Plan Review Details - Permit 00040942
Plan Review Stops For Permit 00040942
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-06-19 Cont ID  
Sent By bstaples Date 2000-04-25 Time 12:53 Rev Time 2.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00FAIR HOUSING ACT: THE PLANS AS SUBMITTED
 DO NOT INDICATE COMPLIANCE WITH THE
 1996 EDITION AS AMENDED IN 1998 SEE
 SHEET DPT A7.05 AND 7.06.
 REFERENCE IS TO 1991 FAIR HOUSING ACT.
 REVISE PLANS AND NOTES TO MEET PROPER
 EDITION OF FAIR HOUSING ACT.
  
 FLORIDA ENERGY SHEETS
  
 THRESHOLD INSPECTOR LETTER RELEASING
 THE BUILDING FOR BUILD OUTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-04-24 Cont ID  
Sent By dpalmer Date 2000-04-24 Time 07:37 Rev Time 0.00
Received By dpalmer Date 2000-04-24 Time 07:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-25 Cont ID  
Sent By bstaples Date 2000-04-25 Time 07:38 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PROVISO ATTACHED TO PLANS
 M. CARSILLO FIRE DEPT. 4/21/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-24 Cont ID  
Sent By ndenmark Date 2000-04-24 Time 08:37 Rev Time 2.00
Received By ndenmark Date 2000-04-24 Time 08:37 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
 1) AC-7 AND AC-6 UNITS SERVING CORRIDORS
 TO HAVE FAN SHUT DOWN BY DUCT SMOKE
 DETECTORS PER 1997 SMC 406.2RECIRCULA-
 TING FANS SERVING AREAS USED FOR EGRESS
 2) OVERFLOW PROTECTION REQUIRED FOR
 ALL A/C UNITS
 3) RISERS WHICH ARE SUBJECT TO MOISTURE
 SHALL BE LINED WITH SUITABLE MATERIAL
 TO PREVENT DETERIORATION OF DRYWALL
 ENCLOSURE PER LOCAL AMENDMENTS 610.1.3.2

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-09-27 Cont ID  
Sent By tlarge Date 2000-09-27 Time 19:06 Rev Time 0.65
Received By tlarge Date 2000-09-27 Time 19:06 Sent To  
Notes
2001-01-08 00:00:00REVISE CONDENSATE SYSTEM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 21:51 Rev Time 1.00
Received By tlarge Date 2000-08-10 Time 21:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-19 Cont ID  
Sent By tlarge Date 2000-06-19 Time 19:24 Rev Time 1.00
Received By tlarge Date 2000-06-19 Time 19:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-04-29 Cont ID  
Sent By tlarge Date 2000-04-29 Time 08:11 Rev Time 2.50
Received By tlarge Date 2000-04-29 Time 08:11 Sent To  
Notes
2001-01-08 00:00:00FLOOR DRAINS ARE REQD.IN THE COMMON
 LAUNDRY ROOMS PER SPC SEC.409.4.5.
  
 PLUMBING DRAWINGS SHOW A 2"PD LINE
 REDUCING TO 1 1/2".CLARIFY.
  
 SHT.DAPT-P5.01-TUBS LOCATED DOWNSTREAM
 OF WATER CLOSETS SHALL BE VENTED PER SPC
 913.2.
  
 ALL BATHROOMS IN THE DWELLING UNIT SHALL
 COMPLY W/THE PROVISIONS OF THE FEDERAL
 FAIR HOUSING ACT 24 CFR 100.205 (C)(3)
 (IV),REQ.#7(2),PARAGRAPH (A) OR (B).
 INDICATE ON THE PLANS WHICH DESIGN
 OPTION (A OR B) IS BEING USED.
  
 COMMON AREA LAUNDRY ROOMS SHALL COMPLY
 W/FEDERAL FAIR HOUSING ACT REQ.#3(USABLE
 DOORS),AND ANSI SEC.4.32.6.
  
 CLEAR SPACE OF 30"WIDE SHALL BE PROVIDED
 BETWEEN FRONT OF TOILET BOWL AND WALL
 TO PROVIDE PERPENDICULAR APPROACH TO TUB
 IF FHA DESIGN OPTION "A"IS USED.
  
 DOORS IN BATHROOMS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQD.FOR ANY FIXTURE.
 SHOW CLEAR FLOOR SPACES ON PLANS AND
 COMPLY W/REQS.OF FEDERAL FAIR HOUSING
 ACT 24 CFR 100.205.
  
 SHT.DAPT-A7.05-MAX.DISTANCE TO BOTTOM OF
 WOOD BLOCKING ABOVE LIP OF TUB SHALL BE
 6" PER FHA REQ.#6,FIGURE #4.