Plan Review Stops For Permit 00060163 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2001-03-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-03-12 |
Time |
10:36 |
Rev Time |
1.50 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-03-12 00:00:00 | TRUSS DRAWINGS : REVIEWED 03/12/01 JW |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2001-01-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-01-25 |
Time |
07:51 |
Rev Time |
1.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-25 00:00:00 | TRUSS PLAN REVIEW: | | 1) TRUSS PLANS ARE TO BE REVIEWED & | | APPROVED BY ARCHITECT. | | 2). THERE IS NO TRUSS ANCHOR SCHEDULE IN | | EITHER THE STRUCTURAL OR ACCHETECTURAL | | PLANS. | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2001-01-25 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2001-01-25 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-25 00:00:00 | 01/24/01 TRUSS PLAN REVIEW: | | UNSAT- 1).ARCHETECT TO REVIEW AND | | APPROVE. | | 2). THERE IS NO ANCHOR SCHEDULE IN | | EITHER THE STRUCTURAL OR ARCHETURAL PLAN | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX. 8412 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2000-10-20 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-10-20 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO NEEDS SKYLIGHT TEST REPORT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2000-10-04 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-10-04 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | LETTER W/ APPLICATION |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-09-11 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-09-11 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | LETTER W/ APPLICATION |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-07-14 |
|
|
Cont ID |
|
Sent By |
hpiskura |
Date |
2000-07-14 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-10-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-10-04 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-10-04 |
Time |
11:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2000-09-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
21:23 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-09-12 |
Time |
21:23 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE: PLEASE ADDRESS FIRST SET OF NOTE | | -S. PLEASE SUBMIT COMPLETED LOAD CALCU- | | -LATIONS AND SHOW ALL CONTINUOUS LOADS | | AND LARGEST MOTOR AT 125%. | | 2)NOTE: PLEASE SEE 240-3-D FOR OCP | | OF CIRCUIT #13 OF PANEL "LB" . | | PLEASE CORRECT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-06-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-06-29 |
Time |
19:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-06-29 |
Time |
19:38 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | WITH ALL CONTINUOUS LOADS AT 125%. | | LIGHTING ETC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2000-10-17 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-10-17 |
Time |
14:27 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | APPROVED | | PLANS HAVE BEEN REVISED AND A HEALTH | | DEPARTMENET PERMIT WILL BE OBTAINED | | AND THROUGH CWPB PUBLIC UTILITIES DEPT. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2000-10-04 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-10-04 |
Time |
