Plan Review Details - Permit 00060163
Plan Review Stops For Permit 00060163
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2001-03-12 Cont ID  
Sent By jwitmer Date 2001-03-12 Time 10:36 Rev Time 1.50
Received By jwitmer Date   Time   Sent To  
Notes
2001-03-12 00:00:00TRUSS DRAWINGS : REVIEWED 03/12/01 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2001-01-25 Cont ID  
Sent By jwitmer Date 2001-01-25 Time 07:51 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-25 00:00:00TRUSS PLAN REVIEW:
 1) TRUSS PLANS ARE TO BE REVIEWED &
 APPROVED BY ARCHITECT.
 2). THERE IS NO TRUSS ANCHOR SCHEDULE IN
 EITHER THE STRUCTURAL OR ACCHETECTURAL
 PLANS.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2001-01-25 Cont ID  
Sent By jwitmer Date 2001-01-25 Time 07:47 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2001-01-25 00:00:0001/24/01 TRUSS PLAN REVIEW:
 UNSAT- 1).ARCHETECT TO REVIEW AND
 APPROVE.
 2). THERE IS NO ANCHOR SCHEDULE IN
 EITHER THE STRUCTURAL OR ARCHETURAL PLAN
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX. 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-10-20 Cont ID  
Sent By hpiskura Date 2000-10-20 Time 13:28 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO NEEDS SKYLIGHT TEST REPORT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-10-04 Cont ID  
Sent By hpiskura Date 2000-10-04 Time 16:42 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER W/ APPLICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-11 Cont ID  
Sent By hpiskura Date 2000-09-11 Time 09:16 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00LETTER W/ APPLICATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-14 Cont ID  
Sent By hpiskura Date 2000-07-14 Time 09:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-10-04 Cont ID  
Sent By dpalmer Date 2000-10-04 Time 11:45 Rev Time 0.00
Received By dpalmer Date 2000-10-04 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 21:23 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 21:23 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE ADDRESS FIRST SET OF NOTE
 -S. PLEASE SUBMIT COMPLETED LOAD CALCU-
 -LATIONS AND SHOW ALL CONTINUOUS LOADS
 AND LARGEST MOTOR AT 125%.
 2)NOTE: PLEASE SEE 240-3-D FOR OCP
 OF CIRCUIT #13 OF PANEL "LB" .
 PLEASE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-29 Cont ID  
Sent By dpalmer Date 2000-06-29 Time 19:38 Rev Time 0.00
Received By dpalmer Date 2000-06-29 Time 19:38 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 WITH ALL CONTINUOUS LOADS AT 125%.
 LIGHTING ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2000-10-17 Cont ID  
Sent By mgonzale Date 2000-10-17 Time 14:27 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00APPROVED
 PLANS HAVE BEEN REVISED AND A HEALTH
 DEPARTMENET PERMIT WILL BE OBTAINED
 AND THROUGH CWPB PUBLIC UTILITIES DEPT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2000-10-04 Cont ID  
Sent By mgonzale Date 2000-10-04 Time 13:04 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAILED
  
 1.DOUBLE DETECTOR CHECK VALVE NEEDS TO
 MOVE TO THE FRONT OF THE PROPERTY. JUST
 INSIDE OF PROPERTY LINE.
  
 2. TWO COPIES OF THE PLANS SHOULD BE PRO
 VIDED TO MANNY GONZALEZ @ ENGINEERING SV
 1000 45TH STREET SUITE 15
 WPB FL 33407
 (561) 659-8040 EXT. 2306
 ONE FOR OUR UTILITY FILE AND ONE FOR
 THE CONSTRUCTION COORDINATOR WHO WILL
 SUPERVISE THE TAPPING.
 A MINIMUM OF 2 SETS OF SHOP DRAWINGS
 SHALL BE SUBMITTED TO THE SAME CONTACT
 FOR THE WORK PERFORMED OUT IN THE CITY
 ROW TO THE SAME CONTACT.
  
 A ROW PERMIT WILL HAVE TO BE ACQUIRED TO
 PERFORM THE TAPP OR ANY OTHER WORK IN TH
 E CITY ROW.
  
