Plan Review Details - Permit 00030941
Plan Review Stops For Permit 00030941
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-06-22 Cont ID  
Sent By lmartine Date 2000-06-22 Time 15:58 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-04-10 Cont ID  
Sent By lmartine Date 2000-04-10 Time 12:30 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:001]1997 FL.ACC.CODE REQUIRES ACCESSIBLE
 PARKING.ACCESSIBLE ENTRANCE SHALL BE
 THE PRIMARY NOT THE SECONDARY[SEE RAMP
 AT REAR].
 2]CERTIFY ADDITIONAL FLOOR LOADING,FROM
 RESIDENTIAL TO BUSINESS USE.SEE TABLE
 1604.1,STANDARD BUILDING CODE.
 3]SUBMIT PRODUCT TESTING ON ALL NEW EXT.
 WINDOWS AND DOORS.
 4]EXPLAIN NOTE ON SHEET A.2"APPLIED
 HURRICANE SHUTTERS".
 5]SUBMIT PALM BEACH COUNTY IMPACT RECEIP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-25 Cont ID  
Sent By dpalmer Date 2000-03-25 Time 09:30 Rev Time 0.00
Received By dpalmer Date 2000-03-25 Time 09:30 Sent To  
Notes
2001-01-08 00:00:00************** PROVISIO ***************
  
 1)NOTE: SUBMIT NEW LOAD CALCULATION FOR
 COMMERCIAL BLDG. SHOW SIZE OF EXISITING
 SERVICE AND WIRE SIZES.215-5
  
  
 THE ABOVE INFORMATION MUST BE SUBMITTED
 FOR REVIEW BEFORE ANY ROUGH INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-06-21 Cont ID  
Sent By rturnque Date 2000-06-21 Time 13:55 Rev Time 0.25
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-03-27 Cont ID  
Sent By rturnque Date 2000-03-27 Time 09:59 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE AN APPROVED SECOND MEANS OF
 EGRESS FROM 2ND FL. OR PROVIDE 1 HR
 PROTECTION TO EXISTING STAIR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-06-28 Cont ID  
Sent By cthirben Date 2000-06-28 Time 09:15 Rev Time 1.00
Received By cthirben Date 2000-06-28 Time 09:15 Sent To  
Notes
2001-01-08 00:00:00PROVISO AS PER MECH. 1 REVIEW BY NCD.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-30 Cont ID  
Sent By ndenmark Date 2000-03-30 Time 14:53 Rev Time 0.33
Received By ndenmark Date 2000-03-30 Time 14:53 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 BATHROOMS TO BE PROVIDED WITH EXHAUST
 PER 1997 SMC 503.3.2

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-06-27 Cont ID  
Sent By tlarge Date 2000-06-27 Time 18:10 Rev Time 0.75
Received By tlarge Date 2000-06-27 Time 18:10 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
  
 SUBMIT SIGNED AND SEALED WATER AND
 SANITARY RISER DIAGRAMS FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 BATHROOM ON 2ND.FLR SHALL BE ADAPTABLE.
 SHOW FIXTURE CLEARANCE OF WATER CLOSET
 (18"REQD.TO CENTER FROM WALL AND LAV.)
  
 SIZE OF SHOWER SHALL COMPLY W/FACBC
 SEC.4.21.2,AND HEIGHT OF CONTROLS SHALL
 COMPLY W/FACBC SEC.4.21.5
  
 SUBMIT DETAILS OFBLOCKING FOR FUTURE
 INSTALLATION OF GRAB BARS AND SEAT PER
 FACBC SEC.4.1.3(11).
  
 SUBMIT ALL OF THE INFORMATION PRIOR TO
 PLUMBING INSPECTION.IF YOU HAVE ANY
 QUESTIONS I CAN BE REACHED AT
 561-659-8096,EXT.8377.TIMOTHY LARGE,
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-06-22 Cont ID  
Sent By tlarge Date 2000-06-22 Time 10:11 Rev Time 1.25
Received By tlarge Date 2000-06-22 Time 10:11 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY AND WATER ISOMETRICS FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING AND STOOPING.
  
 BATHROOM ON 2ND.FLOOR SHALL BE MADE
 ADAPTABLE FOR H.C.ACCESS PER FACBC SEC.
 4.1.6.(B).SHOW CLEARANCE OF W.C.FROM
 WALL,SHOWER STALL SIZE SHALL COMPLY W/
 FACBC 4.21, 4.23.SHOW WOOD BLOCKING FOR
 FUTURE INSTALLATION OF GRAB BARS AND
 SHOW HEIGHT DIMENSIONS.
  
 SHOW WHEELCHAIR TURNING SPACE IN 2ND.FLR
 TOILET.FACBC SEC.4.2.3., 4.16.2.
  
 SUBMIT DETAILS ON VERTICAL ACCESSIBILITY
 AS REQD.BY FACBC SEC.4.1.6(I)(III).THIS
 IS A CHANGE OF OCCUPANCY AND SHALL
 COMPLY W/FACBC OR SUBMIT WAIVER FROM
 FLA.DEPT.OF COMMUNITY AFFAIRS GRANTING
 RELIEF FROM VERTICAL ACCESSIBILITY.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT:659-8096,EXT.8377.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-03-28 Cont ID  
Sent By tlarge Date 2000-03-28 Time 20:30 Rev Time 1.50
Received By tlarge Date 2000-03-28 Time 20:30 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SQUARE FOOTAGE OF BUILDING PER
 SPC SEC.407.1.3.FOR MIN.PLUMBING REQS.
  
 SINK IN LOUNGE /KITCHEN SHALL COMPLY W/
 FACBC SEC.4.24.1-4.24.7.
  
 A DRINKING FOUNTAIN IS REQD.ON THE 1ST.
 AND SECOND FLOORS PER TABLE 407 OF SPC.
  
 SUBMIT ELEVATION DETAILS FOR ALL HANDI-
 CAP FIXTURES AND APPURTENANCES.
  
 SUBMIT OCCUPANT LOAD OF 2ND. FLR.
  
 DRINKING FOUNTAINS SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).
  
 TOILET ROOM ON 2ND.FLR.SHALL COMPLY W/
 FACBC SEC.4.1.6.(B),
  
 CLEARLY SHOW SHOWER DIMENSIONS.COMPLY W/
 FACBC SEC.4.1.3(11),4.21,4.23
  
 SIZE OF TOILET ROOM ON 2ND.SHALL COMPLY
 W/FACBC SEC.4.2.3,4.16.2.
  
 SUBMIT SANITARY AND WATER SUPPLY RISERS
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
  
 THIS IS A CHANGE OF OCCUPANCY AND BLDG.
 SHALL COMPLY W/FACBC 4.1.6 FOR VERTICAL
 ACCESSIBILITY OR SUBMIT WAIVER FROM FLA
 DEPT.OF COMMUNITY AFFAIRS NOT REQUIRING
 VERTICAL ACCESSIBILITY.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-24 Cont ID  
Sent By hpiskura Date 2000-03-24 Time 11:49 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
2001-01-08 00:00:00OK J. MINICOZZI HHP