Plan Review Stops For Permit 00061141 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2000-08-07 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-08-07 |
Time |
08:38 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-08-01 |
|
|
Cont ID |
|
Sent By |
drunnels |
Date |
2000-08-01 |
Time |
09:45 |
Rev Time |
1.00 |
Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | 1. INDICATE FIRE SEPERATION BETWEEN | | OCCUPANCIES, 2 HOUR REQUIRED. SHOW | | LOCATION HORZINTIAL AND VERTICAL | | INDICATE UL RATING FOR ALL ASSEMBLIES | | 2. EXITS, SECOND MEANS OF EGRESS DEFINED | | ON PLANS IS BLOCKED BY A TABLE. | | REVISE. | | 3. FIRE SPRINKLER CONTRACTOR TO APPLY | | FOR PERMIT. | | 4. SIGNS REQUIRE SEPRATE PERMIT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-07-03 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-07-03 |
Time |
08:06 |
Rev Time |
2.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1. FLORIDA ENERGY SHEETS SIGNED AND | | SEALED BY DESIGNER OF RECORD AND OWNER. | | 2. INDICATE FIRE SEPERATION BETWEEN | | OCCUPANCIES 2 HR REQUIRED. SHOW LOCATION | | HORZONTIAL AND VERTICAL INDICATE UL | | RATING FOR ALL ASSEMBLIES. | | 3. EXTERIOR GLAZING IMPACT RESISTANT, | | PROVIDE PRODUCT APPROVAL. | | IF SHUTTERS USED, PROVIDE WIND LOAD | | INFORMATION FOR ALL EXTERIOR GLAZING | | PROVIDE PRODUCT APPROVAL FOR SHUTTERS. | | PROVIDE PLAN FOR INSTULLATION SIGNED BY | | OWNER SHOW STORAGE LOCATION IN UNIT. | | SHUTTER PLANS ARE SUBJECT TO APPROVAL | | BY THE BUILDING OFFICIAL SEE CITY POLICY | | 4. FIRE SPRINKLER CONTRACTOR TO APPLY | | FOR PERMIT. | | 5. EXITS, SECOND MEANS OF EGRESS DEFINED | | ON PLANS IS BLOCKED BY A TABLE. REVISE. | | 6. SIGNS REQUIRE SEPERATE PERMITS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2001-02-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-12 |
Time |
07:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-12 |
Time |
07:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2001-01-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-01-31 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-01-31 |
Time |
10:20 |
Sent To |
|
|
Notes |
2001-01-31 00:00:00 | *********** REVISION NEEDED | | ************1) NOTE: PLEASE NOTE THAT A | | MAIN DSCONNECT HAS BEEN ADDED TO PLANS | | ON SHEET E-5 FOR PANEL "K". NO SPECS | | WERE SUBMITTED | | FOR THIS EQUIPMENT. PLEASE DO SO. | | NOW THAT THERE IS A MAIN INLINE FROM | | TRANSFORMER, DOES PANEL "K " STILL HAVE | | A ,MAIN? | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRNET PER 110-9. | | THIS IS REQ`D FOR NEW PANEL "K " DISC. | | | | 3)NOTE: PLANS HAVE BEEN REDRAWN BY HAND | | AND NEEDS TO BE RE-DONE UNDER | | ADMINISTRATIVE CODE BEING SUBMITTED FOR | | RECORD. | | SEE SECTION 104.2.1 AND 104.2.7 FOR | | QUALITY OF PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. PLANS ARE FOR A"T.C.O" | | AND | | MUST BE DONE BEFORE"C.O.". | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
21:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-09-28 |
Time |
21:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-07-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-07-28 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-06-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-06-27 |
Time |
19:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-06-27 |
Time |
19:39 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | 1)NOTE: PLEASE SUBMIT RATING AND ELEC-R | | -TRICAL DETAIL ON DIMMER PANEL. | | | | 2)NOTE:PLEASE NOTE THAT GROUNDING | | ATTACHMENT NEEDS TO GO TO BLDG. STEEL | | ALSO, BOND AS REQ`D BY 250 OF NEC. | | | | 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS. | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% | | INCLUDING LIGHTING ETC. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 ETX 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-08-02 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) TRAVEL DISTANCE NOTE ON LIFE SAFETY | | TABULATION CHART IS NOT CORRECT. | | TRAVEL DISTANCE ALLOWED IS 200 FEET NOT | | 250 FEET. | | 2) SEE LETTER ATTACHED TO PLANS FROM | | ED GONZALEZ FROM REG ARCHITECTS | | ADDRESSING PREVIOUS FIRE RESCUE PLAN | | REVIEW COMMENTS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-06-23 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-06-23 |
