Plan Review Stops For Permit 00051707 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-05-30 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-05-30 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM TO BE AUDIBLE | | THROUGHOUT THE BUILDING WHEN ACTIVATED. | | 2) SMOKE DETECTORS TO BE A MINIMUM OF | | THREE FEET FROM AC DIFFUSERS. | | 3) FIRE ALARM SYSTEM TO BE CLASS A OR | | ADDRESSABLE. | | 4) FIRE ALARM SYSTEM TO BE MONITORED BY | | A LICENSED UL LISTED CENTRAL STATION. | | 5) SYSTEM SUBJECT TO COMPLETE INSPECTION | | AFTER INSTALLATION. |
|
|
|