Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-26 Cont ID  
Sent By dpalmer Date 2000-02-26 Time 09:27 Rev Time 0.00
Received By dpalmer Date 2000-02-26 Time 09:26 Sent To  
Notes
2001-01-08 00:00:00************* PROVISO *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATION
 ON MAIN 250AMP PANEL. PLEASE SHOW NEW
 LOADS BEING ADDED TO NEW 125A PANEL.
  
 2)NOTE:VALUE OF JOB SHOULD INCLUDE
 UPS SYSTEM, EVEN IF SUPPLIED BY OWNER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 BEFORE ANY INSPECTION IS CALLED IN. IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
 659-8096 EXT 8372