Plan Review Details - Permit 00031741
Plan Review Stops For Permit 00031741
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-18 Cont ID  
Sent By rmcdouga Date 2000-05-18 Time 10:06 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK PER D.PALMER 5-17-00 RM

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-28 Cont ID  
Sent By dpalmer Date 2000-04-28 Time 06:28 Rev Time 0.00
Received By dpalmer Date 2000-04-28 Time 06:28 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: YOU SHOW THE SMOKE DETECTORS ON
 THE SAME CIRCUIT WITH THE BATH GFI`S.
 THIS IS NOT PERMITTED. 210-11-C-3
 BATH(S) ARE DEDICATED.
  
 2)NOTE: ALSO MISSING SMOKE DETECTOR
 OUTSIDE BEDROOM. IF THE DEN/BEDROOM IS
 GIVEN AS OPTIONAL BEDROOM THEN SD`S ARE
 REQ`D INSIDE AND OUTSIDE.
  
  
 3)NOTE:PANEL SCHEDULE SHOWS TWO SM APP-
 -LIANCE CIRCUITS.THIS DOES NOT CORRELATE
 WITH PLANS? THE LIGHTING IS SHOWN AS
 ONE OF THE CIRCUITS?? PLEASE CORRECT.
  
 4)NOTE: THE NOTESON THE LEFTHAND SIDE
 OF THE PLANS REFERENCE CODES FROM THE
 '96' NEC. PLEASE CORRECT CODE #`S TO
 REFLECT '99' NEC.
  
 5)NOTE:PLEASE SUBMIT AND HAVE DRAWN ON
 MAIN/PANEL THE AIC RATING OF THE MAIN
 BREAKER. MAIN MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9/215-5
 AIC RATINGS ARE FIGURED FROM FAULT
 CURRENT CALCULATIONS.
  
  
 PLEASE CORRECT AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 09:48 Rev Time 1.00
Received By cthirben Date 2000-08-14 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-12 Cont ID  
Sent By cthirben Date 2000-04-12 Time 08:49 Rev Time 1.00
Received By cthirben Date 2000-04-12 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By jleech Date 2000-08-16 Time 17:23 Rev Time 0.25
Received By jleech Date 2000-08-16 Time 17:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-04-18 Cont ID  
Sent By tlarge Date 2000-04-18 Time 08:15 Rev Time 0.33
Received By tlarge Date 2000-04-18 Time 08:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-05-17 Cont ID  
Sent By rmcdouga Date 2000-05-17 Time 10:21 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
  
 1)PROVIDE FLOOD ELEVATION CERTIFICATE
  
 2)SPECIFY SPECIFIC ANCHORS TO BE USED
 TO ANCHOR STORM PANELS PRIOR TO INSTALA-
 TION
  
 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO-DADE PRODUCT APPROVALS FOR
 HORIZONTAL SLIDING WINDOWS AS SPECIFIED
 ON PLANS

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-05 Cont ID  
Sent By gjoyce Date 2000-04-05 Time 10:23 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***