Plan Review Details - Permit 00060937
Plan Review Stops For Permit 00060937
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-28 Cont ID  
Sent By dpalmer Date 2000-07-28 Time 06:18 Rev Time 0.00
Received By dpalmer Date 2000-07-28 Time 06:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-21 Cont ID  
Sent By dpalmer Date 2000-06-21 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2000-06-21 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE LIST AIC RATING FOR ALL
 EQUIPMENT MAINS AND PANELS. MAINS AND
 PANELS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. PER 110-9.
  
 2)NOTE:PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210-8-A-6 SHOW IN BOTH UNITS.
  
 3)NOTE: PLEASE INCLUDE COPPER COLD
 WATER PIPE AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250-50
  
 4)NOTE:PLEASE SHOW ON PANEL SCHEDULES
 THE REQ`D BATH(S) CIRCUIT(S) AS PER
 210-11-C-3. MUST BE SHOWN AS 20AMP AND
 #12 AWG..
  
 5)NOTE: PLEASE SHOW TWO SEPARATE PANEL
 SCHEDULES FOR THE TWO UNITS.
  
 6)NOTE: YOU SHOW 'TV BOX' NEXT TO THE
 METERCAN. PLEASE SHYOW THE DISCONNECT
 THAT YOU SHOW ON THE RISER DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-08 Cont ID  
Sent By cthirben Date 2000-08-08 Time 15:45 Rev Time 1.00
Received By cthirben Date   Time 15:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-31 Cont ID  
Sent By cthirben Date 2000-07-31 Time 09:31 Rev Time 0.00
Received By cthirben Date 2000-08-08 Time 15:42 Sent To  
Notes
2001-01-08 00:00:00DENIED
 A/C UNIT ON PLANS IS TOO SMALL FOR
 SUPPLY.
 INFORMED CUSTOMER AT DIVOSTA. 07.31.00
 AT 9:20AM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-21 Cont ID  
Sent By cthirben Date 2000-06-21 Time 10:12 Rev Time 0.00
Received By cthirben Date 2000-06-21 Time 11:15 Sent To  
Notes
2001-01-08 00:00:00****DENIED******************************
 PROVIDE THE FOLLOWING INFORMATION:
 1. MODEL NUMBER,MAKE AND SIZE OF ALL THE
 EXHAUST FANS REQUIRED.
 2. LOCATION &SIZE OF THE CONDENSATE
 LINES 1997 SMC 304.8.3
 3. INDICATE THE LOCATION OF THE CONDEN-
 SATE UNIT.
 4. SHOW THE LOCATION OF THE DRYER VENT.
 1997 SMC 509.3
 5. PROVIDE CFM VALUE OF ALL A/C DROPS ON
 BOTH BUILDING ALSO THE DUCT SIZES.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-07-28 Cont ID  
Sent By tlarge Date 2000-07-28 Time 18:18 Rev Time 0.30
Received By tlarge Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-28 Cont ID  
Sent By tlarge Date 2000-07-28 Time 18:08 Rev Time 0.30
Received By tlarge Date 2000-07-28 Time 18:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-17 Cont ID  
Sent By tlarge Date 2000-06-17 Time 07:05 Rev Time 0.50
Received By tlarge Date 2000-06-17 Time 07:05 Sent To  
Notes
2001-01-08 00:00:00SHOWER ON 2ND.FLOOR SHALL BE SEPARATELY
 VENTED PER SPC 913.2.
  
 MAX.2 WATER CLOSETS ON 3"BUILDING DRAIN
 PER TABLE 714.1 FOOTNOTES #3.
  
 MIN.SIZE OF BUILDING SEWER SHALL BE 4"
 PER TABLE 714.1 FOOTNOTE #2.

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2000-12-12 Cont ID  
Sent By jgomez Date 2000-12-12 Time 10:41 Rev Time 1.00
Received By jgomez Date 2000-12-12 Time 10:41 Sent To  
Notes
2001-01-08 00:00:00STORM PANELS REVISION.

