Plan Review Details - Permit 00011063
Plan Review Stops For Permit 00011063
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-03-20 Cont ID  
Sent By dpalmer Date 2000-03-20 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2000-03-20 Time 14:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-02-24 Cont ID  
Sent By dpalmer Date 2000-02-24 Time 07:20 Rev Time 0.00
Received By dpalmer Date 2000-02-24 Time 07:20 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 ALL NOTES PREVIOUSLY GIVEN!!!
  
 1)NOTE:SHOW TWO CONDIUTS FROM METER TO
 DISCS. YOU SHOW ONE GOING TO PANEL AND
 ONE GOING TO ONE DISC.?????
  
 2)NOTE:ART;210-52D WAS GIVEN FOR REF.
 TO THE BATH CIRCUT REQ`MENTS.
 SEE #12 AND 20 AMP REQ`D.
  
 3)NOTE: AIC RATING OF MAINS REQ`D BY
 110-9/110-10 AND 215-5
  
 4)NOTE:MISSING SMOKE DETECTOR OUTSIDE
 BEDROOM#2
  
 ALSO NOTE IF PLUMB RISER IS ON PLANS
 THEN THEY WILL HAVE TO BE REVIEWED.
  
 PLEASE MAKE THE ABOVE CHANGES AND IF
 THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-02-17 Cont ID  
Sent By dpalmer Date 2000-02-17 Time 07:05 Rev Time 0.00
Received By dpalmer Date 2000-02-17 Time 07:05 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE : THESE ARE THE SAME NOTES AS
 PREVIOUSLY GIVEN.
 AS PER 373-8 DISC. MAY NOT BE USED AS
 A RACEWAY. PLEASE SHOW TWO CONDUIT PATHS
 GOING TO EACH DISC.
  
 2)NOTE: ALSO AS GIVEN BEFORE,,,,SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS IN NEW DWELLINGS.
 AS REQ`D BY 1993.1996 NFPA-72 2-2.1.1.1
 PLEASE SHOW.
  
 3)NOTE: NEED TO SHOW ON PANEL SCHEDULE
 THE DEDICATED BATH(S) CIRCUT(S)REQ`D
 BY ART:210-52D/215-5
  
 PLEASE SUBMIT THE ABOVE INDORMATION FOR
 APPROVAL.IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By jleech Date 2000-02-05 Time 10:22 Rev Time 0.50
Received By jleech Date 2000-02-05 Time 10:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-05-16 Cont ID  
Sent By tlarge Date 2000-05-16 Time 21:06 Rev Time 0.33
Received By tlarge Date 2000-05-16 Time 21:06 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SUBMIT REVISED SANITARY RISER
 PRIOR TO PLBG.INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-01-27 Cont ID  
Sent By tlarge Date 2000-01-27 Time 19:26 Rev Time 0.33
Received By tlarge Date 2000-01-27 Time 19:26 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-03-28 Cont ID  
Sent By fknapp Date 2000-03-28 Time 08:22 Rev Time 2.00
Received By fknapp Date 2000-03-28 Time 08:21 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 EXTERIOR DOORS BEING USED
 FIXED ARCH GLASS WINDOWS
  
 2)PROVIDE ENGINEERING FOR ALL BUTT GLASS
 OPENINGS
 ***PLEASE SUBMIT PRIOR TO INSTALLATION**
 3)PROVIDE ROOF SHEATING NAILING ZONES
 TO COMPLY WITH CITY AMENDMENTS FIG.
 2306.1 ZONE 3 TO BE NAILED 4" OC
  
 4)PROVIDE SAFETY GLASS PER SBC 2405.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-03-21 Cont ID  
Sent By fknapp Date 2000-03-21 Time 14:01 Rev Time 5.00
Received By fknapp Date 2000-03-21 Time 09:25 Sent To  
Notes
2001-01-08 00:00:00 
  
 *****************DENIED*****************
  
 SBC 104.2.2
  
 1)PROVIDE OWNER/AGENT SIGNATURE ON
 ENERGY CALCULATIONS.
  
 2)PROVIDE 2 CURRENT SURVEYS SIGN,DATED
 WITH RAISED SEAL.
  
 3)PROVIDE 2 SEALED COPIES OF SOIL REPORT
  
 4)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 EXTERIOR DOORS BEING USED
 SERIES 6000 ALUMINUM FIXED WINDOWS
 FIXED ARCH WINDOWS
 SLIDING GLASS DOORS
  
 5)PROVIDE PRODUCT INFORMATION FOR UL
 LISTED FIREPLACE.
  
 6)PROVIDE PRODUCT APPROVALS FOR STORM
 SHUTTERS WITH DRAWINGS THAT HAVE DATE,
 SIGNATURE AND RAISED SEAL AND KEY PLAN,
 INSTALLATION SCHEDULE AND SPECIFIC
 ANCHORS TO BE USED.
  
 7)PROVIDE ENGINEERING FOR ALL BUTT GLASS
 OPENINGS.
  
 8)PROVIDE SAFETY GLASS PER SBC 2405.2.1
  
 9)PROVIDE SPECIFIC WINDOW AND DOOR BUCK
 CONNECTION DETAILS FOR WINDLOAD
 RESISTANCE SBC 1606
  
 10)PROVIDE ROOF SHEATING NAILING ZONES
 TO COMPLY WITH CITY AMENDMENTS FIG.
 2306.1 ZONE 3 TO BE NAILED 4" OC
  
 11)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECIEPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-01-26 Cont ID  
Sent By gjoyce Date 2000-01-26 Time 09:00 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***