Plan Review Stops For Permit 00051297 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-06-06 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-05-31 |
Time |
15:17 |
Rev Time |
3.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1. ENGINEER TO PROVIDE LETTER INDICATING | | 1/4" ROOF SLOPE AS PER CODE. OK 6/6/00 | | 2. ROOFING SYSTEM SHALL MEET THE | | REQUIREMENTS OF APPENDIX F FOR FIRST | | FIRE DISTRICT.OK 6/6/00 | | 3. FLORIDA ENERGY SHEETS REQUIRED.OK 6/6 | | 4. SHEET S-3 MEZZANINE DESIGNED FOR | | 50PSF. PLANS SHOW THAT THE AREA IS TO BE | | USED FOR PUBLIC SEATING THUS 100PSF | | REQUIRED SEE TABLE 1604.1, 1997 SBC.OK6/ | | 5. SHEET A-1 WINDOWS AND DOORS SUBMIT | | INFORMATION CERTIFYING CODE COMPLIANCE | | TO 1997 SBC, SECTION 1006.2.4, 3/4 HOUR | | FIRE RATING.OK 6/6/00 | | 6. ALL EXTER GLAZING, SUBMIT PRODUCT | | APPROVAL INFORMATION FOR LARGE MISSLE | | IMPACT. SBCCI OR DADE COUNTY.OK 6/6/00 | | 7. SIGNS AND AWNINGS REQUIRE SEPERATE | | PERMITS. | | 8. NO INTERIOR WORK IS COVERED BY THIS | | PERMIT. | | | | INFORMATION CONTACT JOHN STANDBERG AT | | 561-988-4002. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2001-02-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2001-02-13 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2001-02-13 |
Time |
09:05 |
Sent To |
|
|
Notes |
2001-02-13 00:00:00 | REV FOR ELEV EQUIPMENT ONLY |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-05-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-05-24 |
Time |
21:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-05-24 |
Time |
21:37 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****NOTES ON PLANS FOR COLOR CODING OF | | FEEDERS. TO MEET LOCAL CODE 215 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-05-30 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-05-30 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
bstaples |
Date |
2000-05-30 |
Time |
14:55 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) ADDRESS NOT SHOWN ON ELEVATION VIEWS | | 2) NO LIFE SAFETY PLAN SHOWN ON DRAWINGS | | 3) BUILDING TO COMPLY WITH MERCANTILE | | OCCUPANCIES, 1985 EDITION OF THE LIFE | | SAFETY CODE | | 4) PROVIDE COMPLETE SHOP DRAWINGS FOR | | THE FIRE SPRINKLER SYSTEM. CUT SHEETS | | NEEDED ON FIRE SPRINKLER HEADS AND | | DEVICES PLANNED.ADDITIONAL PERMIT NEEDED | | FOR FIRE SPRINKLER SYSTEM. | | 5) AUTOMATIC DOORS TO COMPLY WITH NFPA | | 101, 1985 EDITION. | | 6) ALL STAIRS TO COMPLY WITH NFPA 101, | | 1985 EDITION FOR NEW STAIRS. | | 7) PROVIDE SHOP DRAWINGS ON FIRE ALARM | | SYSTEM PLANNED FOR USE. CUT SHEETS ON | | DEVICES TO BE USED ARE NEEDED. | | 8) EXIT SIGNS AND EMERGENCY LIGHTS NOT | | SHOWN. | | 9) INTERIOR FINISH TO BE CLASS A OR B. | | 10) KNOX-BOX NEEDED, | | 11) PROVIDE MORE DETAILS ON AWNINGS | | 12) PORTABLE FIRE EXTINGUISHERS REQUIRED | | 13) PROVIDE FLOOR PLAN DETAILS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2000-05-30 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-05-30 |
Time |
14:15 |
Rev Time |
0.50 |
Received By |
ndenmark |
Date |
2000-05-30 |
Time |
14:15 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO: | | SHELL ONLY NO MECH, INCLUDING NO RTU'S | | NO INFO ON CURBS OR CONDENSATE DRAIN | | PROVIDE DETAILS WITH BUILDOUT PERMIT |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
P |
Date |
2000-09-27 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-27 |
Time |
18:23 |
Rev Time |
0.65 |
Received By |
tlarge |
Date |
2000-09-27 |
Time |
18:23 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *****************PROVISO**************** | | 1)GREASE TRAP DESIGN SHALL COMPLY W/CITY | | OF WPB CONSTRUCTION SERVICES DEPT.SEE | | ATTACHED. | | | | 2)VENT FOR GREASE TRAP CANNOT BE | | INSTALLED AS SHOWN.COMPLY W/SPC SEC. | | 906.2.2. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY COMMENTS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2000-09-09 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-09-09 |
Time |
06:15 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-09-09 |
Time |
06:15 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)TWO WAY CLEANOUTS SHALL BE INSTALLED | | ON THE INLET AND OUTLET OF THE GREASE | | INTERCEPTOR.(SEE ATTACHED DETAIL) | | | | 2)SHT.ENG.-3-THE CLEANOUT ON THE OUTLET | | SIDE OF THE GREASE TRAP SHALL BE LOCATED | | IN THE DISCHARGE LINE.AS DESIGNED THERE | | IS A SECTION OF PIPE FROM THE TRAP THAT | | CANNOT BE RODDED.SPC SEC.710.4. | | | | 3)TWO WAY CLEANOUTS ARE REQD.IN THE | | INLET AND OUTLET.SEE DIAGRAM. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2000-06-28 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-06-28 |
Time |
19:32 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-06-28 |
Time |
19:22 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | MAX.OF 5350 SQ.FT.IS PERMITTED TO DRAIN | | INTO 6" PIPE AT 1/8" PER FT.SLOPE.SEE | | SPC TABLE 1108.2.REVISE PIPE SIZE FOR | | RW. | | | | SHT.P1.01-NOTE #3-TESTING OF WATER | | SUPPLY SYSTEM SHALL COMPLY W/SPC SEC. | | 311.3. | | | | DESIGN OF OVERFLOW DRAINAGE SYSTEM SHALL | | COMPLY W/SPC SEC.1109.1-1109.3 AND | | APPENDIX "A" OF SPC. | | | | I CAN BE REACHED AT 561-659-8096,EXT. | | 8377 IF YOU HAVE ANY QUESTIONS. | | TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-05-26 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-05-26 |
Time |
08:48 |
Rev Time |
0.30 |
Received By |
tlarge |
Date |
2000-05-26 |
Time |
08:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-05-25 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-05-25 |
Time |
19:01 |
Rev Time |
0.65 |
Received By |
tlarge |
Date |
2000-05-25 |
Time |
19:01 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SIZING OF ROOF DRAINAGE SYSTEM SHALL | | COMPLY W/TABLE 1108.2 OF SPC. | | INDICATE SLOPE OF STORM LINES.PRESENT | | DESIGN DOESN'T COMPLY W/TABLE 1108.2. |
|
|