Plan Review Details - Permit 00030799
Plan Review Stops For Permit 00030799
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-04-11 Cont ID  
Sent By lmartine Date 2000-04-11 Time 07:32 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-03-29 Cont ID  
Sent By lmartine Date 2000-03-29 Time 11:03 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:001]PLEASE CLERIFY TYPE OF CONSTRUCTION
 AND IF THE BUILDING IS SPRINKLED.
 2]SUBMIT AN EXITING PLAN,IDENTIFYING TWO
 APPROVED EXITS COMPLYING WITH SECTIONS
 1004.2 AND 1004.3 SBC [CANNOT EXIT
 THRU PARTS ROOM OR RESTROOMS]
 3]EXPLAIN AREAS NOT IN USE,THEY MAY BE
 REQUIRED TO HAVE FIRE SEPERATION
 4]TABLE 704.1,SBC,REQUIRES OCCUPANCY
 SEPERATION BETWEEN SERVICE AREA AND
 BUISNESS USE.
 5]SECTION 7.2 FL.ACC.CODE REQUIRES
 SERVICE COUNTERS TO BE ACCESSIBLE
 [PARTS ROOM]
 6]SECTION 4.13.6,FAC,DOOR SEPERATING NEW
 CORRIDOR AND EXISTING CORRIDOR DOES
 NOT COMPLY.
 7]CASHIER/CUSTOMER AREA MUST COMPLY WITH
 1997 FAC
 8]CONSTRUCTION VALUE SUBMITTED SEEMS LOW
 PLEASE PROVIDE COPY OF SIGNED CONTRACT

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-04-28 Cont ID  
Sent By dpalmer Date 2000-04-28 Time 09:31 Rev Time 0.00
Received By dpalmer Date 2000-04-28 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-04-26 Cont ID  
Sent By dpalmer Date 2000-04-26 Time 17:12 Rev Time 0.00
Received By dpalmer Date 2000-04-26 Time 17:12 Sent To  
Notes
2001-01-08 00:00:00NEED TO HAVE PLANS RE-DONE TO REFLECT
 WORK ON THE JOBSITE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-29 Cont ID  
Sent By dpalmer Date 2000-03-29 Time 14:35 Rev Time 0.00
Received By dpalmer Date 2000-03-29 Time 14:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 10:26 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 10:26 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: NEED TO SHOW ALL ELECTRICAL
 WHICH IS REQ`D BY NEC. AND OUTLET
 SPACING TO MEET PALM BEACH COUNTY AMEND-
 MENTS. 210-50.
  
 2)NOTE: ELECTRICAL FOR LIGHTING IS TO BE
 SHOWN.
  
 3)NOTE: ALL BRANCH CIRCUTS FOR REQ`D
 ELECTRICAL ARE TO BE LISTED ON PLANS AND
 SHOW REVISED PANEL SCHEDULES TO MATCH.
 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND APPROVAL. IF THERE ARE ANY
 QUESTIONS PLEASE CALL. 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-04-07 Cont ID  
Sent By rturnque Date 2000-04-07 Time 09:56 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE 45 MINUTE, SELF CLOSING FIRE
 DOOR IN SOUTH EXIT CORRIDOR.
  
 PROVIDE PERMIT AND SHOP DRAWINGS FOR
 FIRE ALARM SYSTEM REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-03-24 Cont ID  
Sent By rturnque Date 2000-03-24 Time 15:28 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00IMPROPER EXITING FROM BATHROOM AREA

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-31 Cont ID  
Sent By cthirben Date 2000-03-31 Time 11:51 Rev Time 1.00
Received By cthirben Date 2000-03-31 Time 11:51 Sent To  
Notes
***NONE***