2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-FLOOD ZONE "AO". NEED ELEVATION |
| CERTIFICATE. |
| -NOTE: LOWEST FLOOR ELEVATION TO BE NO |
| LESS THAN 18" ABOVE THE CROWN OF THE |
| ROAD. SEC 3107.1.1 CITY AMENDMENTS. |
| 2-CLEARLY INDICATE AREAS TO HAVE SAFETY |
| GLASS. SEE PLANS FOR COMMENTS. |
| SECTION 2405.2 SBC 1997. |
| 3-CLARIFY WINDOW SIZE FOR BEDROOMS #2 |
| AND #3. WHAT IS A SH 34+4?. WINDOW TO |
| HAVE OPENING WITH A CLEAR HEIGHT OF |
| 24" MINIMUM. SEC 1005.4 SBC 1997. |
| 4-DESIGN CERTIFICATION FOR BUILDING CODE |
| COMPLIANCE FORM: |
| -ENGINEER WHO SEALED THIS FORM TO SEAL |
| STRUCTURAL DRAWINGS TOO. |
| -REVISE MEAN ROOF HEIGHT. 16'-0" PLUS |
| OR MINUS. MEAN ROOF HEIGHT IS TAKEN |
| FROM GRADE, NOT FROM FINISH FLOOR TO |
| THE AVERAGE POINT OF THE HIGHEST ROOF. |
| 5-REVISE/UPDATE DRAWINGS. SEE COMMENTS |
| ON PLANS. |
| 6-SOIL TEST REPORT TO HAVE ORIGINAL |
| SIGNATURE AND DATE WHEN DOCUMENT WAS |
| SEALED. |
| 7-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| DOOR WITHOUT SIDELITES AND WITH |
| LEGIBLE DRAWINGS. |
| 8-PROVIDE COPIES OF TEST REPORTS FOR |
| SLIDING GLASS DOORS AS PER ASTM E-330. |
| SECTION 1706 SBC 1997. |
| -PROFESSIONAL OF RECORD TO WRITE JOB |
| LOCATION FOR SITE SPECIFIC PRODUCT |
| APPROVAL FOR DOORS AND WINDOWS BY |
| NORANDEX. ALSO CLEARLY INDICATE WHICH |
| WINDOWS SIZES AND TYPES ARE GOING TO |
| BE USED ON THIS PROJECT. |
| -PROFESSIOANL OF RECORD TO CLEARLY |
| PROVIDE NAME, ADDRESS, LICENSE NUMBER |
| AND TELEPHONE ON THIS DOCUMENT ALSO. |
| 9-STORM PANELS: |
| -CLEARLY INDICATE FASTENING METHOD TO |
| BE USED AND HIGHLIGHT ANCHOR TYPE AND |
| SPACING ACCORDING TO THE DESIGN |
| PRESSURES, STORM PANEL SPAN, EDGE |
| DISTANCE AND BUILDING STRUCTURE (THIS |
| IS MASONRY CONSTRUCTION). |