Plan Review Details - Permit 00051297
Plan Review Stops For Permit 00051297
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By bstaples Date 2000-05-31 Time 15:17 Rev Time 3.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. ENGINEER TO PROVIDE LETTER INDICATING
 1/4" ROOF SLOPE AS PER CODE. OK 6/6/00
 2. ROOFING SYSTEM SHALL MEET THE
 REQUIREMENTS OF APPENDIX F FOR FIRST
 FIRE DISTRICT.OK 6/6/00
 3. FLORIDA ENERGY SHEETS REQUIRED.OK 6/6
 4. SHEET S-3 MEZZANINE DESIGNED FOR
 50PSF. PLANS SHOW THAT THE AREA IS TO BE
 USED FOR PUBLIC SEATING THUS 100PSF
 REQUIRED SEE TABLE 1604.1, 1997 SBC.OK6/
 5. SHEET A-1 WINDOWS AND DOORS SUBMIT
 INFORMATION CERTIFYING CODE COMPLIANCE
 TO 1997 SBC, SECTION 1006.2.4, 3/4 HOUR
 FIRE RATING.OK 6/6/00
 6. ALL EXTER GLAZING, SUBMIT PRODUCT
 APPROVAL INFORMATION FOR LARGE MISSLE
 IMPACT. SBCCI OR DADE COUNTY.OK 6/6/00
 7. SIGNS AND AWNINGS REQUIRE SEPERATE
 PERMITS.
 8. NO INTERIOR WORK IS COVERED BY THIS
 PERMIT.
  
 INFORMATION CONTACT JOHN STANDBERG AT
 561-988-4002.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2001-02-13 Cont ID  
Sent By dpalmer Date 2001-02-13 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2001-02-13 Time 09:05 Sent To  
Notes
2001-02-13 00:00:00REV FOR ELEV EQUIPMENT ONLY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-24 Cont ID  
Sent By dpalmer Date 2000-05-24 Time 21:37 Rev Time 0.00
Received By dpalmer Date 2000-05-24 Time 21:37 Sent To  
Notes
2001-01-08 00:00:00****NOTES ON PLANS FOR COLOR CODING OF
 FEEDERS. TO MEET LOCAL CODE 215

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-05-30 Cont ID  
Sent By bstaples Date 2000-05-30 Time 14:53 Rev Time 0.00
Received By bstaples Date 2000-05-30 Time 14:55 Sent To  
Notes
2001-01-08 00:00:001) ADDRESS NOT SHOWN ON ELEVATION VIEWS
 2) NO LIFE SAFETY PLAN SHOWN ON DRAWINGS
 3) BUILDING TO COMPLY WITH MERCANTILE
 OCCUPANCIES, 1985 EDITION OF THE LIFE
 SAFETY CODE
 4) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE FIRE SPRINKLER SYSTEM. CUT SHEETS
 NEEDED ON FIRE SPRINKLER HEADS AND
 DEVICES PLANNED.ADDITIONAL PERMIT NEEDED
 FOR FIRE SPRINKLER SYSTEM.
 5) AUTOMATIC DOORS TO COMPLY WITH NFPA
 101, 1985 EDITION.
 6) ALL STAIRS TO COMPLY WITH NFPA 101,
 1985 EDITION FOR NEW STAIRS.
 7) PROVIDE SHOP DRAWINGS ON FIRE ALARM
 SYSTEM PLANNED FOR USE. CUT SHEETS ON
 DEVICES TO BE USED ARE NEEDED.
 8) EXIT SIGNS AND EMERGENCY LIGHTS NOT
 SHOWN.
 9) INTERIOR FINISH TO BE CLASS A OR B.
 10) KNOX-BOX NEEDED,
 11) PROVIDE MORE DETAILS ON AWNINGS
 12) PORTABLE FIRE EXTINGUISHERS REQUIRED
 13) PROVIDE FLOOR PLAN DETAILS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-05-30 Cont ID  
Sent By ndenmark Date 2000-05-30 Time 14:15 Rev Time 0.50
Received By ndenmark Date 2000-05-30 Time 14:15 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 SHELL ONLY NO MECH, INCLUDING NO RTU'S
 NO INFO ON CURBS OR CONDENSATE DRAIN
 PROVIDE DETAILS WITH BUILDOUT PERMIT

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-09-27 Cont ID  
Sent By tlarge Date 2000-09-27 Time 18:23 Rev Time 0.65
Received By tlarge Date 2000-09-27 Time 18:23 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 1)GREASE TRAP DESIGN SHALL COMPLY W/CITY
 OF WPB CONSTRUCTION SERVICES DEPT.SEE
 ATTACHED.
  
 2)VENT FOR GREASE TRAP CANNOT BE
 INSTALLED AS SHOWN.COMPLY W/SPC SEC.
 906.2.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY COMMENTS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-09-09 Cont ID  
Sent By tlarge Date 2000-09-09 Time 06:15 Rev Time 0.50
Received By tlarge Date 2000-09-09 Time 06:15 Sent To  
Notes
2001-01-08 00:00:001)TWO WAY CLEANOUTS SHALL BE INSTALLED
 ON THE INLET AND OUTLET OF THE GREASE
 INTERCEPTOR.(SEE ATTACHED DETAIL)
  
 2)SHT.ENG.-3-THE CLEANOUT ON THE OUTLET
 SIDE OF THE GREASE TRAP SHALL BE LOCATED
 IN THE DISCHARGE LINE.AS DESIGNED THERE
 IS A SECTION OF PIPE FROM THE TRAP THAT
 CANNOT BE RODDED.SPC SEC.710.4.
  
 3)TWO WAY CLEANOUTS ARE REQD.IN THE
 INLET AND OUTLET.SEE DIAGRAM.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-06-28 Cont ID  
Sent By tlarge Date 2000-06-28 Time 19:32 Rev Time 0.50
Received By tlarge Date 2000-06-28 Time 19:22 Sent To  
Notes
2001-01-08 00:00:00MAX.OF 5350 SQ.FT.IS PERMITTED TO DRAIN
 INTO 6" PIPE AT 1/8" PER FT.SLOPE.SEE
 SPC TABLE 1108.2.REVISE PIPE SIZE FOR
 RW.
  
 SHT.P1.01-NOTE #3-TESTING OF WATER
 SUPPLY SYSTEM SHALL COMPLY W/SPC SEC.
 311.3.
  
 DESIGN OF OVERFLOW DRAINAGE SYSTEM SHALL
 COMPLY W/SPC SEC.1109.1-1109.3 AND
 APPENDIX "A" OF SPC.
  
 I CAN BE REACHED AT 561-659-8096,EXT.
 8377 IF YOU HAVE ANY QUESTIONS.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-26 Cont ID  
Sent By tlarge Date 2000-05-26 Time 08:48 Rev Time 0.30
Received By tlarge Date 2000-05-26 Time 08:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-05-25 Cont ID  
Sent By tlarge Date 2000-05-25 Time 19:01 Rev Time 0.65
Received By tlarge Date 2000-05-25 Time 19:01 Sent To  
Notes
2001-01-08 00:00:00SIZING OF ROOF DRAINAGE SYSTEM SHALL
 COMPLY W/TABLE 1108.2 OF SPC.
 INDICATE SLOPE OF STORM LINES.PRESENT
 DESIGN DOESN'T COMPLY W/TABLE 1108.2.