2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-UPDATE THE DESIGN CERTIFICATION FOR |
| BUILDING CODE COMPLIANCE FORM. SEE |
| ATTACHED. MAKE SURE SEAL IS LEGIBLE. |
| 2-MASONRY LETTER BY CSR RINKER: |
| -UPDATE LETTER AND ENGINEER TO SIGN, |
| SEAL AND DATE CROSS SECTIONS DETAILS |
| AND SAFE LOADS. |
| -PROVIDE LEGIBLE DRAWINGS. |
| 3-MULLION PRODUCT APPROVAL IS TO BE USED |
| WITH SERIES 7500 WINDOWS MULLED |
| TOGETHER ONLY. PROVIDE MULLION PRODUCT |
| APPROVAL FOR HORIZONTAL APPLICATIONS |
| AND MULLION FOR TRANSOMS ABOVE DOORS. |
| -CLEARLY INDICATE WHAT MULLION SIZE AND |
| FASTENERS ARE GOING TO BE USED FOR |
| EACH APPLICATION. |
| -PROVIDE UPDATED PRODUCT APPROVAL. |
| 4-NEED STORM PANELS PRODUCT APPROVAL. |
| -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS |
| AND ANCHOR TYPE AND SPACING ACCORDING |
| TO THE DESIGN PRESSURES (MEAN ROOF HT) |
| EDGE DISTANCE, PANEL SPAN AND ANCHOR'G |
| STRUCTURE. |
| 5-SIZE OF ATTIC ACCESS TO BE 22"X36" MIN |
| SECTION 2309.6 SBC 1997. REVISE NOTE 7 |
| 6-UPDATE ALL DRAWINGS. THIS CITY HAS |
| ADOPTED SBC 1997.SEE COMMENTS ON PLANS |
| 7-PROVIDE COMPLETE FRAMING DETAILS AT |
| ALL ARCHED OPENINGS. SECTION 104.2.2 |
| CITY AMENDMENTS TO SBC 1997. |
| 8-PROVIDE COMPLETE DETAIL/SPECIFICATIONS |
| FOR CEILING CONSTRUCTION AT ENTRY AND |
| REAR PORCHES. SECTION 2504.2 SBC 1997. |
| INCLUDING FASTENER TYPE AND SPACING. |
| 9-PROVIDE COMPLETE HEADER/MULLION DETAIL |
| AT ENTRY DOORS. BET. DOOR AND TRANSOM. |
| 10-PROVIDE COPIES OF CURRENT PRODUCT |
| APPROVAL FOR "LA PORTE" FRENCH DOORS. |
| 11-PROVIDE SOIL TEST REPORT WITH THE |
| MINIMUM INFORMATION AS REQUESTED ON |
| SECTION 1804.2.7.2 OF CITY AMENDMENTS. |