Plan Review Details - Permit 00061141
Plan Review Stops For Permit 00061141
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-07 Cont ID  
Sent By drunnels Date 2000-08-07 Time 08:38 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-01 Cont ID  
Sent By drunnels Date 2000-08-01 Time 09:45 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
 1. INDICATE FIRE SEPERATION BETWEEN
 OCCUPANCIES, 2 HOUR REQUIRED. SHOW
 LOCATION HORZINTIAL AND VERTICAL
 INDICATE UL RATING FOR ALL ASSEMBLIES
 2. EXITS, SECOND MEANS OF EGRESS DEFINED
 ON PLANS IS BLOCKED BY A TABLE.
 REVISE.
 3. FIRE SPRINKLER CONTRACTOR TO APPLY
 FOR PERMIT.
 4. SIGNS REQUIRE SEPRATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-03 Cont ID  
Sent By bstaples Date 2000-07-03 Time 08:06 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS SIGNED AND
 SEALED BY DESIGNER OF RECORD AND OWNER.
 2. INDICATE FIRE SEPERATION BETWEEN
 OCCUPANCIES 2 HR REQUIRED. SHOW LOCATION
 HORZONTIAL AND VERTICAL INDICATE UL
 RATING FOR ALL ASSEMBLIES.
 3. EXTERIOR GLAZING IMPACT RESISTANT,
 PROVIDE PRODUCT APPROVAL.
 IF SHUTTERS USED, PROVIDE WIND LOAD
 INFORMATION FOR ALL EXTERIOR GLAZING
 PROVIDE PRODUCT APPROVAL FOR SHUTTERS.
 PROVIDE PLAN FOR INSTULLATION SIGNED BY
 OWNER SHOW STORAGE LOCATION IN UNIT.
 SHUTTER PLANS ARE SUBJECT TO APPROVAL
 BY THE BUILDING OFFICIAL SEE CITY POLICY
 4. FIRE SPRINKLER CONTRACTOR TO APPLY
 FOR PERMIT.
 5. EXITS, SECOND MEANS OF EGRESS DEFINED
 ON PLANS IS BLOCKED BY A TABLE. REVISE.
 6. SIGNS REQUIRE SEPERATE PERMITS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-02-12 Cont ID  
Sent By dpalmer Date 2001-02-12 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2001-02-12 Time 07:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-01-31 Cont ID  
Sent By dpalmer Date 2001-01-31 Time 10:20 Rev Time 0.00
Received By dpalmer Date 2001-01-31 Time 10:20 Sent To  
Notes
2001-01-31 00:00:00*********** REVISION NEEDED
 ************1) NOTE: PLEASE NOTE THAT A
 MAIN DSCONNECT HAS BEEN ADDED TO PLANS
 ON SHEET E-5 FOR PANEL "K". NO SPECS
 WERE SUBMITTED
 FOR THIS EQUIPMENT. PLEASE DO SO.
 NOW THAT THERE IS A MAIN INLINE FROM
 TRANSFORMER, DOES PANEL "K " STILL HAVE
 A ,MAIN?
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 THIS IS REQ`D FOR NEW PANEL "K " DISC.
  
 3)NOTE: PLANS HAVE BEEN REDRAWN BY HAND
 AND NEEDS TO BE RE-DONE UNDER
 ADMINISTRATIVE CODE BEING SUBMITTED FOR
 RECORD.
 SEE SECTION 104.2.1 AND 104.2.7 FOR
 QUALITY OF PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. PLANS ARE FOR A"T.C.O"
 AND
 MUST BE DONE BEFORE"C.O.".
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-28 Cont ID  
Sent By dpalmer Date 2000-09-28 Time 21:28 Rev Time 0.00
Received By dpalmer Date 2000-09-28 Time 21:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-28 Cont ID  
Sent By dpalmer Date 2000-07-28 Time 10:13 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-27 Cont ID  
Sent By dpalmer Date 2000-06-27 Time 19:39 Rev Time 0.00
Received By dpalmer Date 2000-06-27 Time 19:39 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT RATING AND ELEC-R
 -TRICAL DETAIL ON DIMMER PANEL.
  
 2)NOTE:PLEASE NOTE THAT GROUNDING
 ATTACHMENT NEEDS TO GO TO BLDG. STEEL
 ALSO, BOND AS REQ`D BY 250 OF NEC.
  
 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%
 INCLUDING LIGHTING ETC.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 ETX 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By mcarsill Date 2000-08-02 Time 15:56 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) TRAVEL DISTANCE NOTE ON LIFE SAFETY
 TABULATION CHART IS NOT CORRECT.
 TRAVEL DISTANCE ALLOWED IS 200 FEET NOT
 250 FEET.
 2) SEE LETTER ATTACHED TO PLANS FROM
 ED GONZALEZ FROM REG ARCHITECTS
 ADDRESSING PREVIOUS FIRE RESCUE PLAN
 REVIEW COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-23 Cont ID  
Sent By bstaples Date 2000-06-23 Time 13:33 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED SEE NOTES ATTACHED TO PLANS
 M. CARSULLO 6/23/00.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-01-30 Cont ID  
Sent By ndenmark Date 2001-01-30 Time 11:58 Rev Time 0.33
Received By ndenmark Date 2001-01-30 Time 11:58 Sent To  
Notes
2001-01-30 00:00:00AS BUILTS
 NOTE EXFAN #2 IS AIR TRANSFER NOT
 EXHAUST

