Plan Review Details - Permit 00040714
Plan Review Stops For Permit 00040714
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-26 Cont ID  
Sent By bstaples Date 2000-04-18 Time 13:12 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00ELECTRICAL AND PLUMBING REQUIRE
 SEPERATE PERMITS SEE PROVISO ON PLANS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-04-21 Cont ID  
Sent By mgonzale Date 2000-04-21 Time 13:16 Rev Time 3.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:0000040714
 DATE APPROVED WITH PROVISOS.
 4-24-2000
 BY: MANUEL GONZALEZ
 561-659-8040 EXT. 2306
  
 PASSED WITH PROVISOS.
 1. BACKFLOW AND METERS MUST BE SHOWN AND
 SIZES MUST BE CALLED.
 2. HOLDING TANK WILL BE APPROVED WITH A
 HEALTH DEPARTMENT LETTER
 (SEWER IS AVAILABLE FROM ALABAMA AVE
 OR IN THE ALLEY)
 3. MUST PROVIDE A SIDEWALK CONNECTING
 FROM OKEECHOBEE BLVD TO PROPOSED PAVER
 SIDEWLK ALONG HANDICAP PARKING
 4. ANY WORK PERFORMED IN THE OKEECHOBEE
 R.O.W. MUST BE DONE UNDER AN FDOT PERMIT
 OBTAINED BY CONTRACTOR.
 5. GRAVEL PARKING IS NOT ACCEPTED.IT
 MUST BE ASPHALT.
 6. PARKING MUST BE SLOPED IN SUCH A
 MANNER WHERE STORM WATER IS RETAINED ON
 SITE. LANDSCAPE AREAS ALONG ALABAMA AVE
 SHOULD BE TURNED INTO SWALES FOR
 RETAINAGE.
 7. IF ANY WORK IS PERFORMED OUTSIDE OF
 THIS SITE ONTO A CITY R.O.W. AN
 APPLICATION FOR CONSTRUCTION WITHIN
 PUBLIC RIGHTS-OF-WAYS" MUST BE SUBMITTED
 TO THE CITY ENGINEER RICHARD D. PITTMAN.
 ALSO SUBMIT SHOP DRAWINGS ON ALL
 WATER AND SEWER MATERIALS TO BE USED TO
 PUBLIC UTILITY ENGINEERING SERVICES DEPT
 ATTENTION: DEAN LAUDERMILK
 1000 45TH STREET, WPB FL 33407
 8. METER BOXES MUST BE BY "CDR" CORP
 ONLY.IT MUST HAVE A LOCK DOWN LID
 ALONG WITH A DRILLED HOLE FOR TOUCH READ
 METERS.
 9. IF TIE-IN IS MADE, THE SANITARY
 SERVICE AND FITTINGS MUST BE SDR-26
 (TEES, TEE WYES AND CROSSES NOT ALLOWED)
 A 6" MIN DIA. IS REQUIRED.
 10. NO TRASH DUMPSTER OR TRASH LOCATION
 HAS BEEN SHOWN.
 11. TRASH NEEDS TO BE LOCATED IN A
 LOCATION WHERE IT IS TRUCK ACCESSIBLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-04-19 Cont ID  
Sent By bstaples Date 2000-04-19 Time 10:01 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00R. TURNQUEST REVIEWED 4/19/00.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-19 Cont ID  
Sent By bstaples Date 2000-04-19 Time 10:42 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVIEWED BY GRACE JOYCE.