Plan Review Details - Permit 00050015
Plan Review Stops For Permit 00050015 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2000-08-31 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2000-08-31 |
Time |
17:38 |
Rev Time |
9.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | COURTYARD MARRIOT | | | | CHANGE OF BUILDING DESIGN FROM METAL | | TO MASONRY. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-05-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2000-05-24 |
Time |
13:37 |
Rev Time |
1.30 |
Received By |
jleahy |
Date |
2000-05-24 |
Time |
13:34 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SEE NOTES FROM PLAN REVIEW 00030112JL |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2000-06-01 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2000-06-01 |
Time |
11:34 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DEAN HAS PROVIDED PROVISOS UNDER A | | DIFFERENT PERMIT NUMBER. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2000-06-01 |
|
|
Cont ID |
|
Sent By |
lsmith |
Date |
2000-06-01 |
Time |
11:28 |
Rev Time |
0.50 |
Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISOPER RT 5/31/00 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2000-05-23 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-05-23 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
lsmith |
Date |
2000-06-02 |
Time |
12:18 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED FOR MECHANICAL | | | | BASED ON PLAN REVIEW 00030112 THE FOLLOW | | ING ITEMS NEED TO BE REVISED ON THE MECH | | DRAWINGS: | | 1) PROVIDE INFORMATION ON BATH EXHAUST | | DUCT MATERIAL FOR CODE COMPLIANCE | | 2) OUTSIDE AIR CALCULATIONS LOCATED ON | | SKM-9 NEED TO BE PERMANTLY ATTACHED TO | | APPROVED DRAWINGS | | 3) AIR BALANCE SCHEDULE LOCATED ON SKM- | | 10 NEEDS TO BE PERMANENTLY ATTACHED TO | | APPROVED DRAWINGS | | 4) ALL FIRE DAMPER LOCATIONS TO BE SHOWN | | AND PROPERLY IDENTIFIED ON PLANS PER | | 1997 SMC 610.6 | | 5) FIRE DAMPERS REQUIRED AT ALL WALL | | PENETRATIONS OF 1 HOUR OR MORE PER 1997 | | SMC 610.1.2 SEE PRIOR LIST FOR SPECIFICS | | | | THE FOLLOWING ARE PROVISO ITEMS: | | 1) KITCHEN HOOD AND EXHAUST DUCT WILL | | REQUIRE SEPARATE MECHANICAL PERMIT | | 2) SEPARATE PERMITS REQUIRED FOR HOOD, | | SUPPRESSION, WALK IN COOLER/FREEZER,ETC. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-08-17 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-17 |
Time |
14:25 |
Rev Time |
3.50 |
Received By |
tlarge |
Date |
2000-08-17 |
Time |
14:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************PROVISO****************** | | PLUMBING APPROVED FOR UNDERGROUND SYSTEM | | ONLY.NO ABOVE THE SLAB WORK PERMITTED | | UNTIL REVISED PLUMBING DRAWINGS | | SUBMITTED AND APPROVED. | | | | DOES NOT INCLUDE PLBG.FOR POOL HOUSE.. | | 8/17/00. | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-05-03 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-05-03 |
Time |
10:03 |
Rev Time |
0.50 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|