Plan Review Details - Permit 00031492
Plan Review Stops For Permit 00031492
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-04-06 Cont ID  
Sent By lmartine Date 2000-04-06 Time 12:43 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-30 Cont ID  
Sent By dpalmer Date 2000-03-30 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2000-03-30 Time 15:24 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO **************
  
 1)NOTE: NEED TO SHOW BRANCH CIRCUT #`S
 ON PLANS CORRESPONDING TO PANEL SCHEDULE
 215-5
  
 2)NOTE: PLEASE LIST AIC RATING OF THE
 EQUIPMENT MAINS. MAINS ARE TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. 110-9
  
 M)NOTE: YOU SHOW PANEL 'A' AS BEING MLO?
 IF THIS IS THE CASE THEN PLEASE SHOW THE
 EQUIPMENT GROUNDING CONDUCTOR REQ`D AND
 SIZE PER 250-122
  
 4)NOTE: YOU SHOW PANEL BEING INSTALLED
 IN CLOSET. THIS IS NOT PERMITTED! THIS
 AREA IS TO BE LABELED ON PLANS AS DED-
 -ICATED ELEC. EQUIPMENT SPACE/ROOM.
 PLEASE CHECK 384-7 AND 240-24D/110-26
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEWBEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-29 Cont ID  
Sent By rturnque Date 2000-03-29 Time 14:41 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-03 Cont ID  
Sent By cthirben Date 2000-04-03 Time 07:32 Rev Time 1.00
Received By cthirben Date 2000-04-03 Time 07:28 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 ******************PROVISO***************
  
 1. INDICATE ON PLANS CFM'S VALUE IN ROOM
 # 122 AND 102.
  
 2. INSTALL EXHAUST FAN IN BATHROOM# 106.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-25 Time 12:00 Rev Time 0.33
Received By tlarge Date 2000-08-25 Time 12:00 Sent To  
Notes
2001-01-08 00:00:00REVISE SANITARY AND WATER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-28 Cont ID  
Sent By tlarge Date 2000-04-28 Time 07:29 Rev Time 0.65
Received By tlarge Date 2000-04-28 Time 07:21 Sent To  
Notes
2001-01-08 00:00:00RPIVATE TOILET ROOM SHALL BE ADAPTABLE
 PER FACBC SEC.4.1.3.(11).

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-04-01 Cont ID  
Sent By tlarge Date 2000-04-01 Time 07:21 Rev Time 0.65
Received By tlarge Date 2000-04-01 Time 07:21 Sent To  
Notes
2001-01-08 00:00:00ALL COMMON AREA TOILET ROOMS SHALL
 COMPLY W/FACBC SEC.4.22.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY PERMANENT FIXED
 LADDER OR RELOCATE EWH TO FLOOR.
  
 SUBMIT ELEVATION DETAILS FOR HANDICAP
 FIXTURES AND APPURTENANCES.MOUNTING
 HEIGHTS SHALL COMPLY W/FACBC.
  
 SUBMIT WATER SUPPLY RISER DIAGRAM FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.WATER SUPPLY CONTROL SHALL
 COMPLY W/SPC 610.4.1,610.4.2
  
 SINK IN LOUNGE SHALL COMPLY W/FACBC SEC.
 4.24.1-4.24.7.CLEAR FLOOR SPACE SHALL BE
 CENTERED ON FIXTURE.
  
 SUBMIT OCCUPANT LOAD OF SPACE PER SPC
 SEC.407.1.3.SUPPLY MIN.FIXTURE REQS.PER
 TABLE 407 OF SPC.
  
 DRINKING FOUNTAINS ARE REQD.PER SPC
 TABLE 407.DRINKING FOUNTAINS SHALL
 COMPLY W/FACBC SEC.4.1.3.(10)(A).
  
 SHOWER SHALL COMPLY W/FACBC 4.21.2 THRU
 4.21.8.