Plan Review Stops For Permit 00011046 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2000-12-15 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2000-12-15 |
Time |
16:01 |
Rev Time |
3.00 |
Received By |
jwitmer |
Date |
2000-12-15 |
Time |
14:01 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | BUILDING REVIEW 12/15/2000 J. WITMER | | | | 1).503.3 GENERAL AREA MODIFICATION IN- | | CREASES TYPE 5 UNSPRINKLERED BLDG. | | ALLOWABLE AREA 8000 S.F. TOTAL FOOTAGE | | EXISTING STRUCTURE 5060 SQ.FT. ADDITION | | ANOTHER 598 S.F. TOTAL 5658 SQ. FT. | | ALLOWABLE AREA INCREASES NOT REQUIRED. | | | | 2). 104.2.2 ADMINISTRATIVE CODE: | | A).PLEASE PROVIDE ADD INFORMATION, PAGE | | 5 SHOWS A CROSS SECTION OF A 2ND | | STORY ADDITION. NO INFORMATION IS | | GIVEN ON THE 1ST FLOOR EXTERIOIR | | WALLS AND FOUNDATION FOR THE AREA | | WHERE THE ADDITION IS TO TAKE PLACE. | | B) TYPE 5 BUILDING, IS THIS BUILDING | | FIRE SPRINKLERED FULY OR PARTIALLY? | | C).DISCREPANCIES: SHEET 1 SHOWS THE 2ND | | FL. AS CLASSROOMS VS SHEET 4 AS | | MEETING ROOMS? CLASSROOMS AGE OF | | OCCUPANT? | | 3). TABLE 500: A-2 SMALL ASSEMBLY | | TABLE 500 FOR A UNSPRINKLERED BUILD- | | ING ALLOWS FOR A TYPE 5 BUILDING 2 | | STORIES. WOOD FRAME CAN ONLY BE A | | SINGLE STORY IF FRAME AND 5000 SF. | | 4). 1001.1.3 (NORTH STAIRWAY) MEANS OF | | EGRESS SHALL NOT BE PERMITTED | | THROUGH KITCHENS, CLOSETS, RESTROOMS | | & SIMILAR AREAS NOR THROUGH ADJACENT | | TENANT SPACES. | | 5). 1606.4/ 1707.4 MISSLE IMPACT RESIS- | | TANCE GLAZING. | | A).1606.4 GLAZING UNITS TO HAVE LARGE | | MISSLE IMPACT TESTING OR HAVE SHUT- | | TERS THAT HAVE BEEN TESTED & APPROVE | | B).1707.4 WINDOWS NEED TO BE TESTED 10 | | SECONDS TO 11/2 THEIR DESIGN PRES. | | 6).1606.2.6.2 COMPONENETS & CLADDING | | ROOFING SYSTEMS ARE TO BE TESTED FOR | | 110 MPH WIND ZONE. A SBCCI REPORT OR | | DADE COUNTY REPORT ARE REQUIRED. | | 7).ADM.CODE 104.2.2 ADDITIONAL INFO. | | REQUIRED, THE EAST WALL OF THE PASTORS | | OFFICE WILL REQUIRE SUPPORT (CBS CON). | | 8).2405.2.1.2 GLAZING IN HAZARDOUS LOCA- | | TIONS, SHOWER ENCLOSURES. | | 9).2309.6 ATTIC ACCESS REQUIRED, 22 X 36 | | WHEN MECHANICAL EQUIPMENT INSTALLED IN | | THE ATTIC, IT SHALL BE IN ACCORDANCE | | WITH 304.4 OF THE MECHANICAL CODE. | | 10).HURRICANE ANCHOR SCHEDULE FOR TRUSS | | SHOWING THE NATURE, LOCATION DIRECTION | | & MAGNITUDE OF LOADS TO BE RESISTED. | | 11).ASCERTAIN SPECIFIC WINDOW AND DOOR | | BUCK CONNECTIONS FOR WIND RESISTANCE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2000-09-05 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2000-09-05 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 2ND REVIEW[BUILDING] | | | | | | 1]SHOW WHERE #1 OPENS OUTSIDE. | | 2]OK, SEE PROVISO ON PLANS. | | 3]NOT PROVIDED. | | 4]NOT PROVIDED. | | 5]NOT PROVIDED. | | | | | | | | REVIEWED BY; | | LUIS MARTINEZ | | 659-8096#8456 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2000-05-02 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2000-05-02 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | **************************************** | | | | 1]ASSEMBLY OCCUPANCY REQUIRES TWO | | SEPERATE AND REMOTE EXITS FROM EACH | | STORY,SEE SECTIONS 1004.1.4AND1004.2, | | ALSO 1001.1.3,1997 SBC. | | 2]SHEET 3 SHOWS A DEAD END HALLWAY,20' | | LONG NOT PERMITTED PER SECT.1005.2. | | 3]PROVIDE DETAIL SPECIFYING OLD ROOF | | JOIST/NEW FLOOR JOIST SIZE AND SPACING | | LAYOUT. | | 4]PLEASE CLERIFY PREFAB BEAM AND POST | | COMMENT ON SHEET 4[EXISTING,NEW,BEARIN | | POINTS]. | | 5]CERTIFY ADDITIONAL LOADS IMPOSED ON | | EXISTING ONE STORY CONSTRUCTION. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2000-12-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-12-14 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-12-14 |
Time |
17:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT THE SAME PLANS | | FOR ELECTRICAL WERE SUBMITTED FOR REVIEW | | ???????????????????????????????????????? | | NOTES FORM OTHER REVIEWS ARE STILL NOT | | ADDRESSED??? | | THIS WILL BE THE FORTH ELEC PLAN REVIEW. | | PLEASE CALL TO GO OVER SETTING UP A TIME | | FOR A PLAN REVIEW MEETING WITH ME AND | | ANY OTHER REVIEWERS THAT STILL HAVE NOTE | | -S. THIS HAS BEEN ONGOING SINCE JAN,2000 | | AND THE PLAN ISSUES NEED TO BE RESOLVED. | | | | | | PLEASE ADDRESS THE ABOVE AND CALL FOR | | FOR A MEETING. IF THERE ARE ANY QUESTION | | -S PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | 659-8096 EXT 8372 | | | | LUIS MARTINEZ CHIEF PLAN REVIEWER. | | EXT 8456 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2000-08-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-08-11 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-08-11 |
