Plan Review Details - Permit 00041354
Plan Review Stops For Permit 00041354
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-18 Cont ID  
Sent By dpalmer Date 2000-07-18 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2000-07-18 Time 11:36 Sent To  
Notes
2001-01-08 00:00:00STILL MISSING SMOKE DETECTORS.
 NFPA-72 2-2.1.1.1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-05-23 Cont ID  
Sent By dpalmer Date 2000-05-23 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2000-05-23 Time 08:59 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT THE AIC RATING
 OF EQUIPMENT MAINS AND PANELS.215-5
 MAINS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT AS PER 110-9
  
 2)NOTE: NEED TO HAVE THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) TO BE 20 AMP AND #12
 AWG. AS PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS CALL
 659-8096 EXT 8372
  
  
 ***************NOTE*********************
  
 SHEET A-4(ELEC) MAY BE CHANGED OUT
 BY ARCH ENT. BEFORE BLDG.DOES THEIR PLAN
 REVIEW. THIS WAY MAYBE THE PLANS WON`T
 HAVE TO COME BACK JUST FOR ELEC. COMMENT
 -S.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-05-02 Cont ID  
Sent By cthirben Date 2000-05-02 Time 13:59 Rev Time 1.00
Received By cthirben Date 2000-05-02 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-07-02 Cont ID  
Sent By kstevens Date 2001-07-02 Time 09:41 Rev Time 0.25
Received By kstevens Date 2001-07-02 Time 09:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-05-02 Cont ID  
Sent By tlarge Date 2000-05-02 Time 06:42 Rev Time 0.50
Received By tlarge Date 2000-05-02 Time 06:42 Sent To  
Notes
2001-01-08 00:00:00PROVISO:REQS.FOR COMBUSTION AIR SHALL
 COMPLY W/SGC SEC.402.4.4.3.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date   Cont ID  
Sent By fknapp Date 2000-07-26 Time 12:30 Rev Time 1.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER J CALAGERO

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-06-13 Cont ID  
Sent By jcaloger Date 2000-06-13 Time 17:07 Rev Time 1.50
Received By jcaloger Date   Time   Sent To  
Notes
2001-01-08 00:00:00DESIGN COMPLIANCE FORM SPECIFYS
 INCORRECT BUILDING CODE
  
 SPECIFY THE SPECIES OF LUMBER REQUIRED
 TO CONSTRUCT THE WOOD FRAMED BEARING
 WALLS
  
 NEEDS COUNTY IMPACT FEES PAID
  
 SEE ELECTRIC REVIEW COMMENTS

Review Stop Z ZONING
Rev No 1 Status P Date 2000-05-01 Cont ID  
Sent By gjoyce Date 2000-05-01 Time 09:40 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***