Plan Review Details - Permit 00021260
Plan Review Stops For Permit 00021260
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-03-23 Cont ID  
Sent By hpiskura Date 2000-03-23 Time 10:00 Rev Time 99.00
Received By hpiskura Date 2000-03-23 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-03-13 Cont ID  
Sent By dpalmer Date 2000-03-13 Time 09:32 Rev Time 0.00
Received By dpalmer Date 2000-03-13 Time 09:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-03-23 Cont ID  
Sent By hpiskura Date 2000-03-23 Time 10:01 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-03-15 Cont ID  
Sent By ndenmark Date 2000-03-15 Time 06:57 Rev Time 0.33
Received By ndenmark Date 2000-03-15 Time 06:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-06-15 Cont ID  
Sent By tlarge Date 2000-06-15 Time 09:17 Rev Time 0.33
Received By tlarge Date 2000-06-15 Time 09:17 Sent To  
Notes
2001-01-08 00:00:00REVISED SANITARY RISER-CHANGE TO AIR
 ADMITTANCE VALVES.
  
 SUBMIT SIGNED AND SEALED WATER RISER
 PRIOR TO FINAL PLBG.INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-03-20 Cont ID  
Sent By tlarge Date 2000-03-23 Time 09:56 Rev Time 0.50
Received By tlarge Date 2000-03-23 Time 09:56 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SUBMIT WATER RISER PRIOR TO TOP
 OUT INSP.

Review Stop P PLUMBING
Rev No 1 Status N Date 2000-03-23 Cont ID  
Sent By tlarge Date 2000-03-04 Time 12:02 Rev Time 1.00
Received By tlarge Date 2000-03-04 Time 12:02 Sent To  
Notes
2001-01-08 00:00:00SIZE OF ACCESSIBLE STALLS SHALL COMPLY
 W/FACBC 4.1.6(B),4.17.3(SEE EXCEPTION &
 EXCEPTION:NEW CONSTRUCTION.)
  
 MIN.CLEAR FLOOR SPACE UNDER H.C..LAV.
 SHALL BE 29" PER FACBC SEC.4.19.2 AND
 TOP SHALL BE 34" MAX.
  
 HT.OF WATER CLOSET SHALL BE 19"PER FACBC
 SEC.4.16.3.
  
 SIZE ALL WASTE STACKS.COMPLY W/SPC SEC.
 714.2.
  
 DRINKING FOUNTAIN NOT VENTED.COMPLY W/
 SPC SEC.901.2.
  
 SUBMIT DETAIL OF H.C. DRINKING.COMPLY W/
 FACBC SEC.4.15.2.,4.15.5
  
 SHOW CLEAR FLOOR SPACE FOR URINAL.COMPLY
 W/FACBC SEC.4.18.3.
  
 ALL PIPING UNDER FIXTURES SHALL BE
 CONFIGURED TO PROTECT AGAINST IMPACT PER
 FACBC SEC.4.19.4.