Time |
13:33 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED SEE NOTES ATTACHED TO PLANS | | M. CARSULLO 6/23/00. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2001-01-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2001-01-30 |
Time |
11:58 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2001-01-30 |
Time |
11:58 |
Sent To |
|
|
Notes |
2001-01-30 00:00:00 | AS BUILTS | | NOTE EXFAN #2 IS AIR TRANSFER NOT | | EXHAUST |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-09-27 |
Time |
16:15 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-09-27 |
Time |
16:15 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISION PLANS NOT CITYPLACE STAMPED |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2000-08-07 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-08-07 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-08-07 |
Time |
09:44 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: | | *PROVIDE THE SIZE OF THE PIZZA OVEN | | EXHAUST FANS. | | *PROVIDE A THIRD M2 SHEET FOR REVIEW | | SUBMITTED ON 08.02.00. | | | | NOTE: | | SEPERATE PERMIT REQUIRED FOR HOODS,WALK- | | IN COOLERS/FREEZERS AND FIRE SUPPRESSION | | SYSTEM AT THE TIME OF PERMIT APPLICATION | | WITH THE RELEVANT INFORMATION ON THESE | | SYSTEMS... |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2000-07-27 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-07-27 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-07-27 |
Time |
09:52 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NOTES: | | SEPERATE PERMIT REQUIRED FOR HOOD, WALK- | | IN COOLER/FREEZER AND FIRE SUPPRESSION, | | SUBMIT PLANS AT TIME OF PERMIT APPLICA- | | TION WITH THE RELEVANT INFO ON THESE | | SYSTEMS. | | PROVISO: | | PROVIDE THE SIZE OF THE PIZZA OVEN | | EXHAUST FAN..... |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
A |
Date |
2000-06-27 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-06-27 |
Time |
14:17 |
Rev Time |
2.00 |
Received By |
ndenmark |
Date |
2000-06-27 |
Time |
14:17 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ACCEPTED FOR AIR CONDITIONING | | PROVIDE MORE INFORMATION ON : | | WATER HEATER FLUE; LENGTH TI HGT ? | | PIZZA OVEN EXHAUST CAPACITY (LOAD) | | FIRE DAMPERS TO BE LOCATED AT SHAFT WALL | | FOR DUCTS ENTERING SHAFT | | GREASE DUCT ENCLOSURE TO BE FOR A SINGLE | | EXHAUST DUCT AND FOR NO OTHER PURPOSE | | DUCT REQUIRES MIN. 6" CLEARANCE FROM | | INSIDE OF ENCLOSURE | | PROVIDE INFORMATION ON ABOVE PRIOR TO | | MECH WORK ON THESE SYSTEMS | | SEPARATE PERMIT REQUIRED FOR HOOD, WALK | | IN COOLER/FREEZER AND FIRE SUPPRESSION | | SUBMIT PLANS AT TIME OF PERMIT APPLICA- | | TION FOR THESE SYSTEMS |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
F |
Date |
2001-02-11 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2001-02-11 |
Time |
08:34 |
Rev Time |
2.00 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-02-11 00:00:00 | PLUMBING PLAN REVIEW, REVISION DENIED | | (1) RE: PREVIOUS COMMENTS DATED 01-31-01 | | SHT P-4 GAS ISOMETRIC IS NOT AS BUILT, | | ALSO SHOW LOCATION OF SEDIMENT TRAP AND | | GAS APPLIANCE LEGEND, REQUIRED. | | SPC 94 SEC 104.3 | | END OF COMMENTS QUESTIONS | | PAUL SCHMITZ 561-659-8096 X 8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
F |
Date |
2001-01-31 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2001-01-31 |
Time |
11:49 |
Rev Time |
2.00 |
Received By |
jleech |
Date |
2001-01-31 |
Time |
11:48 |
Sent To |
|
|
Notes |
2001-01-31 00:00:00 | DENIED; | | | | 1.PAGE P-4 GAS ISOMETRIC SHUTOFF VALVE | | AND UNION AT SOLENOID VALVE MUST BE | | ADDED TO PLANS ALSO SHOW LOCATION OF | | DRIP LEGS. | | | | 2.CHANGES TO WATER ISOMETRIC ARE | | EXTENSIVE PLEASE REDRAW SHOW PROPER | | SYMBOLS AND SIZES OF PIPE. | | | | 3.SHT. P-3 (NOT WITH PAGES SUBMITED) TIM | | LARGE HAD PROVISOS ON THIS PAGE THAT | | NEED TO BE ADDRESSED. 3" VENT ON G.W. | | LINE AND PIPE SIZING. | | | | 4.PAGE P-2 NEEDS TO BE REDRAWN USING | | PROPER SYMBOLS AND SIZES OF PIPING. | | SEE ADMINISTRATIVE CODE SEC. 104.2.1 | | AND 104.2.7. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2000-08-18 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-18 |