 YOUR DESIGNMEETS THE CRITERIA THAT
 REQUIRES A PALM BEACH COUNTY HEALTH DEPT
 PERMIT. (OVER 100 LINEAR FEET OF 6" PIPE
  
 MUST SHOW SANITARY SEWER MAIN AND PROVID
 E CLEARANCES AN 18" MINIMUM CLEARANCE
 IS REQUIRED BETWEEN WATER AND SEWER.
  
 A 12" MINIMUM CLEARANCE WILL BE REQUIRED
 BETWEEN WATERMAIN AND GAS MAIN.
  
 THESE COMMENTS MUST BE REVISED ON SHEET
 C-1 OF 7 AND ON FIRE SPRINKLER PLANS.
  
 IF ANY QUESTIONS OR COMMENTS FEEL FREE
 TO CONTACT ME AT 561 659 8040 EXT. 2306

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2000-10-20 Cont ID  
Sent By mcarsill Date 2000-10-20 Time 13:04 Rev Time 0.00
Received By mcarsill Date 2000-10-20 Time 13:04 Sent To  
Notes
2001-01-08 00:00:001) RECEIVED LETTER FROM COLIN PRICE
 OF REG ARCHITECTS. THE LETTER INDICATED
 FLAME SPREAD RATINGS AND THE RELOCATION
 OF THE BACKFLOW AND FIRE DEPARTMENT
 CONNECTION DEVICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-10-04 Cont ID  
Sent By mcarsill Date 2000-10-04 Time 12:42 Rev Time 0.00
Received By mcarsill Date 2000-10-04 Time 12:42 Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISHES ON PAGE A12.2 IS
 STILL INCORRECT. THE CORRECT DATA IS
 STILL MISSING AND THE INFORMATION
 PROVIDED DOES NOT CORRESPOND WITH
 NFPA 101, THE LIFE SAFETY CODE, 1985
 EDITION.
 2) FIRE DEPARTMENT CONNECTION IS TO BE
 LOCATED NEAR PINEWOOD AVENUE INSTEAD
 OF THE WEST SIDE OF THE BUILDING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-09-06 Cont ID  
Sent By mcarsill Date 2000-09-06 Time 15:08 Rev Time 0.00
Received By mcarsill Date 2000-09-06 Time 15:08 Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER DRAWINGS ON PAGE
 A8.1.THE FIRE SPRINKLER DRAWING DOES
 NOT INCLUDE LOCATION OF FIRE DEPARTMENT
 CONNECTION OR LOCATION OF FIRE HYDRANTS.
 2) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM DRAWINGS AND CUT SHEETS FOR FIRE
 ALARM EQUIPMENT SHOWN ON PLANS. A
 SEPARATE PLAN AND PERMIT ARE REQUIRED.
 3) PLEASE CHECK THE INTERIOR FINISH
 SCHEDULE ON PAGE A12.2. SINCE THE
 BUILDING IS A MIXED OCCUPANCY, THE MOST
 STRINGENT FLAME SPREAD CRITERIA IS TO
 BE USED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-18 Cont ID  
Sent By mcarsill Date 2000-07-18 Time 09:31 Rev Time 1.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.
 FIRE ALARM SYSTEM SHALL BE CLASS "A" OR
 ADDRESSABLE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-12 Cont ID  
Sent By ndenmark Date 2000-07-12 Time 14:49 Rev Time 1.00
Received By ndenmark Date 2000-07-12 Time 14:49 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 OUTSIDE AIR QUANTITIES SHALL NOT BE REDU
 CED BELOW VALUES GIVEN CO SENSOR TO
 INCREASE ABOVE MINIMUM VALUES

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-03 Cont ID  
Sent By tlarge Date 2000-10-03 Time 19:01 Rev Time 2.50
Received By tlarge Date 2000-10-03 Time 19:00 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO******************
 SUBMIT A SANITARY RISER THAT COMPLIES W/
 THE STANDARD PLUMBING CODE PRIOR TO
 INSPECTION.
 A)WATER CLOSETS NOT PERMITTED ON WET
 VENTS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 B)CIRCUIT AND LOOP SYSTEM SHALL COMPLY
 W/SPC SEC.914.1,914.2,914.3.4,920.3,IF
 THAT IS THE INTENT OF THE DESIGN.I HAVE
 NO IDEA WHAT YOU ARE ATTEMPTING WITH THE
 SANITARY SYSTEM AS DRAWN.
  
