Plan Review Details - Permit 00031211
Plan Review Stops For Permit 00031211
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-06-01 Cont ID  
Sent By hpiskura Date 2000-06-01 Time 10:10 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-05-11 Cont ID  
Sent By hpiskura Date 2000-05-11 Time 15:09 Rev Time 0.00
Received By hpiskura Date 2000-05-11 Time 13:10 Sent To  
Notes
2001-01-08 00:00:00SAME NO CHANGE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-05-03 Cont ID  
Sent By hpiskura Date 2000-05-03 Time 10:23 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-04-05 Cont ID  
Sent By hpiskura Date 2000-04-05 Time 12:56 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-05-10 Cont ID  
Sent By dpalmer Date 2000-05-10 Time 17:51 Rev Time 0.00
Received By dpalmer Date 2000-05-10 Time 17:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 11:55 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: SEE FIRST SET OF NOTES.
  
  
 IN ODER FOR MIANS NOT TO BE GROUPED YOU
 MUST MEET CODE FOR TENNAT SEPARATION.
  
 YOU STILL ARE MISSING CORRECTIONS ON
 FIRST SET OF NOTES.
  
 YOU ARE NOW SHOWING NEW METER AT SEPARAT
 -E BLDG.? PLEASE GIVE DETAIL ON SERVICE
 EQUIPMENT.ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUEESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-30 Cont ID  
Sent By dpalmer Date 2000-03-30 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2000-03-30 Time 17:23 Sent To  
Notes
2001-01-08 00:00:00*************** UNAST *****************
 1)NOTE: SEPARATE LIGHTING FEED TO SEP-
 -PARATE STUCTURE NOT PERMITTED!.
  
 2)NOTE: PLEASE SUBMIT AIC RATING OF NEW
 EQUIPMENT MAINS. MAIN IS TO BE RATED FOR
 THE AVAILABLE FAULT CURRENT.110-9/215-5
  
 3)NOTE: MAINS TO BE GROUPED THIS IS
 GOING TO DEPEND MAINLY ON NEW TENTS.
 YOU ARE SHOWING NOW THAT YOU ARE ADDING
 NEW HOUSE PANEL. THIS SHOULD BE GROUPED
 AND/OR CLEARLY LABELED AS TO THE LOCATIO
 -NS OF OTHER MAIN DISC.(EG) 1 OF 2,2OF3
 ETC ETC.
  
 4)NOTE: ALL CONTIUOUS LOADS ARE TO BE
 FIGURED AT 125% (LIGHTING).
  
 5)NOTE: PLEASE SUBMIT PANEL SCHEDULE AND
 SHOW BRANCH CIRCUT #`S ON PLANS FOR
 LIGHTING AND ANY BRANCH CIRCUTS. 215-5
  
 6)NOTE: PLEASE SHOW /LIST EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 PANEL AS REQ`D AFTER FIRST MEANS OF DISC
 ANDSIZE PER 250-122
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 659-8096 EXT 8372