Plan Review Details - Permit 00011063
Plan Review Stops For Permit 00011063 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2000-03-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-03-20 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-03-20 |
Time |
14:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2000-02-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-24 |
Time |
07:20 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-24 |
Time |
07:20 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | ALL NOTES PREVIOUSLY GIVEN!!! | | | | 1)NOTE:SHOW TWO CONDIUTS FROM METER TO | | DISCS. YOU SHOW ONE GOING TO PANEL AND | | ONE GOING TO ONE DISC.????? | | | | 2)NOTE:ART;210-52D WAS GIVEN FOR REF. | | TO THE BATH CIRCUT REQ`MENTS. | | SEE #12 AND 20 AMP REQ`D. | | | | 3)NOTE: AIC RATING OF MAINS REQ`D BY | | 110-9/110-10 AND 215-5 | | | | 4)NOTE:MISSING SMOKE DETECTOR OUTSIDE | | BEDROOM#2 | | | | ALSO NOTE IF PLUMB RISER IS ON PLANS | | THEN THEY WILL HAVE TO BE REVIEWED. | | | | PLEASE MAKE THE ABOVE CHANGES AND IF | | THERE ARE ANY QUESTIONS PLEASE CALL | | 659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2000-02-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-17 |
Time |
07:05 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-17 |
Time |
07:05 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE : THESE ARE THE SAME NOTES AS | | PREVIOUSLY GIVEN. | | AS PER 373-8 DISC. MAY NOT BE USED AS | | A RACEWAY. PLEASE SHOW TWO CONDUIT PATHS | | GOING TO EACH DISC. | | | | 2)NOTE: ALSO AS GIVEN BEFORE,,,,SMOKE | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | ALL SLEEPING ROOMS IN NEW DWELLINGS. | | AS REQ`D BY 1993.1996 NFPA-72 2-2.1.1.1 | | PLEASE SHOW. | | | | 3)NOTE: NEED TO SHOW ON PANEL SCHEDULE | | THE DEDICATED BATH(S) CIRCUT(S)REQ`D | | BY ART:210-52D/215-5 | | | | PLEASE SUBMIT THE ABOVE INDORMATION FOR | | APPROVAL.IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2000-02-05 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-02-05 |
Time |
10:22 |
Rev Time |
0.50 |
Received By |
jleech |
Date |
2000-02-05 |
Time |
10:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2000-05-16 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-05-16 |
Time |
21:06 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-05-16 |
Time |
21:06 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVISO:SUBMIT REVISED SANITARY RISER | | PRIOR TO PLBG.INSPECTION. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2000-01-27 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-01-27 |
Time |
19:26 |
Rev Time |
0.33 |
Received By |
tlarge |
Date |
2000-01-27 |
Time |
19:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2000-03-28 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-03-28 |
Time |
08:22 |
Rev Time |
2.00 |
Received By |
fknapp |
Date |
2000-03-28 |
Time |
08:21 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | ****************PROVISO***************** | | | | SBC 104.2.2 | | | | 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | METRO DADE PRODUCT APPROVALS FOR: | | EXTERIOR DOORS BEING USED | | FIXED ARCH GLASS WINDOWS | | | | 2)PROVIDE ENGINEERING FOR ALL BUTT GLASS | | OPENINGS | | ***PLEASE SUBMIT PRIOR TO INSTALLATION** | | 3)PROVIDE ROOF SHEATING NAILING ZONES | | TO COMPLY WITH CITY AMENDMENTS FIG. | | 2306.1 ZONE 3 TO BE NAILED 4" OC | | | | 4)PROVIDE SAFETY GLASS PER SBC 2405.2.1 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2000-03-21 |
|
|
Cont ID |
|
Sent By |
fknapp |
Date |
2000-03-21 |
Time |
14:01 |
Rev Time |
5.00 |
Received By |
fknapp |
Date |
2000-03-21 |
Time |
09:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | | | | | *****************DENIED***************** | | | | SBC 104.2.2 | | | | 1)PROVIDE OWNER/AGENT SIGNATURE ON | | ENERGY CALCULATIONS. | | | | 2)PROVIDE 2 CURRENT SURVEYS SIGN,DATED | | WITH RAISED SEAL. | | | | 3)PROVIDE 2 SEALED COPIES OF SOIL REPORT | | | | 4)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | METRO DADE PRODUCT APPROVALS FOR: | | EXTERIOR DOORS BEING USED | | SERIES 6000 ALUMINUM FIXED WINDOWS | | FIXED ARCH WINDOWS | | SLIDING GLASS DOORS | | | | 5)PROVIDE PRODUCT INFORMATION FOR UL | | LISTED FIREPLACE. | | | | 6)PROVIDE PRODUCT APPROVALS FOR STORM | | SHUTTERS WITH DRAWINGS THAT HAVE DATE, | | SIGNATURE AND RAISED SEAL AND KEY PLAN, | | INSTALLATION SCHEDULE AND SPECIFIC | | ANCHORS TO BE USED. | | | | 7)PROVIDE ENGINEERING FOR ALL BUTT GLASS | | OPENINGS. | | | | 8)PROVIDE SAFETY GLASS PER SBC 2405.2.1 | | | | 9)PROVIDE SPECIFIC WINDOW AND DOOR BUCK | | CONNECTION DETAILS FOR WINDLOAD | | RESISTANCE SBC 1606 | | | | 10)PROVIDE ROOF SHEATING NAILING ZONES | | TO COMPLY WITH CITY AMENDMENTS FIG. | | 2306.1 ZONE 3 TO BE NAILED 4" OC | | | | 11)BEFORE A PERMIT TO CONSTRUCT CAN BE | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | BEACH CO., THE PERMIT PLANS STAMPED BY | | THEM AND THE RECIEPT ATTACHED TO THE | | PERMIT APPLICATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-01-26 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-01-26 |
Time |
09:00 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
|