Plan Review Details - Permit 00031470
Plan Review Stops For Permit 00031470
Review Stop P PLUMBING
Rev No 3 Status P Date 2000-05-06 Cont ID  
Sent By tlarge Date 2000-05-06 Time 05:23 Rev Time 0.50
Received By tlarge Date 2000-05-06 Time 05:23 Sent To  
Notes
2001-01-08 00:00:00REVISE GAS LINE.U/G TANK SHALL BE
 PROTECTED IF WITHIN 10' OF DRIVE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-04-21 Cont ID  
Sent By tlarge Date 2000-04-21 Time 09:44 Rev Time 0.30
Received By tlarge Date 2000-04-21 Time 09:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-29 Cont ID  
Sent By tlarge Date 2000-03-29 Time 05:51 Rev Time 0.75
Received By tlarge Date 2000-03-29 Time 05:51 Sent To  
Notes
2001-01-08 00:00:00SUBMIT COPY OF STATE OF FLA.LP GAS
 LICENSE.COUNTYWIDE AMENDMENTS TO SPC
 SECS.101.4.7.,104.1.1.
  
 SUBMIT GAS SIZING CHART FOR SYSTEM
 DESIGN.COMPLY W/TABLES 305.4(A)-305.4(E)
  
 LP TANK SHALL BE A MIN.10' FROM
 RESIDENCE PER NFPA TABLE 3-2.2.2.
  
 UNDERGROUND CONTAINERS WITHIN 10' OF
 DRIVE SHALL COMPLY W/NFPA 58 SEC.3-2.4.8
  
 INDICATE LOCATION OF STUB FOR HOUSE ON
 PLAN.
  
 LOCATION OF LP TANK FROM SOURCES OF
 IGNITION,BUILDING OPENINGS,AND MECH.AIR
 INTAKES SHALL COMPLY W/NFPA 58 SEC.
 3-2.2.2(D).
  
 SUBMIT COPIES OF ASTM STANDARDA120.
 THIS STANDARD IS NOT REFERENCED IN SPC,
 SGC,OR NFPA 58.