13:04 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | FAILED | | | | 1.DOUBLE DETECTOR CHECK VALVE NEEDS TO | | MOVE TO THE FRONT OF THE PROPERTY. JUST | | INSIDE OF PROPERTY LINE. | | | | 2. TWO COPIES OF THE PLANS SHOULD BE PRO | | VIDED TO MANNY GONZALEZ @ ENGINEERING SV | | 1000 45TH STREET SUITE 15 | | WPB FL 33407 | | (561) 659-8040 EXT. 2306 | | ONE FOR OUR UTILITY FILE AND ONE FOR | | THE CONSTRUCTION COORDINATOR WHO WILL | | SUPERVISE THE TAPPING. | | A MINIMUM OF 2 SETS OF SHOP DRAWINGS | | SHALL BE SUBMITTED TO THE SAME CONTACT | | FOR THE WORK PERFORMED OUT IN THE CITY | | ROW TO THE SAME CONTACT. | | | | A ROW PERMIT WILL HAVE TO BE ACQUIRED TO | | PERFORM THE TAPP OR ANY OTHER WORK IN TH | | E CITY ROW. | | | | YOUR DESIGNMEETS THE CRITERIA THAT | | REQUIRES A PALM BEACH COUNTY HEALTH DEPT | | PERMIT. (OVER 100 LINEAR FEET OF 6" PIPE | | | | MUST SHOW SANITARY SEWER MAIN AND PROVID | | E CLEARANCES AN 18" MINIMUM CLEARANCE | | IS REQUIRED BETWEEN WATER AND SEWER. | | | | A 12" MINIMUM CLEARANCE WILL BE REQUIRED | | BETWEEN WATERMAIN AND GAS MAIN. | | | | THESE COMMENTS MUST BE REVISED ON SHEET | | C-1 OF 7 AND ON FIRE SPRINKLER PLANS. | | | | IF ANY QUESTIONS OR COMMENTS FEEL FREE | | TO CONTACT ME AT 561 659 8040 EXT. 2306 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2000-10-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-10-20 |
Time |
13:04 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-10-20 |
Time |
13:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) RECEIVED LETTER FROM COLIN PRICE | | OF REG ARCHITECTS. THE LETTER INDICATED | | FLAME SPREAD RATINGS AND THE RELOCATION | | OF THE BACKFLOW AND FIRE DEPARTMENT | | CONNECTION DEVICE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2000-10-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-10-04 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-10-04 |
Time |
12:42 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) INTERIOR FINISHES ON PAGE A12.2 IS | | STILL INCORRECT. THE CORRECT DATA IS | | STILL MISSING AND THE INFORMATION | | PROVIDED DOES NOT CORRESPOND WITH | | NFPA 101, THE LIFE SAFETY CODE, 1985 | | EDITION. | | 2) FIRE DEPARTMENT CONNECTION IS TO BE | | LOCATED NEAR PINEWOOD AVENUE INSTEAD | | OF THE WEST SIDE OF THE BUILDING. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-09-06 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-09-06 |
Time |
15:08 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | WITH FIRE SPRINKLER DRAWINGS ON PAGE | | A8.1.THE FIRE SPRINKLER DRAWING DOES | | NOT INCLUDE LOCATION OF FIRE DEPARTMENT | | CONNECTION OR LOCATION OF FIRE HYDRANTS. | | 2) PLEASE PROVIDE COMPLETE FIRE ALARM | | SYSTEM DRAWINGS AND CUT SHEETS FOR FIRE | | ALARM EQUIPMENT SHOWN ON PLANS. A | | SEPARATE PLAN AND PERMIT ARE REQUIRED. | | 3) PLEASE CHECK THE INTERIOR FINISH | | SCHEDULE ON PAGE A12.2. SINCE THE | | BUILDING IS A MIXED OCCUPANCY, THE MOST | | STRINGENT FLAME SPREAD CRITERIA IS TO | | BE USED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-07-18 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-07-18 |
Time |
09:31 |
Rev Time |
1.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVIDE FIRE SPRINKLER DRAWINGS. | | FIRE ALARM SYSTEM SHALL BE CLASS "A" OR | | ADDRESSABLE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-07-12 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-07-12 |
Time |
14:49 |
Rev Time |
1.00 |
Received By |
ndenmark |
Date |
2000-07-12 |
Time |
14:49 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: | | OUTSIDE AIR QUANTITIES SHALL NOT BE REDU | | CED BELOW VALUES GIVEN CO SENSOR TO | | INCREASE ABOVE MINIMUM VALUES |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2000-10-03 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-10-03 |
Time |
19:01 |
Rev Time |
2.50 |
Received By |
tlarge |
Date |
2000-10-03 |
Time |
