Plan Review Details - Permit 00030757
Plan Review Stops For Permit 00030757
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-18 Cont ID  
Sent By dpalmer Date 2000-04-18 Time 07:28 Rev Time 0.00
Received By dpalmer Date 2000-04-18 Time 07:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-04-05 Cont ID  
Sent By dpalmer Date 2000-04-05 Time 23:19 Rev Time 0.00
Received By dpalmer Date 2000-04-05 Time 23:19 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:ALL PLANS NEED TO HAVE AIC RATING
 SUBMITTED ON PLANS.110-09/215-5
 MAINS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT.
  
 2)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1
  
 3)NOTE: PLEASE LIST THE REQ`D CIRCUIT
 FOR BATH(S) AS PER 210-11-C-3/215-5
  
 4)NOTE: ALL SERVICE ENTRANCE CONDUCTORS
 ARE TOO SMALL FOR SERVICE AND LOAD.
 310-16 PLEASE CORRECT.
  
 5)NOTE: AS REQ`D BY 250-50 GROUNDING
 ELECTRODE CONDUCTOR MUST GO TO BLDG
 STEEL. PLEASE SHOW.
  
 6)NOTE: AS PER 210-52E GFI IN FRONT OF
 DWELLING IS REQ`D. PLEASE SHOW.
  
 7)NOTE: NEED TO HAVE GFI RECEPT FOR A/C
 AS PER 210-63
  
 ALL THE ABOVE NOTES HAVE BEEN GIVEN AS
 PREVIOUS NOTES. ALL THE ABOVE NEEDS TO
 BE ON ALL PLANS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-23 Cont ID  
Sent By cthirben Date 2000-03-23 Time 08:16 Rev Time 1.00
Received By cthirben Date 2000-03-23 Time 08:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-17 Cont ID  
Sent By tlarge Date 2000-03-17 Time 17:20 Rev Time 0.33
Received By tlarge Date 2000-03-17 Time 17:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-05-15 Cont ID  
Sent By fknapp Date 2000-05-15 Time 15:22 Rev Time 2.00
Received By fknapp Date 2000-05-15 Time 15:22 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 ALL EXTERIOR DOOR ASSEMBLIES
 MULLIONS
 ARCH TRANSOMS
  
 2)PROVIDE DRAWINGS FOR STORM PANELS
 THAT ARE SIGN, DATED AND HAVE RAISE SEAL
 OF REQ ENGINEER WITH SPECIFIC ANCHORS
 AND MOUNTING TO BE USED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-04-29 Cont ID  
Sent By fknapp Date 2000-04-29 Time 13:55 Rev Time 4.00
Received By fknapp Date 2000-04-28 Time 15:30 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************DENIED*****************
  
 SBC 104.2.2
  
 1)PROVIDE SOIL REPORT
  
 2)PROVIDE ENGINEERING FOR BUTT GLASS
  
 3)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 ALL EXTERIOR DOOR ASSEMBLIES
 MULLIONS
 ARCH TRANSOMS
 ROOF COVERING
  
 4)PROVIDE DRAWINGS FOR STORM PANELS
 THAT ARE SIGN,DATED AND HAVE RAISE SEAL
 OF REQ ENGINEER WITH SPECIFIC ANCHORS
 AND MOUNTING TO BE USED.
  
 5)PROVIDE DESIGN PRESSURES FOR ALL
 EXTERIOR OPENINGS.
  
 6)PROVIDE ROOF SHEATHING NAIL ZONES THAT
 COMPLY WITH CITY AMENDMENTS FIG 2306.1
 4"OC ZONE 3.
  
 7)PROVIDE GUARDRAILS THAT COMPLY WITH
 SBC 1015.3 4" SPHERE SHALL NOT PASS THRU
  
 8)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED T0 THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-03-16 Cont ID  
Sent By gjoyce Date 2000-03-16 Time 15:13 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***