Plan Review Details - Permit 00030083
Plan Review Stops For Permit 00030083
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-04-25 Cont ID  
Sent By dpalmer Date 2000-04-25 Time 08:24 Rev Time 0.00
Received By dpalmer Date 2000-04-25 Time 08:24 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: PLEASE PROVIDE THE AIC RATING
 OF THE MAIN. THE MAIN MUST BE RATED FOR
 THE AVIALABLE FAULT CURRENT PER 110-9.
 PLEASE HAVE THIS LISTED ON THE RISER
 DIAGRAM. 215-5
  
 PLEASE SUBMIT THE ABOVEINFORMATION FOR
 REVIEW BEFORE ANY ROUGH INSPECTION IS
 CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By dpalmer Date 2000-03-07 Time 13:58 Rev Time 0.00
Received By dpalmer Date 2000-03-07 Time 13:58 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: NEED TO SHOW ANY NEW A/C UNITS
 BEING ADDED FOR ADDITION.
  
 2)NOTE: NEED TO SUBMIT COMPLETE LOAD
 CALCULATIONS FOR THE EXISTING SERVICE,
 TO INCLUDE ALL NEW LOADS.
  
 3)NOTE:NEED TO HAVE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PLEASE SHOW. AS REQ`D BY 210-8-A-6
  
 4)NOTE: NEED TO SHOW NEW CIRCUTS ON
 PANEL SCHEDULE FOR NEW BATH AS REQ`D BY
 210-52D AND 210-11-C-3.
  
 5)NOTE: NEED TO SHOW ANY NEW BLDG. STEEL
 AS BEING BONDED TO THE GROUNDING ELEC-
 -TRODE. MUST BE A PART OF GROUNDING
 SYSTEM. AS PER 250-50
  
 PLEASE SUBMIT FOR REVIEW AND APPROVAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXY 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2001-06-28 Cont ID  
Sent By pkrauss Date 2001-06-28 Time 11:49 Rev Time 0.30
Received By pkrauss Date 2001-06-28 Time 11:49 Sent To  
Notes
2001-06-28 00:00:00MECHANICAL PERMIT 00030085

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-04-25 Cont ID  
Sent By ndenmark Date 2000-03-10 Time 07:22 Rev Time 0.50
Received By ndenmark Date 2000-03-10 Time 07:22 Sent To  
Notes
2001-01-08 00:00:00ACCEPTED BY REVISION******************
  
 SUBMIT PLANS DETAILING MECH INSTALLATION

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-03-04 Cont ID  
Sent By tlarge Date 2000-03-04 Time 08:57 Rev Time 0.33
Received By tlarge Date 2000-03-04 Time 08:56 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 SUBMIT SIGNED AND SEALED SANITARY RISER
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-04-24 Cont ID  
Sent By hpiskura Date 2000-04-24 Time 11:40 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-23 Cont ID  
Sent By hpiskura Date 2000-03-23 Time 08:25 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-04-25 Cont ID  
Sent By gjoyce Date 2000-04-25 Time 08:46 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***