Plan Review Stops For Permit 00051132 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2000-07-21 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-07-21 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | OK PER B.STAPLES |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-06-26 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-06-26 |
Time |
10:43 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | REVISION 6/26/00 | | 1. SIGNATURE OF DESIGNER OF RECORD IS | | NOT ORIGIONAL. | | 2. INFORMATION REQUESTED ON FIRST REVIEW | | 5/18 NOT SUBMITTED AS PER CORRESPONDENCE | | RECEIVED WITH REVISIONS. | | 3. LETTER FROM CITYPLACE SPECIAL | | INSPECTOR RELEASING SPACE. SEE FAX. | | COVER PAGE DATED 5/23/00. | | 4. FIRE SPRINKLER CONTRACTOR TO SECURE | | PERMIT PRIOR TO ISSUANCE OF BUILDING | | PERMIT. | | | | ITEMS REFERENCED IN #2 ARE, | | 1. FLORIDA ENERGY SHEETS, 1997 EDITION. | | 2. PRODUCT INFORMATION ON STORE FRONT | | MEET INPACT PROTECTION STANDARDS AND | | WIND LOADS. SBC 1997 CHAPTER 16 AND | | SSTD12-97. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-05-18 |
|
|
Cont ID |
|
Sent By |
bstaples |
Date |
2000-05-18 |
Time |
15:28 |
Rev Time |
1.00 |
Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1 NEEDS FLORIDA ENERGY SHEETS | | 2 NEEDS PRODUCT APPROVAL INFORMATION FOR | | IMPACT RESISTANT GLAZING SYSTEM. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-07-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-07-05 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-07-05 |
Time |
17:09 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | STILL NEEDS ORIG SIGNATURE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2000-06-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-06-27 |
Time |
21:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-06-27 |
Time |
21:42 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: AS REQUESTED ON FIRST SET OF | | NOTES. PLEASE SUBMIT AIC RATINGS OF | | MAINS AND PANELS. THIS IS REQ`D BEFORE | | PLANS ARE ISSUED FOR PERMIT. | | MAINS AND PANELS MUST BE RATED FOR THE | | AVAILABLE FAULT CURRENT. FAULT CURRENT | | CALCULATIONS MAY BE SUBMITTED INSTEAD | | OF RATINGS AND CONTRACTOR WILL BE | | RESPONSIBLE FOR INSTALLING EQUIPMENT | | RATED FOR AVAILABLE FAULT GIVEN BY | | CALCULATIONS.THIS REQ`D BY 110-9 AND | | 215-5 OF THE NEC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 561-659-8096 EXT 8372 | | | | DEWEY PALMER | | ELETRICAL PLAN REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-05-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-05-22 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-05-22 |
Time |
14:05 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE PROVIDE AIC RATINGS OF | | ANY EQUIPMENT BEING INSTALLED. MAINS | | MUST BE RATED FOR THE AVAILABLE FAULT | | CURRENT. 110-9/215-5 | | | | 2)NOTE:PLEASE NOTE THE OUTLETS REQ`D FOR | | SHOW WINDOWS AS PER 210-62 | | | | 3)NOTE:PLEASE NOTE AS PER PALM BEACH | | COUNTY/CITY OF WEST PALM BEACH LOCAL | | AMENDMENTS. OUTLET SPACINGTO MEET | | 210-50. EVERY 20` OF UNENCUMBERED WALL | | SPACE REGARDLESS OF WALL FIXTURES AND/OR | | OTHER WALL MODIFICATIONS. | | | | | | PLEASE MAKE THE ABOVECHANGES AND | | SUBMIT FOR REVIEW. IF THERE ARE ANY | | QUESTIONS PLEASE CALL 659-8096 EXT 8372 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-05-23 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-05-23 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
ndenmark |
Date |
2000-05-23 |
Time |
09:14 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NO FIRE SPRINKLER PROTECTION SHOWN. | | WHERE DOES THE REAR EXIT TERMINATE | | HORN STROBES NEEDED IN TENANT SPACE | | INTERIOR FINISH CLASS A OR B | | PLAN REVIEWED BY LT. CARSILLO |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-05-19 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-05-19 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-08-08 |
Time |
12:53 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ******************PROVISO*************** | | A/C UNIT TO COMPLY WITH SMC 97 SEC.406.1 | | FAN SHUTDOWN CONTROL. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-06-28 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-06-28 |
Time |
19:17 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-06-28 |
Time |
19:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-05-18 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-05-18 |
Time |
20:26 |
Rev Time |
0.50 |
Received By |
tlarge |
Date |
2000-05-18 |
Time |
20:26 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY | | W/FACBC SEC.4.1.3.(10)(A).PROVISIONS | | SHALL BE MADE FOR PEOPLE WHO HAVE | | TROUBLE BENDING OR STOOPING. | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | PER SPC SEC.501.7.SUPPLY FIXED LADDER | | FOR ACCESSIBILITY OR RELOCATE EWH TO | | FLOOR. | | | | TOILET PAPER DISPENSER SHALL BE A MIN.OF | | 19" TO CENTER PER FACBC SEC.4.16.6 | | | | A CLEAR FLOOR SPACE OF 30"WIDE X 48"DEEP | | SHALL BE PROVIDED AT DRINKING FOUNTAIN | | TO ALLOW A FORWARD APPROACH PER FACBC | | SEC.4.15.5. | | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | SECS.4.15.2.,4.15.3. |
|
|