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-09-27 Cont ID  
Sent By ndenmark Date 2000-09-27 Time 16:15 Rev Time 0.50
Received By ndenmark Date 2000-09-27 Time 16:15 Sent To  
Notes
2001-01-08 00:00:00REVISION PLANS NOT CITYPLACE STAMPED

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-07 Cont ID  
Sent By cthirben Date 2000-08-07 Time 09:43 Rev Time 0.00
Received By cthirben Date 2000-08-07 Time 09:44 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 *PROVIDE THE SIZE OF THE PIZZA OVEN
 EXHAUST FANS.
 *PROVIDE A THIRD M2 SHEET FOR REVIEW
 SUBMITTED ON 08.02.00.
  
 NOTE:
 SEPERATE PERMIT REQUIRED FOR HOODS,WALK-
 IN COOLERS/FREEZERS AND FIRE SUPPRESSION
 SYSTEM AT THE TIME OF PERMIT APPLICATION
 WITH THE RELEVANT INFORMATION ON THESE
 SYSTEMS...

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-27 Cont ID  
Sent By cthirben Date 2000-07-27 Time 09:51 Rev Time 0.00
Received By cthirben Date 2000-07-27 Time 09:52 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 SEPERATE PERMIT REQUIRED FOR HOOD, WALK-
 IN COOLER/FREEZER AND FIRE SUPPRESSION,
 SUBMIT PLANS AT TIME OF PERMIT APPLICA-
 TION WITH THE RELEVANT INFO ON THESE
 SYSTEMS.
 PROVISO:
 PROVIDE THE SIZE OF THE PIZZA OVEN
 EXHAUST FAN.....

Review Stop M MECHANICAL (A/C)
Rev No 1 Status A Date 2000-06-27 Cont ID  
Sent By ndenmark Date 2000-06-27 Time 14:17 Rev Time 2.00
Received By ndenmark Date 2000-06-27 Time 14:17 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED FOR AIR CONDITIONING
 PROVIDE MORE INFORMATION ON :
 WATER HEATER FLUE; LENGTH TI HGT ?
 PIZZA OVEN EXHAUST CAPACITY (LOAD)
 FIRE DAMPERS TO BE LOCATED AT SHAFT WALL
 FOR DUCTS ENTERING SHAFT
 GREASE DUCT ENCLOSURE TO BE FOR A SINGLE
 EXHAUST DUCT AND FOR NO OTHER PURPOSE
 DUCT REQUIRES MIN. 6" CLEARANCE FROM
 INSIDE OF ENCLOSURE
 PROVIDE INFORMATION ON ABOVE PRIOR TO
 MECH WORK ON THESE SYSTEMS
 SEPARATE PERMIT REQUIRED FOR HOOD, WALK
 IN COOLER/FREEZER AND FIRE SUPPRESSION
 SUBMIT PLANS AT TIME OF PERMIT APPLICA-
 TION FOR THESE SYSTEMS

Review Stop P PLUMBING
Rev No 7 Status F Date 2001-02-11 Cont ID  
Sent By pschmitz Date 2001-02-11 Time 08:34 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-02-11 00:00:00PLUMBING PLAN REVIEW, REVISION DENIED
 (1) RE: PREVIOUS COMMENTS DATED 01-31-01
 SHT P-4 GAS ISOMETRIC IS NOT AS BUILT,
 ALSO SHOW LOCATION OF SEDIMENT TRAP AND
 GAS APPLIANCE LEGEND, REQUIRED.
 SPC 94 SEC 104.3
 END OF COMMENTS QUESTIONS
 PAUL SCHMITZ 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 6 Status F Date 2001-01-31 Cont ID  
Sent By jleech Date 2001-01-31 Time 11:49 Rev Time 2.00
Received By jleech Date 2001-01-31 Time 11:48 Sent To  
Notes
2001-01-31 00:00:00DENIED;
  
 1.PAGE P-4 GAS ISOMETRIC SHUTOFF VALVE
 AND UNION AT SOLENOID VALVE MUST BE
 ADDED TO PLANS ALSO SHOW LOCATION OF
 DRIP LEGS.
  
 2.CHANGES TO WATER ISOMETRIC ARE
 EXTENSIVE PLEASE REDRAW SHOW PROPER
 SYMBOLS AND SIZES OF PIPE.
  
 3.SHT. P-3 (NOT WITH PAGES SUBMITED) TIM
 LARGE HAD PROVISOS ON THIS PAGE THAT
 NEED TO BE ADDRESSED. 3" VENT ON G.W.
 LINE AND PIPE SIZING.
  