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2000-11-28 Cont ID  
Sent By jgomez Date 2000-11-28 Time 17:08 Rev Time 0.50
Received By jgomez Date 2000-11-28 Time 17:07 Sent To  
Notes
2001-01-08 00:00:00TRUSS DRAWINGS REVISION CHECKLIST:
 1-ALL TRUSS DRAWINGS NEED TO BE REVIEWED
 BY THE ARCHITECT OF RECORD PRIOR TO
 SUBMITTAL TO THIS OFFICE.
 2-TRUSS ENGINEER TO SIGN AND SEAL TRUSS
 LAYOUT AS WELL.
 3-REVISE TRUSS ANCHOR SCHEDULE AS
 REQUIRED TO RESIST THE UPLIFT LOADS
 CALCULATED FOR THE ENGINEERED ROOF
 TRUSSES.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-08-10 Cont ID  
Sent By jgomez Date 2000-08-10 Time 12:05 Rev Time 0.50
Received By jgomez Date 2000-08-10 Time 12:05 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-RECEIVED LETTER FROM METRO DADE COUNTY
 STATING THAT PRODUCT APPROVAL FOR
 0.050" BERTHA STORM PANEL IS UNDER THE
 RENEWAL PROCESS.
 -PLEASE PROVIDE COPIES OF UPDATED
 PRODUCT APPROVALS ONCE RENEWAL IS
 ISSUED.
 2-EXTERIOR DOORS AND WINDOWS:
 -PROVIDE SITE SPECIFIC PRODUCT APPROVAL
 FOR EACH UNIT.
 3-BATH AT FIRST FLOOR MUST HAVE DOOR
 THAT PROVIDES 29" MINIMUM CLEAR OPN'G
 AS PER CHAPTER 11 OF FLORIDA
 ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-07-26 Cont ID  
Sent By jgomez Date 2000-07-26 Time 15:52 Rev Time 3.00
Received By jgomez Date 2000-07-26 Time 17:36 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-EXTERIOR DOORS AND WINDOWS:
 -SINCE NORANDEX DOESN'T HAVE APPROVED
 PRODUCT APPROVAL, THEN PROVIDE A SITE
 SPECIFIC PRODUCT APPROVAL FOR EACH
 UNIT SIGNED, SEALED AND DATED BY THE
 MANUFACTURER ENGINEER AND BY THE
 ENGINEER OF RECORD.
 -SLIDING GLASS DOORS: PROVIDE COPIES OF
 THE TESTS PERFORMED AS PER ASTM E330.
 SECTION 1706 SBC 1997.
 2-BATH AT FIRST FLOOR MUST HAVE DOOR
 THAT PROVIDES 29" MINIMUM CLEAR
 OPENING AS PER CHAPTER 11 OF FLORIDA
 ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-07-06 Cont ID  
Sent By jgomez Date 2000-07-06 Time 20:13 Rev Time 3.00
Received By jgomez Date 2000-07-06 Time 20:13 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-BATH AT FIRST FLOOR TO HAVE DOOR THAT
 PROVIDES A 29" MINIMUM CLEAR OPENING.
 CHAPTER 11 OF FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION, 1997.
 2-PROVIDE PRODUCT APPROVAL FROM SBCCI OR
 DADE COUNTY FOR ALL WINDOWS, INCLUDING
 THE OCTAGON WINDOW, OR SITE SPECIFIC
 ENGINEERING FOR EACH HOUSE.
 -SLIDING GLASS DOORS: PROVIDE COPIES OF
 TESTS RESULTS AS PER ASTM E 330.
 SECTION 1706 SBC 1997.
 PROVIDE SITE SPECIFIC ENGINEERING.
 3-ENTRY DOOR PRODUCT APPROVAL HAS
 EXPIRED.
 -PROVIDE COPIES OF APPROVED DWGS ALSO.
 4-REVISE/UPDATE DRAWINGS SEE COMMENTS ON
 PLANS.
 5-POVIDE SOIL TESTS REPORT AS PER CITY
 AMENDMENTS SECTION 1804.2.7.3.
 6-PROVIDE UPDATE PRODUCT APPROVAL FOR
 STORM PANELS. THE ONE SUBMITTED IS
 ABOUT TO EXPIRE.
  
 NOTES:
 -SEE COMMENTS BY OTHER TRADES.
 -PLEASE RETURN REVIEWED SET IN ORDER
 EXPEDITE THE REVIEW PROCESS.
 -TOTAL CALCULATED VALUATION IS $118,803.
 CALCULATED AS FOLLOWS:
 $69.69 $/SF FOR A/C AREAS AND
 $36.40 $/SF FOR NON A/C AREAS.