Time |
12:45 |
Rev Time |
0.75 |
Received By |
tlarge |
Date |
2000-08-18 |
Time |
12:44 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | **************PROVISO******************* | | A VENT IS REQD.DOWNSTREAM ON THE GREASY | | WASTE SYSTEM PER SPC SEC.921. | | | | 2)A SHUTOFF VALVE AND UNION IS REQD.ON | | THE GAS LINE PER NFPA 96 & 54.VALVE TO | | BE LOCATED BELOW CEILING. | | | | CALL 561-659-8096,EXT.8377 IIF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLAN EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2000-08-17 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-17 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
tlarge |
Date |
2000-08-17 |
Time |
08:22 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | LAYOUT OF TOILET ROOMS ON SHT.A9.1 DOES | | NOT CORRELATE W/THE REST OF THE PLANS. | | | | 2)THE OCCUPANT LOAD OF 148 PEOPLE NOTED | | ON SHT.A9.1 REQUIRES 4 W.C'S FOR MALES | | AND FEMALES AND 2 LAVS.IN EACH RESTROOM. | | (TABLE 407 REQS.ARE FOR TOTAL NUMBER OF | | PERSONS.) | | | | 3)THE SIZE OF THE HANDICAP STALLS DON'T | | COMPLY W/FACBC SEC.4.17.3.REVISE PLANS | | TO COMPLY. | | | | 4)A VENT IS REQD.DOWNSTREAM OF ALL | | FIXTURES ON THE GREASY WASTE SYSTEM PER | | SPC SEC.921. | | | | 5)A UNION IS REQD.DOWNSTREAM OF SHUTOFF | | VALVE PER NFPA 5.5.4. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-10 |
Time |
12:12 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-08-08 |
Time |
20:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-07-22 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2000-07-22 |
Time |
07:49 |
Rev Time |
2.50 |
Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | (1) PROVISO HAS BEEN MADE FOR RESUBMITAL | | DATED 06-27-00 SEE NOTES ON PLBG SHTS. | | QUESTIONS CONTACT PAUL SCHMITZ | | 561-659-8096 X 8233 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-06-26 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-06-26 |
Time |
10:25 |
Rev Time |
5.00 |
Received By |
tlarge |
Date |
2000-06-26 |
Time |
10:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | HANDICAP STALLS ARE REQUIRED IN THE | | MALE AND FEMALE TOILET ROOMS PER FACBC | | SEC.4.1.2.(6),4.17.3,4.22.4. | | | | LAVATORIES ARE REQD.IN THE HANDICAP | | STALLS PER FACBC SEC.4.17.3.AND SIZE | | SHALL COMPLY W/FACBC SEC.4.17.3. | | | | SHOW THE REQUIRED WHEELCHAIR TURNING | | SPACE IN THE TOILET ROOMS PER FACBC SEC. | | 4.2.3. | | | | HEIGHT OF URINAL SHALL COMPLY W/FACBC | | SEC.4.18.2. | | | | SHT.P-1-FLOOR DRAINS AND FLOOR SINKS | | ARE NOT PROPERLY VENTED PER SPC SEC. | | 901.2,TABLE 908.1. | | | | SHT.P-3-VENT SIZING SHALL COMPLY W/SPC | | TABLE 920.2.(DETERMINE BY FIXTURE UNIT | | LOAD.) | | | | DISHWASHER SHALL DISCHARGE TO THE | | SANITARY SYSTEM PER CITY OF WPB | | ORDINANCE. | | | | A UNION IS REQD.ON THE GAS CONTROLS PER | | NFPA 54 SEC.5.5.4. | | | | SUBMIT COPY OF/OR MAKE REFERENCE TO THE | | APPROPRIATE GAS SIZING TABLE USED TO | | DESIGN THE GAS SYSTEM.COMPLY W/ SGC SEC. | | 305.4. | | | | INDICATE TYPE OF PIPING MATERIAL USED | | FOR THE GAS SYSTEM.COMPLY W/SGC SEC.306. | | | | RECALCULATE THE BTU LOAD.MY CALCULATIONS | | ARE 201,198.PLEASE VERIFY.SGC 305.3. | | | | SUBMIT LEGEND FOR ALL FIXTURES NOTED BY | | NUMBERS ON SHT.P-4.COUNTYWIDE AMENDMENTS | | TO SPC SEC.104.2.1. | | | | OVER 2 FIXTURES SUPPLIED BY 1/2"C.W.& | | OVER 4 FIXTURES SUPPLIED BY 1/2" H.W. | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | 607.7 | | | | SHT.P-5-NOTE #14-PIPING INSULATION SHALL | | COMPLY W/F.E.C. TABLE 4-11. | | | | SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT. | | EQUIPMENT SHALL BE APPROVED PER SGC SEC. | | 402.1.,501.2. | | | | GARBAGE DISPOSAL SHALL DISCHARGE TO THE | | SANITARY PER 1004.11. | | | | SUBMIT ADDITIONAL INFORMATION FOR THE | | WATER HEATER FLUE.INSTALLATION SHALL | | COMPLY W/STANDARD GAS AND STANDARD | | MECHANICAL CODES.(1997 EDITION.) |
|
|