 C)CLEARLY INDICATE ON THE PLAN WHERE
 SANITARY RISERS #5-8 CONNECT TO RISERS
 #1-4.COUNTYWIDE AMENDMENTS 104.2.1.
  
 D)CONDENSATE DRAIN SHALL BE EQUIPPED W/
 AN EMERGENCY OVERFLOW.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-07 Cont ID  
Sent By tlarge Date 2000-09-07 Time 16:20 Rev Time 1.50
Received By tlarge Date 2000-09-07 Time 12:03 Sent To  
Notes
2001-01-08 00:00:001)THE WAIVER FOR THE GREASE TRAP SHALL
 BE SIGNED BY R.COMPO.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.101.4.7.
  
 2)THE LOCATION OF THE HANDICAP
 FACILITIES ON SHT.P2.1 DOESN'T CORRELATE
 W/THE ARCHITECTURAL PLANS.CLARIFY.
  
 3)THE SANITARY RISER SHALL CORRELATE W/
 THE CORRECT FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 4)WATER CLOSETS ARE NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 5)THE HABITABLE SQUARE FEET AND OCCUPANT
 SHALL BE ON THE PLANS.SPC SEC.407.1.3.
  
 6)A DEP PERMIT IS REQD.FOR THE INSTALL-
 ATION OF THE WATER SYSTEMS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.7.
  
 7)AN EMERGENCY OVERFLOW IS REQD.ON THE
 CONDENSATE DRAIN TO THE DRYWELL.
  
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-17 Cont ID  
Sent By tlarge Date 2000-06-17 Time 09:38 Rev Time 2.75
Received By tlarge Date 2000-06-17 Time 09:38 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD OF STRUCTURE
 BASED ON HABITABLE FLOOR SPACE PER TABLE
 407 0F THE SPC.MINIMUM SANITARY REQS.
 SHALL BE BASED UPON THIS OCCUPANT LOAD.
  
 A HANDICAP STALL W/LAVATORY SHALL BE
 PROVIDED IN THE RESTROOMS PER FACBC
 SECS.4.17.3, 4.22.4.
  
 SHT.A9.1-DETAIL #7-H.C.URINAL SHALL BE
 MOUNTED MAX.17"PER FACBC SEC.4.18.2.
  
 MAX.TEMPERATURE OF WATER TO RESTROOMS
 SHALL BE 110 DEGREES PER F.E.C SEC.
 412.1ABCD.2.3.2.
  
 DRINKING FOUNTAIN AT VOLLEYBALL COURT
 SHALL BE H.C. ACCESSIBLE AND ON AN
 ACCESSIBLE ROUTE PER FACBC SEC.4.3
  
 SUBMIT COMPLETE STORM DRAINAGE ISOMETRIC
 FOR REVIEW.SHOW SLOPE OF PIPE,PIPE SIZES
 AND PROVISIONS FOR SECONDARY(EMERGENCY)
 DRAINAGE.COMPLY W/SPC SEC.1108.1, 1108.2
 1109.1,1109.3 AND APPENDIX "A".
  
 A GREASE TRAP IS REQUIRED ON THE
 SANITARY SYSTEM PER SPC SEC.1004.4.
 CONTACT R.COMPO AT CITY OF W.P.B.
 (561)835-7423.SUBMIT APPROVAL FORM FROM
 UTILITIES FOR GREASE TRAP. SUBMIT DETAIL
 OF GREASE TRAP.
  
 SHT.P3.1-WATER CLOSETS NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC SEC.914.1.
  
 EMERGENCY OVERFLOW IS REQD.ON THE COND.
 DRAIN TO DRYWELL.SPC 701.4,
  
 SUBMIT WATER ISOMETRIC FOR ALL AREAS OF
 NEW WORK.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 A DEP PERMIT IS REQD.FOR THE INSTALL-
 ATION OF THE WATER SYSTEMS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.7.
  
 CLEARLY SHOW LENGTH AND WIDTH OF TOILET
 ROOMS AND STALLS.COMPLY W/FACBC SECS.
 4.17.3.,4.16.2.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By gjoyce Date 2000-06-06 Time 10:22 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***