Plan Review Details - Permit 00061550
Plan Review Stops For Permit 00061550
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-03 Cont ID  
Sent By tlarge Date 2000-07-03 Time 09:18 Rev Time 0.30
Received By tlarge Date 2000-07-03 Time 09:18 Sent To  
Notes
2001-01-08 00:00:00****************NOTE********************
 THE FOLLWING INFORMATION SHALL BE NOTED
 ON ALL FUTURE GAS SUBMITTALS:
 1)A COPY OF THE APPROPRIATE GAS SIZING
 TABLE SHALL BE SUBMITTED FOR EACH SET OF
 PLANS.
  
 2)CLEARLY SHOW ALL CUT SECTIONS OF PIPE,
 TYPE OF PIPING MATERIAL BEING INSTALLED,
 PIPE SIZES,(AND EHD NUMBER OF CSST FOR
 EACH PIPE SIZE BEING USED,)TYPE OF GAS,
 (LP OR NATURAL),BTU LOAD OF EACH
 APPLIANCE AND TOTAL BTU LOAD ON THE
 SYSTEM.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-02 Cont ID  
Sent By tlarge Date 2000-07-02 Time 06:53 Rev Time 0.30
Received By tlarge Date 2000-07-02 Time 06:53 Sent To  
Notes
2001-01-08 00:00:00SUBMIT COPY OF APPLICABLE GAS SIZING
 TABLE USED IN SYSTEM DESIGN.SGC SEC.302.
  
 INDICATE TYPE OF PIPING BEING INSTALLED.
 SGC SEC.302.
  
 INDICATE DELIVERY PRESSURE.SGC 305.2,
 305.4.