Plan Review Details - Permit 00051707
Plan Review Stops For Permit 00051707
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By mcarsill Date 2000-05-30 Time 13:44 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) FIRE ALARM SYSTEM TO BE AUDIBLE
 THROUGHOUT THE BUILDING WHEN ACTIVATED.
 2) SMOKE DETECTORS TO BE A MINIMUM OF
 THREE FEET FROM AC DIFFUSERS.
 3) FIRE ALARM SYSTEM TO BE CLASS A OR
 ADDRESSABLE.
 4) FIRE ALARM SYSTEM TO BE MONITORED BY
 A LICENSED UL LISTED CENTRAL STATION.
 5) SYSTEM SUBJECT TO COMPLETE INSPECTION
 AFTER INSTALLATION.