Plan Review Details - Permit 00061478
Plan Review Stops For Permit 00061478
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-10-24 Cont ID  
Sent By drunnels Date 2000-10-24 Time 12:33 Rev Time 1.00
Received By drunnels Date 2000-10-24 Time 12:32 Sent To  
Notes
2001-01-08 00:00:001.REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-09-19 Cont ID  
Sent By hpiskura Date 2000-09-19 Time 14:13 Rev Time 0.00
Received By hpiskura Date 2000-09-13 Time 08:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-27 Cont ID  
Sent By dpalmer Date 2000-07-27 Time 19:59 Rev Time 0.00
Received By dpalmer Date 2000-07-27 Time 19:59 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE : PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 (LIGHTING ETC.,) 220
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL ELECTRICAL INSPECT-
 -IONIS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELETRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 ETX8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-09-08 Cont ID  
Sent By mgonzale Date 2000-09-08 Time 10:02 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED WITH PROVISOS
  
 1. WHEN INSTALLING METERS MUST BE INSTAL
 LED JUST OUTSIDE OF PROPERTY IN THE ROW
  
 2. PLEASE PROVIDE SITE PERSRVIOUS AND IM
 PERVIOUS CALCULATIONS. PLEASE LIST AMOUN
 TS IN SQ. FT. AND IN ACRES. THE TOTAL
 SHOULD AMOUNT TO TOTAL SITE ACREAGE.
 PLEASE FAX ATTENTION MANNY 561-653-2648
  
 3. ANY WORK PERFORMED IN THE R.O.W. WILL
 REQUIRE A R.O.W. PERMIT FROM RICHARD
 D. PITTMAN, CITY ENGINEER.
 1000 45TH ST. WPB FL 33407
 (561) 659-8040
  
 4. A VALVE MUST BE ADDED NEXT TO FIRE
 HYDRANTS THAT ARE BEING RELOCATED
 BECAUSE OF A DRIVEWAY ENTRANCE. 2 TOTAL
  
 5. A COMMENT WAS MADE ON BEHALF OF
 PUBLIC UTILITIES TO USE CITY OF WPB
 STANDARD UTILITY DETAILS FOR ANY WORK
 PERFORMED AND BEING APPROVED BY THE
 CITY OF WEST PALM BEACH PUBLIC
 UTILITIES ENGINEERING DEPARTMENT.
  
 6. ALSO A MINIMUM OF TWO SETS OF PLANS
 MUST BE DELIVERED TO MANNY GONZALEZ
 1000 45TH STREET SUITE 15, WPB FL 33407
 (561) 659 8040. ONE FOR THE UTILITY FILE
 AND ONE FOR THE UTILITY INSPECTOR.
 2 SETS OF SHOP DRAWINGS MUST BE SUBMITTE
 D FOR APPROVAL BEFORE JOB COMMENCEMENT.
  
 7. SUNSHINE LOCATION SERVICE 1-800 SHOUL
 D BE NOTED ON ALL UTILITY PLANS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-08-14 Cont ID  
Sent By mgonzale Date 2000-08-14 Time 09:29 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSED
 POLLUTION PREVENTION PLAN SUBMITTED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-30 Cont ID  
Sent By rturnque Date 2000-08-30 Time 10:04 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-16 Cont ID  
Sent By mcarsill Date 2000-08-16 Time 11:33 Rev Time 0.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001) IT APPEARS THAT THE FIRE DEPARTMENT
 CONNECTION WAS NOT RELOCATED. NO
 CLOUDS OR TRIANGLES WERE USED TO NOTE
 RELOCATED FIRE DEPARTMENT CONNECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-29 Cont ID  
Sent By rturnque Date 2000-06-29 Time 12:53 Rev Time 0.35
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.
 MOVE FIRE DEPARTMENT CONNECTION FOR BLDG
 "B" FURTHER EAST,ON THE CORNER NEAR
 DRIVEWAY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-07-25 Cont ID  
Sent By ndenmark Date 2000-07-25 Time 11:15 Rev Time 0.50
Received By ndenmark Date 2000-07-25 Time 11:15 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED AS SHELL ONLY W/ PTAC ONLY MECH
 EQUIPMENT ON THIS PERMIT

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-10-16 Cont ID  
Sent By tlarge Date 2000-10-16 Time 17:42 Rev Time 0.65
Received By tlarge Date 2000-10-16 Time 17:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-26 Cont ID  
Sent By tlarge Date 2000-07-26 Time 17:26 Rev Time 1.25
Received By tlarge Date 2000-07-26 Time 17:05 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
 1)OVERFLOW SYSTEM FOR ROOF SHALL BE
 DESIGNED ON THE 1994 EDITION OF THE
 STANDARD PLUMBING CODE SEC.1109 &
 APPENDIX "A".
  
 2)INSTALLATION OFBFP DEVICES IN VAULTS
 SHALL COMPLY W/SPC 606.4.1.LOCATION
 SHALL BE APPROVED BY WPB UTILITIES.
  
 3)STORM DRAIN LINES SHALL BE SHOWN ON
 THE CIVIL DRAWINGS AND SIZED PER TABLES
 1108.1,1108.2 OF THE SPC.
  
 *******NOTE:REVISED DRAWINGS SHALL BE
 SUBMITTED PRIOR TO ISSUANCE OF PLUMBING
 PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-09-19 Cont ID  
Sent By gjoyce Date 2000-09-19 Time 14:09 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***