Plan Review Details - Permit 00020370
Plan Review Stops For Permit 00020370
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-03-15 Cont ID  
Sent By dpalmer Date 2000-03-15 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2000-03-15 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-03-08 Cont ID  
Sent By dpalmer Date 2000-03-08 Time 20:51 Rev Time 0.00
Received By dpalmer Date 2000-03-08 Time 20:50 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *******************
  
 NOTES ON PLANS
 PLEASE CORRECT PANEL SCHEDULES,
 TO INCLUDE ALL LOADS, WIRE SIZES, BRKR
 SIZES FOR OVERCURRENT PROTECTION.
 MISSING OUTLET FOR A/C.
 FEEDERS FOR PANEL B

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-30 Cont ID  
Sent By jleech Date 2000-08-30 Time 18:00 Rev Time 0.25
Received By jleech Date 2000-08-30 Time 18:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-03-16 Cont ID  
Sent By cthirben Date 2000-03-16 Time 16:18 Rev Time 1.00
Received By cthirben Date 2000-03-16 Time 16:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-02-26 Cont ID  
Sent By jleech Date 2000-02-26 Time 12:11 Rev Time 0.35
Received By jleech Date 2000-02-26 Time 12:10 Sent To  
Notes
2001-01-08 00:00:00DENIED
 ALL PROBLEMS IN GUEST QUARTERS;
 1.FIRST FLOOR, CFM'S REQUIRED FOR ALL
 DROPS.
 2.SECOND FLOOR, RETURN AIR NOT PERMITED
 IN BATHROOM.
 3.A/C UNIT TO SMALL FOR CFM'S SHOWN.
 790 CFM WITH ONE DROP MISSING
 CALCULATIONS. 1 1/2 TON A/H WILL
 PROVIDE ONLY 600 CFM.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-02-11 Cont ID  
Sent By tlarge Date 2000-02-11 Time 07:15 Rev Time 0.33
Received By tlarge Date 2000-02-11 Time 07:15 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-05-08 Cont ID  
Sent By rmcdouga Date 2000-05-08 Time 12:39 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-04-25 Cont ID  
Sent By rmcdouga Date 2000-04-25 Time 07:41 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)PROVIDE DESIGN COMPLIANCE FORM FOR
 MEAN ROOF HEIGHT OF 24'
 2)FORM 600A AND EPL DISPLAY CARD SPECIFY
 FLOOR AREA OF 2348 SQFT.PLANS INDICATE
 2468 SQFT PLUS 754 SQFT FOR GUEST
 SUITE. CLARIFY
 3)MANUAL J SPECIFIES 2348 SQFT FOR MAIN
 HOUSE AND DOES NOT ADDRESS GUEST SUITE
 4)EXTERIOR DOOR AT GUEST SUITE DOES NOT
 COMPLY WITH EGRESS REQUIREMENTS.SEE
 97 SBC-1012.1
 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI APPROVED PRODUCT APPROVALS
 FOR INSWING EXTERIOR DOOR AT GUESS
 SUITE.
 6)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI APPROVED PRODUCT APPROVALS
 FOR STORM PANELS
 7)PROVIDE SOIL BEARING TEST RESULTS
 PRIOR TO FIRST INSPECTION

Review Stop Z ZONING
Rev No 2 Status P Date 2000-02-10 Cont ID  
Sent By gjoyce Date 2000-02-10 Time 13:44 Rev Time 0.50
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2000-02-10 Cont ID  
Sent By gjoyce Date 2000-02-10 Time 10:59 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00COTTAGE TOO HIGH