET IN ORDER TO EXPEDITE
 THE REVIEW PROCESS.
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXT. 8232.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By jgomez Date 2000-07-27 Time 19:21 Rev Time 3.00
Received By jgomez Date 2000-07-27 Time 19:21 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-REVISE LOAD REQUIREMENTS FOR ATTIC
 STORAGE. 30 PSF LIVE LOAD. SEE TABLE
 1604.1 SBC 1997.
 3-PROVIDE SAFETY GLASS AS REQUIRED AT
 FAMILY ROOM, LIVING ROOM AND MASTER
 BATH. SECTION 2405.2 SBC 1997.
 4-PROVIDE COMPLETE AHU HANGING DETAILS.
 INCLUDE FASTENERS TYPES AND SIZES.
 DETAIL SHOWN ON SHEET A5 DOESN'T APPLY
 TO THIS HOUSE. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 5-PROVIDE COMPLETE SPECIFICATIONS/DETAIL
 FOR CEILING CONSTRUCTION AT ENTRY AND
 REAR PORCHES. INCLUDE FASTENERS TYPES
 AND SPACING. SECTION 2504 SBC 1997.
 6-FOOTING F2 TO HAVE 16" MINIMUM IN
 DEPTH AS PER SECTION 1804.1.9 OF CITY
 AMENDMENTS AND SEC. 1804.1.3 SBC 1997.
 7-ROOF FRAMING PLAN: SOME TRUSS GIRDERS
 ARE SHOWN WITHOUT A SUPPORTING POST TO
 TRANSFER THE LOAD TO THE FOOTING.
 SPECIFY POSTS AND TOP AND BOTTOM
 CONNECTORS. VERIFY IF CONCRETE PAD
 REQUIRED TO CARRY THE LOAD.
 SECTION 104.2.2 CITY AMENDMENTS.
 8-PROVIDE DETAIL/SPECS SHOWING HOW ARE
 OPENINGS DESIGNED TO RECEIVESTORM
 PANELS. DRAWINGS SHOW PRECAST LINTELS,
 BUT WHAT ABOUT WINDOW SILLS?
 THIS WILL DETERMINE THE TYPE OF ANCHOR
 AND SPACING REQUIRED TO INSTALL THE
 STORM PANEL.
 9-PROVIDE COMPLETE DETAIL/SPECS FOR
 CONSTRUCTION OF ARCHED OPENINGS.
 SECTION 104.2.2 CITY AMENDMENTS.
 10-PROVIDE SURVEY SHOWING NEW BUILDING
 LAYOUT.
 11-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.7.3 OF CITY AMENDMENTS.
 12-PROVIDE COMPLETE BUCK DETAILS FOR
 INSTALLATION OF DOORS AND WINDOWS.
 INCLUDING THE STRUCTURAL BUCK DETAIL
 FOR GARAGE DOORS AND SGD POCKET TYPE.
 NOTE: SEE PRODUCT APPROVALS FOR
 REQUIRED BUCK SIZE.
 13-STORM PANELS:
 -CLARIFY WHICH PRODUCT APPROVAL IS
 GOING TO BE USED. SBCCI OR DADE COUNTY
 AND PROVIDE COMPLETE DRAWINGS FOR
 EITHER ONE.
 -SBCCI PRODUCT APPROVAL REPORT AND
 DRAWINGS DON'T MATCH. SEE PAGE TWO OF
 PRODUCT APPROVAL FOR APPROVED DRAWINGS
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AS PER CITY SAMPLE ATTACHED AND KEY
 PLAN.
 NOTE: KEEP IN MIND THAT ANCHOR TYPE
 AND SPACING IS TO BE SELECTED ACCORD'G
 TO THE DESIGN PRESSURES,EDGE DISTANCE,
 PANEL SPAN, MEAN ROOF HEIGHT,CONNECT'N
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 (THIS BUILDING IS MASONRY CONSTRUCTION
 NOT 3000PSF CONCRETE).
 14-PROVIDE CURRENT PRODUCT APPROVAL FOR:
 BUTT GLAZING SYSTEM AS SHOWN ON PLANS,
 GARAGE DOORS (DADE COUNTY OR SBCCI, NO
 BROWARD COUNTY), SLIDING GLASS DOORS
 (POCKET TYPE AS SHOWN ON PLANS), FIXED
 WINDOWS OF SIZES AS SHOWN ON LIVING RM
 AND FAMILY RM,WINDOW MULLIONS, ARCHED
 WINDOWS, ENTRY DOORS (IF SITE SPECIFIC
 THEN THE PRODUCT APPROVAL FORM SHALL
 BE SIGNED, SEALED AND DATED BY THE
 COMPANY ENGINEER AND BY THE ARCHITECT
 OF RECORD. PROVIDE LEGIBLE FORMS).
 15-SEE ADDTIONAL COMMENTS ON PLANS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 16-HIGHLIGHT FASTENING METHOD AND SYSTEM
 TO BE USED IN ROOF TILE PRODUCT APP'L.
  
  
  
 NOTE:
 -PLEASE RETURN REVIEWED SET OF PLANS
 AFTER CORRECTIONS ARE DONE TO THE
 ORIGINAL DRAWINGS IN ORDER TO EXPEDITE
 THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-30 Cont ID  
Sent By gjoyce Date 2000-06-30 Time 15:34 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***