Plan Review Details - Permit 00030757
Plan Review Stops For Permit 00030757 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2000-04-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-04-18 |
Time |
07:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-04-18 |
Time |
07:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-04-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-04-05 |
Time |
23:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-04-05 |
Time |
23:19 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | 1)NOTE:ALL PLANS NEED TO HAVE AIC RATING | | SUBMITTED ON PLANS.110-09/215-5 | | MAINS ARE TO BE RATED FOR THE AVAILABLE | | FAULT CURRENT. | | | | 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE | | AND OUTSIDE ALL SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1 | | | | 3)NOTE: PLEASE LIST THE REQ`D CIRCUIT | | FOR BATH(S) AS PER 210-11-C-3/215-5 | | | | 4)NOTE: ALL SERVICE ENTRANCE CONDUCTORS | | ARE TOO SMALL FOR SERVICE AND LOAD. | | 310-16 PLEASE CORRECT. | | | | 5)NOTE: AS REQ`D BY 250-50 GROUNDING | | ELECTRODE CONDUCTOR MUST GO TO BLDG | | STEEL. PLEASE SHOW. | | | | 6)NOTE: AS PER 210-52E GFI IN FRONT OF | | DWELLING IS REQ`D. PLEASE SHOW. | | | | 7)NOTE: NEED TO HAVE GFI RECEPT FOR A/C | | AS PER 210-63 | | | | ALL THE ABOVE NOTES HAVE BEEN GIVEN AS | | PREVIOUS NOTES. ALL THE ABOVE NEEDS TO | | BE ON ALL PLANS. | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-03-23 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-03-23 |
Time |
08:16 |
Rev Time |
1.00 |
Received By |
cthirben |
Date |
2000-03-23 |
Time |
08:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-03-17 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-03-17 |
Time |
17:20 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-03-17 |
Time |
17:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2000-05-15 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-05-15 |
Time |
15:22 |
Rev Time |
2.00 |
Received By |
fknapp |
Date |
2000-05-15 |
Time |
15:22 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | ****************PROVISO***************** | | | | SBC 104.2.2 | | | | 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | METRO DADE PRODUCT APPROVALS FOR: | | ALL EXTERIOR DOOR ASSEMBLIES | | MULLIONS | | ARCH TRANSOMS | | | | 2)PROVIDE DRAWINGS FOR STORM PANELS | | THAT ARE SIGN, DATED AND HAVE RAISE SEAL | | OF REQ ENGINEER WITH SPECIFIC ANCHORS | | AND MOUNTING TO BE USED. |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2000-04-29 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-04-29 |
Time |
13:55 |
Rev Time |
4.00 |
Received By |
fknapp |
Date |
2000-04-28 |
Time |
15:30 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | *****************DENIED***************** | | | | SBC 104.2.2 | | | | 1)PROVIDE SOIL REPORT | | | | 2)PROVIDE ENGINEERING FOR BUTT GLASS | | | | 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | METRO DADE PRODUCT APPROVALS FOR: | | ALL EXTERIOR DOOR ASSEMBLIES | | MULLIONS | | ARCH TRANSOMS | | ROOF COVERING | | | | 4)PROVIDE DRAWINGS FOR STORM PANELS | | THAT ARE SIGN,DATED AND HAVE RAISE SEAL | | OF REQ ENGINEER WITH SPECIFIC ANCHORS | | AND MOUNTING TO BE USED. | | | | 5)PROVIDE DESIGN PRESSURES FOR ALL | | EXTERIOR OPENINGS. | | | | 6)PROVIDE ROOF SHEATHING NAIL ZONES THAT | | COMPLY WITH CITY AMENDMENTS FIG 2306.1 | | 4"OC ZONE 3. | | | | 7)PROVIDE GUARDRAILS THAT COMPLY WITH | | SBC 1015.3 4" SPHERE SHALL NOT PASS THRU | | | | 8)BEFORE A PERMIT TO CONSTRUCT CAN BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | BEACH CO., THE PERMIT PLANS STAMPED BY | | THEM AND THE RECEIPT ATTACHED T0 THE | | PERMIT APPLICATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-03-16 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-03-16 |
Time |
15:13 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|