Plan Review Details - Permit 00050266
Plan Review Stops For Permit 00050266
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-09 Cont ID  
Sent By dpalmer Date 2000-06-09 Time 09:33 Rev Time 0.00
Received By dpalmer Date 2000-06-09 Time 09:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-31 Cont ID  
Sent By dpalmer Date 2000-05-31 Time 20:02 Rev Time 0.00
Received By dpalmer Date 2000-05-31 Time 20:00 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAIN. MAINS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT.110-9/215-5
 THIS IS REQ`D ON ALL PLANS.
  
 2)NOTE: PLEASE INCLUDE THE COLD WATER
 PIPE AND BLDG.STEEL AS PART OF THE
 GROUNDING ELETRODE SYSTEM,AS PER 250-50
  
 3)NOTE: PLEASE INDICATE THE PANEL AS \\
 BEING MAIN BRKR 215-5
  
 4)NOTE: PLEASE SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3
  
 5)NOTE: PLEASE SEE THE MISSING OUTLET
 REQ`D FOR TWO FEET OF WALL 210-52.
  
 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`DOUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS. NFPA-72 2-2.1.1.1
  
 7)NOTE:PLEASE COMPLETE LOAD CALCULATION.
  
 8)NOTE:PLEASE SEE PANEL SCHEDULE.YOU
 SHOW 4500VAON 20AMPTHIS MUST BE
 RATED AT 125% OF MIN CIRCUIT AMPACITY,
  
  
 9)NOTE: PLEASE SHOW THE SWITCH LOCATION
 FOR EGRESS LIGHTING IN GARAGE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-09-06 Cont ID  
Sent By jleech Date 2000-09-06 Time 17:32 Rev Time 0.33
Received By jleech Date 2000-09-06 Time 17:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2000-06-14 Cont ID  
Sent By cthirben Date 2000-06-14 Time 15:33 Rev Time 1.00
Received By cthirben Date 2000-06-14 Time 15:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-06-12 Cont ID  
Sent By cthirben Date 2000-06-12 Time 10:19 Rev Time 1.00
Received By cthirben Date 2000-06-12 Time 10:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-06-09 Cont ID  
Sent By cthirben Date 2000-06-07 Time 09:59 Rev Time 1.00
Received By cthirben Date 2000-06-07 Time 09:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-05-18 Cont ID  
Sent By cthirben Date 2000-05-18 Time 10:44 Rev Time 0.00
Received By cthirben Date 2000-06-09 Time 11:55 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1. DRYER VENT TO BE SHOWN ON PLANS.
 2. RETURN AIR TO BE INDICATED.
 3. EXHAUST FANS TO BE SHOWN AND INSTALL
 IN BATHROOMS.
 4. PLANS SHOW A TOTAL OF 1738 CFM'S
 A/C SUPPLY OF 1400 CFM'S
 A/C UNIT TOO SMALL FOR THE DEMAND.
 5. ENERGY CALCULATIONS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-05-16 Cont ID  
Sent By tlarge Date 2000-05-16 Time 06:10 Rev Time 0.33
Received By tlarge Date 2000-05-16 Time 06:10 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-06-14 Cont ID  
Sent By fknapp Date 2000-06-14 Time 16:58 Rev Time 4.00
Received By fknapp Date 2000-06-14 Time 13:55 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************PROVISO****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 WINDOWS
 MULLIONS
  
 2)PROVIDE INSTALLATION SCHEDULE AND KEY
 PLAN FOR STORM PANELS WITH SPECIFIC
 ANCHORS TO BE USED.
  
 3)PROVIDE ROOF SHEATHING NAILING ZONES
 COMPLYING WITH CITY AMENDMENTS
 FIG. 2306.1
  
 4)PROVIDE SAFETY GLASS AS REQUIRED PER
 1997 SBC 2405.2.1
  
 PLEASE SUBMIT PRIOR TO INSTALLATION

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-08 Cont ID  
Sent By gjoyce Date 2000-05-08 Time 10:15 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***