Plan Review Details - Permit 00030252
Plan Review Stops For Permit 00030252
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-05-03 Cont ID  
Sent By dpalmer Date 2000-05-03 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2000-05-03 Time 17:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-08 Cont ID  
Sent By dpalmer Date 2000-03-08 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2000-03-08 Time 14:13 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE:PLEASE SUBMIT PLANS SHOWING ALL
 BRANCH CIRCUT #`S TO OUTLETS AND LIGHT-
 -ING.
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULE.
  
 3)NOTE: EVEN THOUGH SERVICE LOOKS LARGE
 ENOUGH. PLEASE SUBMIT LOAD CALCULATION
 FOR CITY AND FOR YOUR RECORDS.215-5
  
 PLEASE HAVE ALL THE ABOVE INFORMATION
 SUBMITTED FOR REVIEW AND APPROVAL BEFORE
 ROUGH INSPECTION IS CALLED IN. IF THERE
 ARE ANY QUESTIONS PLEASE CALL.659-8096
 EXT 8372