 4.PAGE P-2 NEEDS TO BE REDRAWN USING
 PROPER SYMBOLS AND SIZES OF PIPING.
 SEE ADMINISTRATIVE CODE SEC. 104.2.1
 AND 104.2.7.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-08-18 Cont ID  
Sent By tlarge Date 2000-08-18 Time 12:45 Rev Time 0.75
Received By tlarge Date 2000-08-18 Time 12:44 Sent To  
Notes
2001-01-08 00:00:00**************PROVISO*******************
 A VENT IS REQD.DOWNSTREAM ON THE GREASY
 WASTE SYSTEM PER SPC SEC.921.
  
 2)A SHUTOFF VALVE AND UNION IS REQD.ON
 THE GAS LINE PER NFPA 96 & 54.VALVE TO
 BE LOCATED BELOW CEILING.
  
 CALL 561-659-8096,EXT.8377 IIF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLAN EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 08:22 Rev Time 0.00
Received By tlarge Date 2000-08-17 Time 08:22 Sent To  
Notes
2001-01-08 00:00:00LAYOUT OF TOILET ROOMS ON SHT.A9.1 DOES
 NOT CORRELATE W/THE REST OF THE PLANS.
  
 2)THE OCCUPANT LOAD OF 148 PEOPLE NOTED
 ON SHT.A9.1 REQUIRES 4 W.C'S FOR MALES
 AND FEMALES AND 2 LAVS.IN EACH RESTROOM.
 (TABLE 407 REQS.ARE FOR TOTAL NUMBER OF
 PERSONS.)
  
 3)THE SIZE OF THE HANDICAP STALLS DON'T
 COMPLY W/FACBC SEC.4.17.3.REVISE PLANS
 TO COMPLY.
  
 4)A VENT IS REQD.DOWNSTREAM OF ALL
 FIXTURES ON THE GREASY WASTE SYSTEM PER
 SPC SEC.921.
  
 5)A UNION IS REQD.DOWNSTREAM OF SHUTOFF
 VALVE PER NFPA 5.5.4.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 12:12 Rev Time 1.50
Received By tlarge Date 2000-08-08 Time 20:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-22 Cont ID  
Sent By pschmitz Date 2000-07-22 Time 07:49 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) PROVISO HAS BEEN MADE FOR RESUBMITAL
 DATED 06-27-00 SEE NOTES ON PLBG SHTS.
 QUESTIONS CONTACT PAUL SCHMITZ
 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-26 Cont ID  
Sent By tlarge Date 2000-06-26 Time 10:25 Rev Time 5.00
Received By tlarge Date 2000-06-26 Time 10:25 Sent To  
Notes
2001-01-08 00:00:00HANDICAP STALLS ARE REQUIRED IN THE
 MALE AND FEMALE TOILET ROOMS PER FACBC
 SEC.4.1.2.(6),4.17.3,4.22.4.
  
 LAVATORIES ARE REQD.IN THE HANDICAP
 STALLS PER FACBC SEC.4.17.3.AND SIZE
 SHALL COMPLY W/FACBC SEC.4.17.3.
  
 SHOW THE REQUIRED WHEELCHAIR TURNING
 SPACE IN THE TOILET ROOMS PER FACBC SEC.
 4.2.3.
  
 HEIGHT OF URINAL SHALL COMPLY W/FACBC
 SEC.4.18.2.
  
 SHT.P-1-FLOOR DRAINS AND FLOOR SINKS
 ARE NOT PROPERLY VENTED PER SPC SEC.
 901.2,TABLE 908.1.
  
 SHT.P-3-VENT SIZING SHALL COMPLY W/SPC
 TABLE 920.2.(DETERMINE BY FIXTURE UNIT
 LOAD.)
  
 DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY OF WPB
 ORDINANCE.
  
 A UNION IS REQD.ON THE GAS CONTROLS PER
 NFPA 54 SEC.5.5.4.
  
 SUBMIT COPY OF/OR MAKE REFERENCE TO THE
 APPROPRIATE GAS SIZING TABLE USED TO
 DESIGN THE GAS SYSTEM.COMPLY W/ SGC SEC.
 305.4.
  
 INDICATE TYPE OF PIPING MATERIAL USED
 FOR THE GAS SYSTEM.COMPLY W/SGC SEC.306.
  
 RECALCULATE THE BTU LOAD.MY CALCULATIONS
 ARE 201,198.PLEASE VERIFY.SGC 305.3.
  
 SUBMIT LEGEND FOR ALL FIXTURES NOTED BY
 NUMBERS ON SHT.P-4.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.1.
  
 OVER 2 FIXTURES SUPPLIED BY 1/2"C.W.&
 OVER 4 FIXTURES SUPPLIED BY 1/2" H.W.
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 607.7
  
 SHT.P-5-NOTE #14-PIPING INSULATION SHALL
 COMPLY W/F.E.C. TABLE 4-11.
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT.
 EQUIPMENT SHALL BE APPROVED PER SGC SEC.
 402.1.,501.2.
  
 GARBAGE DISPOSAL SHALL DISCHARGE TO THE
 SANITARY PER 1004.11.
  
 SUBMIT ADDITIONAL INFORMATION FOR THE
 WATER HEATER FLUE.INSTALLATION SHALL
 COMPLY W/STANDARD GAS AND STANDARD
 MECHANICAL CODES.(1997 EDITION.)