Plan Review Details - Permit 00040264
Plan Review Stops For Permit 00040264
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 10:31 Rev Time 0.00
Received By dpalmer Date 1900-05-03 Time 10:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-23 Cont ID  
Sent By jleech Date 2000-09-23 Time 12:29 Rev Time 0.33
Received By jleech Date 2000-09-23 Time 12:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-24 Cont ID  
Sent By cthirben Date 2000-04-24 Time 07:33 Rev Time 1.00
Received By cthirben Date 2000-04-24 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-20 Cont ID  
Sent By tlarge Date 2000-04-20 Time 06:30 Rev Time 0.33
Received By tlarge Date 2000-04-20 Time 06:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-06-01 Cont ID  
Sent By jgomez Date 2000-05-28 Time 15:56 Rev Time 3.00
Received By jgomez Date 2000-06-01 Time 19:48 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-UPDATE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. SEE
 ATTACHED. MAKE SURE SEAL IS LEGIBLE.
 2-MASONRY LETTER BY CSR RINKER:
 -UPDATE LETTER AND ENGINEER TO SIGN,
 SEAL AND DATE CROSS SECTIONS DETAILS
 AND SAFE LOADS.
 -PROVIDE LEGIBLE DRAWINGS.
 3-MULLION PRODUCT APPROVAL IS TO BE USED
 WITH SERIES 7500 WINDOWS MULLED
 TOGETHER ONLY. PROVIDE MULLION PRODUCT
 APPROVAL FOR HORIZONTAL APPLICATIONS
 AND MULLION FOR TRANSOMS ABOVE DOORS.
 -CLEARLY INDICATE WHAT MULLION SIZE AND
 FASTENERS ARE GOING TO BE USED FOR
 EACH APPLICATION.
 -PROVIDE UPDATED PRODUCT APPROVAL.
 4-NEED STORM PANELS PRODUCT APPROVAL.
 -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING ACCORDING
 TO THE DESIGN PRESSURES (MEAN ROOF HT)
 EDGE DISTANCE, PANEL SPAN AND ANCHOR'G
 STRUCTURE.
 5-SIZE OF ATTIC ACCESS TO BE 22"X36" MIN
 SECTION 2309.6 SBC 1997. REVISE NOTE 7
 6-UPDATE ALL DRAWINGS. THIS CITY HAS
 ADOPTED SBC 1997.SEE COMMENTS ON PLANS
 7-PROVIDE COMPLETE FRAMING DETAILS AT
 ALL ARCHED OPENINGS. SECTION 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 8-PROVIDE COMPLETE DETAIL/SPECIFICATIONS
 FOR CEILING CONSTRUCTION AT ENTRY AND
 REAR PORCHES. SECTION 2504.2 SBC 1997.
 INCLUDING FASTENER TYPE AND SPACING.
 9-PROVIDE COMPLETE HEADER/MULLION DETAIL
 AT ENTRY DOORS. BET. DOOR AND TRANSOM.
 10-PROVIDE COPIES OF CURRENT PRODUCT
 APPROVAL FOR "LA PORTE" FRENCH DOORS.
 11-PROVIDE SOIL TEST REPORT WITH THE
 MINIMUM INFORMATION AS REQUESTED ON
 SECTION 1804.2.7.2 OF CITY AMENDMENTS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-11 Cont ID  
Sent By gjoyce Date 2000-04-11 Time 10:17 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***