Plan Review Details - Permit 00061076
Plan Review Stops For Permit 00061076
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-07-19 Cont ID  
Sent By fknapp Date 2000-07-19 Time 11:44 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER B.STAPLES

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-07-14 Cont ID  
Sent By bstaples Date 2000-07-14 Time 08:52 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. ITEM 5 SPECIAL INSPECTOR LETTER NOT
 ON FILE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-13 Cont ID  
Sent By bstaples Date 2000-07-13 Time 10:36 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. SEE ITEMS 2 & 5 PRIOR REVIEW. NOT
 SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-22 Cont ID  
Sent By bstaples Date 2000-06-22 Time 12:50 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FIRE SPRINKLER PERMIT REQUIRED BEFORE
 BUILDING PERMIT CAN BE ISSUED.
 2. PROVIDE PRODUCT APPROVAL FOR WINDOW
 SYSTEM, METRO DADE COUNTY OR SBC 1997.
 NOTE: DOORS OK.
 3. FLORIDA ENERGY SHEETS NOT SIGNED BY
 OWNER.
 4. SIGNS REQUIRE SEPERATE PERMITS.
 5. LETTER FROM SPECIAL INSPECTOR
 RELEASING THE SPACE FOR PERMIT.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2000-09-28 Cont ID  
Sent By dpalmer Date 2000-09-28 Time 17:34 Rev Time 0.00
Received By dpalmer Date 2000-09-28 Time 17:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-18 Cont ID  
Sent By dpalmer Date 2000-09-18 Time 17:33 Rev Time 0.00
Received By dpalmer Date 2000-09-18 Time 19:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-13 Cont ID  
Sent By dpalmer Date 2000-07-13 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2000-07-13 Time 10:49 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: PLEASE SEE ORIG. NOTES. THE
 DIMMER SCHEDULE SHOWS SWITCH #6 FOR
 FIXTURE "X" WHICH IS SHOWN AS EXIT SIGN.
 SWITCHING THE EXIT SIGN IS NOT PERMITTED
 IF THIS IS NOT THE CASE PLEASE CLARIFY.
  
 2)NOTE: PLEASE SEE AND NOTE THAT ON E-1
 YOU SHOW TWO WATER HEATERS @ 3500W? YET
 THE LOAD CALCULATION SHOWS A TOTAL OF
 4800W? PLEASE CHECK AND RE-DO.
  
 3)NOTE: PLEASE SEE E-2. THE SHOW WINDOW
 LIGHTING IS SHOWMN AT .4 KVA. AND ON
 E-1 ITIS SHOWN AT .45 KVA. 125% OF
 .4 IS NOT .45. PLEASE VERIFY.
  
 4)NOTE: PLEASE SUBMIT THE AIC RATINGS OF
 THE DISCONNECTS. IT APPEARS THAT THEY
 ARE FUSED DISC. PLEASE GIVE FUSE TYPE.
  
  
 5)NOTE: AS BEFORE; PLEASE SHOW DIMMER
 LOCATION ON PLANS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 561-659-8096 EXT 8372
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-21 Cont ID  
Sent By dpalmer Date 2000-06-21 Time 22:00 Rev Time 0.00
Received By dpalmer Date 2000-06-21 Time 10:44 Sent To  
Notes
2001-01-08 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL DIMMER/SWITCH
 LOCATIONS.
  
 2)NOTE: PLEASE NOTE THAT EXIT LIGHTS ARE
 SHOWN ON SWITCH #6??? THIS IS NOT
 PERMITTED AND EMERGENCY LIGHTS ALSO.
  
 3)NOTE:PLEASE NOTE THAT LOAD OF TRACK
 LIGHTING NEEDS TO BE SHOWN SEPARATE
 IN CALCULATIONS.ALSO AT 125% FOR CONTIN-
 UOUS LOAD.22-12
  
 4)NOTE:SHOW WINDOW IS SHOWNON PANEL AT
 .4 KW AND ON LOAD CALCS AT .45KW?
 PLEASE CORRELATE
  
 5)NOTE:PLEASE SUBMIT AIC RATING OF MAIN
 DISCONNECTS.MAINS//PANLES ARE TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9/215-5
  
 ^0NOTE:LIGHTING IS SHOWN ON LOAD CALCS
 AT 1,630,,,3W-PER-SQ-AT 125% YOU SHOW
 TOTAL AT 4,890? PLEASE SHOW,,,I COME UP
 WITHA DIFFERENT TOTAL.
  
 7)NOTE:PLEASE SEE LOAD CALCS,,YOU SHOW
 LOADS FOR WATER HEATERS AT 3500 EACH
 AND DIFFERENT TOTAL LOAD?? THIS ALSO
 DOES NOT CORRELATE WITH PANEL SCHEDLUE?
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-23 Cont ID  
Sent By bstaples Date 2000-06-23 Time 13:38 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO SEE NOTES ATTACHED TO PLANS,
 M. CARSILLO 6/23/00

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 18:05 Rev Time 1.00
Received By cthirben Date 2000-07-18 Time 18:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-13 Cont ID  
Sent By cthirben Date 2000-07-13 Time 11:33 Rev Time 0.00
Received By cthirben Date 2000-07-13 Time 13:41 Sent To  
Notes
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89.
 2.REQUIRES AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-21 Cont ID  
Sent By cthirben Date 2000-06-21 Time 16:05 Rev Time 1.00
Received By cthirben Date 2000-06-21 Time 15:59 Sent To  
Notes
2001-01-08 00:00:00DENIED*******************************
 1. PROVIDE OUTSIDE CALCULATIONS PER
 ASHRAE 62-89.
 2. REQUIRES AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
 3. NFPA 90A REQUIRES NOTICATION OF
 ACTIVATION OF DUCT SMOKE DETECTOR BY
 VISUAL AND AUDIBLE SIGNAL. THIS IS
 NOT REQUIRED TO BE TIED IN TO THE
 MALL FIRE ALARM SYSTEM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-22 Cont ID  
Sent By tlarge Date 2000-09-22 Time 12:39 Rev Time 0.30
Received By tlarge Date 2000-09-22 Time 12:39 Sent To  
Notes
2001-01-08 00:00:00ADD POINT OF USE WATER HEATER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-22 Cont ID  
Sent By tlarge Date 2000-06-22 Time 05:36 Rev Time 0.50
Received By tlarge Date 2000-06-22 Time 05:36 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 DRESSING ROOM SHALL COMPLY W/FACBC SEC.
 4.35.(A BENCH IS REQD.ALONG THE WALL W/
 THE LONGER DIMENSION.)