Plan Review Stops For Permit 00061481 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2000-11-06 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-11-06 |
Time |
09:00 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
2000-11-06 |
Time |
08:59 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISIONS TO SHELL |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2000-09-06 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-09-06 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NEED COPY OF IMPACT FEE RCPT & RES INSP |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-08-08 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
2000-08-02 |
Time |
16:03 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | LETTER ATTACHED TO PERMIT APPLICATION |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-07-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-07-27 |
Time |
20:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-07-27 |
Time |
20:13 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** PROVISO *************** | | | | 1)NOTE: PLEASE SUBMIT REVISED LOAD | | CALCULATIONS SHOWING ALL CONTINUOUS | | LOADS AT 125% (LIGHTING ETC ) 220 NEC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW BEFORE FINAL ELETRICAL INSPECT- | | -ION IS CALLED IN. IF THERE ARE ANY | | QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2000-09-08 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-09-08 |
Time |
10:08 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PASSED WITH PROVISOS | | | | 1. WHEN INSTALLING METERS MUST BE INSTAL | | LED JUST OUTSIDE OF PROPERTY IN THE ROW | | | | 2. PLEASE PROVIDE SITE PERSRVIOUS AND IM | | PERVIOUS CALCULATIONS. PLEASE LIST AMOUN | | TS IN SQ. FT. AND IN ACRES. THE TOTAL | | SHOULD AMOUNT TO TOTAL SITE ACREAGE. | | PLEASE FAX ATTENTION MANNY 561-653-2648 | | | | 3. ANY WORK PERFORMED IN THE R.O.W. WILL | | REQUIRE A R.O.W. PERMIT FROM RICHARD | | D. PITTMAN, CITY ENGINEER. | | 1000 45TH ST. WPB FL 33407 | | (561) 659-8040 | | | | 4. A VALVE MUST BE ADDED NEXT TO FIRE | | HYDRANTS THAT ARE BEING RELOCATED | | BECAUSE OF A DRIVEWAY ENTRANCE. 2 TOTAL | | | | 5. A COMMENT WAS MADE ON BEHALF OF | | PUBLIC UTILITIES TO USE CITY OF WPB | | STANDARD UTILITY DETAILS FOR ANY WORK | | PERFORMED AND BEING APPROVED BY THE | | CITY OF WEST PALM BEACH PUBLIC | | UTILITIES ENGINEERING DEPARTMENT. | | | | 6. ALSO A MINIMUM OF TWO SETS OF PLANS | | MUST BE DELIVERED TO MANNY GONZALEZ | | 1000 45TH STREET SUITE 15, WPB FL 33407 | | (561) 659 8040. ONE FOR THE UTILITY FILE | | AND ONE FOR THE UTILITY INSPECTOR. | | 2 SETS OF SHOP DRAWINGS MUST BE SUBMITTE | | D FOR APPROVAL BEFORE JOB COMMENCEMENT. | | | | 7. SUNSHINE LOCATION SERVICE 1-800 SHOUL | | D BE NOTED ON ALL UTILITY PLANS. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-08-14 |
Time |
09:27 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PASSED | | POLLUTION PREVENTION PLAN WAS SUBMITTED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2001-04-26 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2001-04-26 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2001-04-26 |
Time |
11:50 |
Sent To |
|
|
Notes |
2001-04-26 00:00:00 | 1) PLANS DO NOT INDICATE THE VOLUME, | | HEIGHT OR WIDTH OF THE TANK. IT IS | | PRESUMED THAT THE TANK WILL CONTAIN | | LIQUID OXYGEN. PLEASE PROVIDE ELEVATION | | DRAWINGS OF THE OXYGEN TANK. | | 2) NO PIPING OR APPURTENANT EQUIPMENT | | SHOWN TO OR FROM THE TANK. | | 3) NO WARNING SIGNS OR LABELS | | IDENTIFYING THE HAZARD OR MATERIAL | | THAT IS PLANNED FOR STORAGE. | | 4) NO SITE PLAN PROVIDED FOR THE | | INSTALLATION AREAS. | | 5) ON THE PREVIOUS APPROVED PLANS THE | | TWO DOORS LEADING INTO THE SCREEN | | ENCLOSURE WERE DESIGNATED AS EXIT DOORS. | | PLEASE EXPLAIN EXITING ARRANGEMENT. | | 6) THE SCREEN ENCLOSURE HAS NO PERMIT | | TO BE CONSTRUCTED. ALL EXTERIOR WORK | | WAS TO BE DONE UNDER SEPARATE PERMIT. | | 7) WHERE DID THE ORIGINAL PROPOSED | | NITROGEN TANK GO. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-08-29 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-08-01 |
|
|
Cont ID |
|
Sent By |
rturnque |
Date |
2000-08-01 |
Time |
15:13 |
Rev Time |
1.00 |
Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FIRE DEPARTMENT CONNECTION SHALL BE | | LOCATED ADJACENT TO MAIN ENTRANCE. | | STAIR DETAILS SHALL BE IN COMPLIANCE | | WITH NFPA,1985 LIFE SAFETY CODE. | | PROVIDE TAMPER SWITCHES FOR DOUBLE OW | | DETECTOR CHECK. | | FIRE ALARM SYSTEM SHALL BE CLASS "A" OR | | ADDRESSABLE. | | FIRE DEPARTMENT CONNECTION SHALL BE | | LOCATED NEAR DRIVEWAY AND FACING | | DIRECTION OF DRIVEWAY |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
A |
Date |
2000-07-25 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-07-25 |
Time |
10:54 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-07-25 |
Time |
10:54 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ACCEPTED AS SHELL ONLY W/ ONE PTAC | | NO OTHER MECHANICAL EQUIPMENT REVIEWED | | W/THIS PERMIT APPLICATION |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-10-16 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-10-16 |
Time |
18:13 |
Rev Time |
0.65 |
Received By |
pschmitz |
Date |
2000-10-16 |
Time |
17:43 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SUBMIT SIGNED,DATED AND SEALED DETAIL OF | | SCUPPER PRIOR TO INSPECTION. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-07-26 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-07-26 |
Time |
16:39 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-07-26 |
Time |
16:39 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************PROVISO***************** | | 1)SHT A3.1-BACKFLOW PREVENTERS LOCATED | | IN VAULTS SHALL COMPLY W/SPC SEC.606.4.1 | | LOCATION SHALL BE APPROVED BY UTILITIES | | DEPT. | | | | 2)OVERFLOW DRAINAGE SYSTEM FOR THE ROOF | | SHALL BE DESIGNED ON 1994 EDITION OF THE | | SPC SEC.1109 & APPENDIX "A". | | | | 3)STORM WATER SYSTEM SHALL BE SHOWN ON | | CIVIL DRAWINGS AND SIZED PER TABLES | | 1108.1 & 1108.2 OF THE SPC. | | | | *****NOTE:REVISED DRAWINGS SHALL BE | | SUBMITTED PRIOR TO ISSUANCE OF PLUMBING | | PERMIT. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-08-15 |
Time |
10:46 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|