Plan Review Details - Permit 00051692
Plan Review Stops For Permit 00051692
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-09 Cont ID  
Sent By lmartine Date 2000-06-09 Time 16:25 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-06-01 Cont ID  
Sent By dpalmer Date 2000-06-01 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2000-06-01 Time 19:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-03 Cont ID  
Sent By cthirben Date 2000-06-03 Time 08:28 Rev Time 1.00
Received By lmartine Date 2000-06-03 Time 08:28 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 EXHAUST FAN VENTILATION AS PER SMC 1997
 503.3.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-07-13 Cont ID  
Sent By tlarge Date 2000-07-13 Time 10:42 Rev Time 0.50
Received By tlarge Date 2000-07-13 Time 10:42 Sent To  
Notes
2001-01-08 00:00:00ADD AIRVAC DISPOSAL SYSTEM

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-07-13 Cont ID  
Sent By tlarge Date 2000-07-13 Time 09:27 Rev Time 0.30
Received By tlarge Date 2000-07-13 Time 09:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-20 Cont ID  
Sent By tlarge Date 2000-06-20 Time 11:05 Rev Time 1.00
Received By tlarge Date 2000-06-20 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-03 Cont ID  
Sent By tlarge Date 2000-06-03 Time 05:18 Rev Time 1.00
Received By tlarge Date 2000-06-03 Time 05:18 Sent To  
Notes
2001-01-08 00:00:00DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 SHOW REQUIRED WHEELCHAIR TURNING SPACE
 IN TOILET ROOMS PER FACBC SEC.4.2.3.
  
 SUBMIT DETAILS FOR INSTALLATION OF
 HANDICAP FIXTURES AND APPURTENANCES.
 (LENGTH AND HEIGHT OF GRAB BARS,FIXTURE
 CLEARANCES,CLEAR FLOOR SPACE UNDER
 FIXTURES,MOUNTING HEIGHTS OF ALL ITEMS.
 COMPLY W/FACBC,OCTOBER 1997 EDITION.
  
 MINIMUM SIZE SANITARY LINE BELOW GROUND
 SHALL BE 2"PER SPC SEC.714.4.
  
 VENT SIZES FOR LAVS SHALL COMPLY W/SPC
 TABLE 920.2.
  
 FAUCETS IN TOILET ROOMS SHALL COMPLY W/
 FACBC SECS.4.19.5,4.27.4.
  
 WATER SERVICE SHALL BE EQUIPPED W/BACK-
 FLOW PREVENTION DEVICE PER SPC SEC.601.6