19:00 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************PROVISO****************** | | SUBMIT A SANITARY RISER THAT COMPLIES W/ | | THE STANDARD PLUMBING CODE PRIOR TO | | INSPECTION. | | A)WATER CLOSETS NOT PERMITTED ON WET | | VENTS.COUNTYWIDE AMENDMENTS TO SPC SEC. | | 911.1.1. | | | | B)CIRCUIT AND LOOP SYSTEM SHALL COMPLY | | W/SPC SEC.914.1,914.2,914.3.4,920.3,IF | | THAT IS THE INTENT OF THE DESIGN.I HAVE | | NO IDEA WHAT YOU ARE ATTEMPTING WITH THE | | SANITARY SYSTEM AS DRAWN. | | | | C)CLEARLY INDICATE ON THE PLAN WHERE | | SANITARY RISERS #5-8 CONNECT TO RISERS | | #1-4.COUNTYWIDE AMENDMENTS 104.2.1. | | | | D)CONDENSATE DRAIN SHALL BE EQUIPPED W/ | | AN EMERGENCY OVERFLOW. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2000-09-07 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-07 |
Time |
16:20 |
Rev Time |
1.50 |
Received By |
tlarge |
Date |
2000-09-07 |
Time |
12:03 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)THE WAIVER FOR THE GREASE TRAP SHALL | | BE SIGNED BY R.COMPO.COUNTYWIDE AMEND- | | MENTS TO SPC SEC.101.4.7. | | | | 2)THE LOCATION OF THE HANDICAP | | FACILITIES ON SHT.P2.1 DOESN'T CORRELATE | | W/THE ARCHITECTURAL PLANS.CLARIFY. | | | | 3)THE SANITARY RISER SHALL CORRELATE W/ | | THE CORRECT FLOOR PLAN.COUNTYWIDE | | AMENDMENTS TO SPC SEC.104.2.1. | | | | 4)WATER CLOSETS ARE NOT PERMITTED ON WET | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | SEC.911.1.1. | | | | 5)THE HABITABLE SQUARE FEET AND OCCUPANT | | SHALL BE ON THE PLANS.SPC SEC.407.1.3. | | | | 6)A DEP PERMIT IS REQD.FOR THE INSTALL- | | ATION OF THE WATER SYSTEMS.COUNTYWIDE | | AMENDMENTS TO SPC SEC.101.4.7. | | | | 7)AN EMERGENCY OVERFLOW IS REQD.ON THE | | CONDENSATE DRAIN TO THE DRYWELL. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-06-17 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-06-17 |
Time |
09:38 |
Rev Time |
2.75 |
Received By |
tlarge |
Date |
2000-06-17 |
Time |
09:38 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)SUBMIT OCCUPANT LOAD OF STRUCTURE | | BASED ON HABITABLE FLOOR SPACE PER TABLE | | 407 0F THE SPC.MINIMUM SANITARY REQS. | | SHALL BE BASED UPON THIS OCCUPANT LOAD. | | | | A HANDICAP STALL W/LAVATORY SHALL BE | | PROVIDED IN THE RESTROOMS PER FACBC | | SECS.4.17.3, 4.22.4. | | | | SHT.A9.1-DETAIL #7-H.C.URINAL SHALL BE | | MOUNTED MAX.17"PER FACBC SEC.4.18.2. | | | | MAX.TEMPERATURE OF WATER TO RESTROOMS | | SHALL BE 110 DEGREES PER F.E.C SEC. | | 412.1ABCD.2.3.2. | | | | DRINKING FOUNTAIN AT VOLLEYBALL COURT | | SHALL BE H.C. ACCESSIBLE AND ON AN | | ACCESSIBLE ROUTE PER FACBC SEC.4.3 | | | | SUBMIT COMPLETE STORM DRAINAGE ISOMETRIC | | FOR REVIEW.SHOW SLOPE OF PIPE,PIPE SIZES | | AND PROVISIONS FOR SECONDARY(EMERGENCY) | | DRAINAGE.COMPLY W/SPC SEC.1108.1, 1108.2 | | 1109.1,1109.3 AND APPENDIX "A". | | | | A GREASE TRAP IS REQUIRED ON THE | | SANITARY SYSTEM PER SPC SEC.1004.4. | | CONTACT R.COMPO AT CITY OF W.P.B. | | (561)835-7423.SUBMIT APPROVAL FORM FROM | | UTILITIES FOR GREASE TRAP. SUBMIT DETAIL | | OF GREASE TRAP. | | | | SHT.P3.1-WATER CLOSETS NOT PERMITTED ON | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | SPC SEC.911.1.1 | | | | CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/ | | SPC SEC.914.1. | | | | EMERGENCY OVERFLOW IS REQD.ON THE COND. | | DRAIN TO DRYWELL.SPC 701.4, | | | | SUBMIT WATER ISOMETRIC FOR ALL AREAS OF | | NEW WORK.COUNTYWIDE AMENDMENTS TO SPC | | SEC.104.2.1. | | | | A DEP PERMIT IS REQD.FOR THE INSTALL- | | ATION OF THE WATER SYSTEMS.COUNTYWIDE | | AMENDMENTS TO SPC SEC.101.4.7. | | | | CLEARLY SHOW LENGTH AND WIDTH OF TOILET | | ROOMS AND STALLS.COMPLY W/FACBC SECS. | | 4.17.3.,4.16.2. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-06-06 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-06-06 |
Time |
10:22 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|