Plan Review Details - Permit 00050266
Plan Review Stops For Permit 00050266 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-06-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-06-09 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-06-09 |
Time |
09:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-05-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-05-31 |
Time |
20:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-05-31 |
Time |
20:00 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SUBMIT THE AIC RATING OF | | EQUIPMENT MAIN. MAINS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT.110-9/215-5 | | THIS IS REQ`D ON ALL PLANS. | | | | 2)NOTE: PLEASE INCLUDE THE COLD WATER | | PIPE AND BLDG.STEEL AS PART OF THE | | GROUNDING ELETRODE SYSTEM,AS PER 250-50 | | | | 3)NOTE: PLEASE INDICATE THE PANEL AS \\ | | BEING MAIN BRKR 215-5 | | | | 4)NOTE: PLEASE SHOW THE REQ`D DEDICATED | | BATH(S) CIRCUIT(S) PER 210-11-C-3 | | | | 5)NOTE: PLEASE SEE THE MISSING OUTLET | | REQ`D FOR TWO FEET OF WALL 210-52. | | | | 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS | | ARE REQ`DOUTSIDE ALL SLEEPING ROOMS | | IN NEW DWELLINGS. NFPA-72 2-2.1.1.1 | | | | 7)NOTE:PLEASE COMPLETE LOAD CALCULATION. | | | | 8)NOTE:PLEASE SEE PANEL SCHEDULE.YOU | | SHOW 4500VAON 20AMPTHIS MUST BE | | RATED AT 125% OF MIN CIRCUIT AMPACITY, | | | | | | 9)NOTE: PLEASE SHOW THE SWITCH LOCATION | | FOR EGRESS LIGHTING IN GARAGE. | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2000-09-06 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-09-06 |
Time |
17:32 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2000-09-06 |
Time |
17:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2000-06-14 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-06-14 |
Time |
15:33 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-06-14 |
Time |
15:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2000-06-12 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-06-12 |
Time |
10:19 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-06-12 |
Time |
10:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2000-06-09 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-06-07 |
Time |
09:59 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-06-07 |
Time |
09:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2000-05-18 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-05-18 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
cthirben |
Date |
2000-06-09 |
Time |
11:55 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ****************DENIED****************** | | 1. DRYER VENT TO BE SHOWN ON PLANS. | | 2. RETURN AIR TO BE INDICATED. | | 3. EXHAUST FANS TO BE SHOWN AND INSTALL | | IN BATHROOMS. | | 4. PLANS SHOW A TOTAL OF 1738 CFM'S | | A/C SUPPLY OF 1400 CFM'S | | A/C UNIT TOO SMALL FOR THE DEMAND. | | 5. ENERGY CALCULATIONS REQUIRED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-05-16 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-05-16 |
Time |
06:10 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-05-16 |
Time |
06:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
P |
Date |
2000-06-14 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-06-14 |
Time |
16:58 |
Rev Time |
4.00 |
Received By |
fknapp |
Date |
2000-06-14 |
Time |
13:55 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | *****************PROVISO**************** | | | | SBC 104.2.2 | | | | 1)PROVIDE 2 CURRENT COMPLETE COPIES OF | | SBCCI OR METRO DADE PRODUCT APPROVALS | | FOR: | | WINDOWS | | MULLIONS | | | | 2)PROVIDE INSTALLATION SCHEDULE AND KEY | | PLAN FOR STORM PANELS WITH SPECIFIC | | ANCHORS TO BE USED. | | | | 3)PROVIDE ROOF SHEATHING NAILING ZONES | | COMPLYING WITH CITY AMENDMENTS | | FIG. 2306.1 | | | | 4)PROVIDE SAFETY GLASS AS REQUIRED PER | | 1997 SBC 2405.2.1 | | | | PLEASE SUBMIT PRIOR TO INSTALLATION |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-05-08 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-05-08 |
Time |
10:15 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|