Plan Review Details - Permit 00061481
Plan Review Stops For Permit 00061481
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-11-06 Cont ID  
Sent By drunnels Date 2000-11-06 Time 09:00 Rev Time 1.00
Received By drunnels Date 2000-11-06 Time 08:59 Sent To  
Notes
2001-01-08 00:00:00REVISIONS TO SHELL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-09-06 Cont ID  
Sent By hpiskura Date 2000-09-06 Time 11:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEED COPY OF IMPACT FEE RCPT & RES INSP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By hpiskura Date 2000-08-08 Time 09:07 Rev Time 0.00
Received By hpiskura Date 2000-08-02 Time 16:03 Sent To  
Notes
2001-01-08 00:00:00LETTER ATTACHED TO PERMIT APPLICATION

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-27 Cont ID  
Sent By dpalmer Date 2000-07-27 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2000-07-27 Time 20:13 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE SUBMIT REVISED LOAD
 CALCULATIONS SHOWING ALL CONTINUOUS
 LOADS AT 125% (LIGHTING ETC ) 220 NEC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELETRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-09-08 Cont ID  
Sent By mgonzale Date 2000-09-08 Time 10:08 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS
  
 1. WHEN INSTALLING METERS MUST BE INSTAL
 LED JUST OUTSIDE OF PROPERTY IN THE ROW
  
 2. PLEASE PROVIDE SITE PERSRVIOUS AND IM
 PERVIOUS CALCULATIONS. PLEASE LIST AMOUN
 TS IN SQ. FT. AND IN ACRES. THE TOTAL
 SHOULD AMOUNT TO TOTAL SITE ACREAGE.
 PLEASE FAX ATTENTION MANNY 561-653-2648
  
 3. ANY WORK PERFORMED IN THE R.O.W. WILL
 REQUIRE A R.O.W. PERMIT FROM RICHARD
 D. PITTMAN, CITY ENGINEER.
 1000 45TH ST. WPB FL 33407
 (561) 659-8040
  
 4. A VALVE MUST BE ADDED NEXT TO FIRE
 HYDRANTS THAT ARE BEING RELOCATED
 BECAUSE OF A DRIVEWAY ENTRANCE. 2 TOTAL
  
 5. A COMMENT WAS MADE ON BEHALF OF
 PUBLIC UTILITIES TO USE CITY OF WPB
 STANDARD UTILITY DETAILS FOR ANY WORK
 PERFORMED AND BEING APPROVED BY THE
 CITY OF WEST PALM BEACH PUBLIC
 UTILITIES ENGINEERING DEPARTMENT.
  
 6. ALSO A MINIMUM OF TWO SETS OF PLANS
 MUST BE DELIVERED TO MANNY GONZALEZ
 1000 45TH STREET SUITE 15, WPB FL 33407
 (561) 659 8040. ONE FOR THE UTILITY FILE
 AND ONE FOR THE UTILITY INSPECTOR.
 2 SETS OF SHOP DRAWINGS MUST BE SUBMITTE
 D FOR APPROVAL BEFORE JOB COMMENCEMENT.
  
 7. SUNSHINE LOCATION SERVICE 1-800 SHOUL
 D BE NOTED ON ALL UTILITY PLANS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-14 Cont ID  
Sent By mgonzale Date 2000-08-14 Time 09:27 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 POLLUTION PREVENTION PLAN WAS SUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2001-04-26 Cont ID  
Sent By mcarsill Date 2001-04-26 Time 11:50 Rev Time 0.00
Received By mcarsill Date 2001-04-26 Time 11:50 Sent To  
Notes
2001-04-26 00:00:001) PLANS DO NOT INDICATE THE VOLUME,
 HEIGHT OR WIDTH OF THE TANK. IT IS
 PRESUMED THAT THE TANK WILL CONTAIN
 LIQUID OXYGEN. PLEASE PROVIDE ELEVATION
 DRAWINGS OF THE OXYGEN TANK.
 2) NO PIPING OR APPURTENANT EQUIPMENT
 SHOWN TO OR FROM THE TANK.
 3) NO WARNING SIGNS OR LABELS
 IDENTIFYING THE HAZARD OR MATERIAL
 THAT IS PLANNED FOR STORAGE.
 4) NO SITE PLAN PROVIDED FOR THE
 INSTALLATION AREAS.
 5) ON THE PREVIOUS APPROVED PLANS THE
 TWO DOORS LEADING INTO THE SCREEN
 ENCLOSURE WERE DESIGNATED AS EXIT DOORS.
 PLEASE EXPLAIN EXITING ARRANGEMENT.
 6) THE SCREEN ENCLOSURE HAS NO PERMIT
 TO BE CONSTRUCTED. ALL EXTERIOR WORK
 WAS TO BE DONE UNDER SEPARATE PERMIT.
 7) WHERE DID THE ORIGINAL PROPOSED
 NITROGEN TANK GO.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-29 Cont ID  
Sent By mcarsill Date 2000-08-29 Time 15:09 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By rturnque Date 2000-08-01 Time 15:13 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE DEPARTMENT CONNECTION SHALL BE
 LOCATED ADJACENT TO MAIN ENTRANCE.
 STAIR DETAILS SHALL BE IN COMPLIANCE
 WITH NFPA,1985 LIFE SAFETY CODE.
 PROVIDE TAMPER SWITCHES FOR DOUBLE OW
 DETECTOR CHECK.
 FIRE ALARM SYSTEM SHALL BE CLASS "A" OR
 ADDRESSABLE.
 FIRE DEPARTMENT CONNECTION SHALL BE
 LOCATED NEAR DRIVEWAY AND FACING
 DIRECTION OF DRIVEWAY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-07-25 Cont ID  
Sent By ndenmark Date 2000-07-25 Time 10:54 Rev Time 0.50
Received By ndenmark Date 2000-07-25 Time 10:54 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED AS SHELL ONLY W/ ONE PTAC
 NO OTHER MECHANICAL EQUIPMENT REVIEWED
 W/THIS PERMIT APPLICATION

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-16 Cont ID  
Sent By tlarge Date 2000-10-16 Time 18:13 Rev Time 0.65
Received By pschmitz Date 2000-10-16 Time 17:43 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SIGNED,DATED AND SEALED DETAIL OF
 SCUPPER PRIOR TO INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-26 Cont ID  
Sent By tlarge Date 2000-07-26 Time 16:39 Rev Time 1.50
Received By tlarge Date 2000-07-26 Time 16:39 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 1)SHT A3.1-BACKFLOW PREVENTERS LOCATED
 IN VAULTS SHALL COMPLY W/SPC SEC.606.4.1
 LOCATION SHALL BE APPROVED BY UTILITIES
 DEPT.
  
 2)OVERFLOW DRAINAGE SYSTEM FOR THE ROOF
 SHALL BE DESIGNED ON 1994 EDITION OF THE
 SPC SEC.1109 & APPENDIX "A".
  
 3)STORM WATER SYSTEM SHALL BE SHOWN ON
 CIVIL DRAWINGS AND SIZED PER TABLES
 1108.1 & 1108.2 OF THE SPC.
  
 *****NOTE:REVISED DRAWINGS SHALL BE
 SUBMITTED PRIOR TO ISSUANCE OF PLUMBING
 PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-15 Cont ID  
Sent By gjoyce Date 2000-08-15 Time 10:46 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***