Time |
10:38 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: ALL NOTES FROM PREVIOUS REVIEWS | | HAVE NOT BEEN ADDRESSED. PLEASE SEE | | ALL NOTES ATTACHED. SHOW ALL BRANCH | | CIRCUIT #`S ON PLANS!!!! AND CORRELATE | | WITH PANEL SCHEDULE. | | | | 2)NOTE: LOAD CALCULATIONS HAVE BEEN | | SUBMITTED, BUT ALL CONTINUOUS LOADS | | TO BE SHOWN AT 125% (LIGHTING ETC) | | LOAD CALCULATION SUBMITTED IS UNCLEAR. | | YOU SHOW LOADS FOR FELLOWSHIP HALL AND | | NEW SECOND FLOOR AREA. WHAT ABOUT EXIST- | | -ING AREAS??? PLEASE CLARIFY | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 659-8096 EXT 8372 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2000-04-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-04-17 |
Time |
20:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-04-17 |
Time |
20:45 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ************** UNSAT ***************** | | | | I REVIEWED THE PLANS ONCE WITH A PROVISO | | THE ORIG. NOTES WERE NOTE ADDRESSED. | | PLEASE SEE THE ATTACHED NOTES. | | | | PLEASE SUBIMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL.!!!!! |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2000-02-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2000-02-05 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2000-02-05 |
Time |
10:14 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | *************** PROVISO **************** | | | | 1)NOTE:NEED TO SUBMIT RISER DIAGRAM | | SHOWING EXISTING SERVICE/SIZE. PLEASE | | DIVIDE ALL OUTLETS AND LIGHTING CIRCUTS | | AND SHOW CIRCUT #`S ON PANEL SCHEDULE(S) | | | | | | ALL THE ABOVE INFORMATION NEEDS TO BE | | REVISED, RESUBMITTED FOR REVIEW AND | | APPROAVL BEFORE FIRST ROUGH ELECTRCIAL | | INSPECTION IS CALLED IN. IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 | | EXT 8372 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2000-12-20 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-12-20 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-12-20 |
Time |
12:53 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ON DECEMBER 20, 2000, WRITER MET WITH | | MR. MOTTLEY AT CITY HALL. SEVERAL | | QUESTIONS REGARDING THE PLANS WERE | | POSED TO HIM THAT MADE UNDERSTANDING THE | | PLANS MORE DIFFICULT. THE PLANS | | CONTINUE TO BE VERY CONFUSING AND THUS | | UNABLE TO APPROVE. | | | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2000-08-25 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2000-08-25 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2000-08-25 |
Time |
10:25 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1) PLEASE PROVIDE A PROTECTED MEANS | | OF EGRESS FROM THE SECOND FLOOR. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2000-04-13 |
|
|
Cont ID |
|
Sent By |
rturnque |
Date |
2000-04-13 |
Time |
10:45 |
Rev Time |
0.30 |
Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVIDE PROTECTED SECOND MEANS OF EGRESS | | FROM THE SECOND FLOOR. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2000-12-20 |
|
|
Cont ID |
|
Sent By |
ndenmark |
Date |
2000-12-20 |
Time |
13:29 |
Rev Time |
0.33 |
Received By |
ndenmark |
Date |
2000-12-20 |
Time |
13:29 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | PROVIDE INFORMATION ON EQUIPMENT AND | | INSTALLATION DETAILS | | PROVIDE OUTSIDE AIR CALCULATIONS PER | | ASHRAE 62-89 | | SHOW LOCATION OF OUTSIDE AIR DUCT |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2000-05-01 |
|
|
Cont ID |
|
Sent By |
cthirben |
Date |
2000-05-01 |
Time |
08:56 |
Rev Time |
0.25 |
Received By |
cthirben |
Date |
2000-05-01 |
Time |
08:52 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | ***************NOTES******************** | | INSUFFICIENT INFORMATION ON A/C UNIT TO | | BE TIED IN TO THE ADDITION. | | CALLED CUSTOMER863.0156 ON 05.01.00. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2000-12-11 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-11 |
Time |
09:52 |
Rev Time |
0.75 |
Received By |
jleech |
Date |
2000-12-11 |
Time |
09:52 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED; | | | | 1.TABLE 407 MINIMUM PLUMBING FIXTURES | | REQUIRED TWO W/C AND ONE LAV. IN BOTH | | MALE AND FEMALE BATHROOMS. ALSO | | REQUIRED IS TWO DRINKING FOUNTAINS | | HIGH LOW DRINKING FOUNTAIN WILL COUNT | | AS TWO FOUNTAINS. | | | | 2.DRINKING FOUNTAIN TO MEET REQUIREMENTS | | OF FACBC 4.1.3(10). | | | | 3.ICE MACHINE MUST INDIRECTLY DISCHARGE | | TO A FLOOR DRAIN. | | | | 4.GAS DIAGRAM REQUIRED SHOWING; TYP. AND | | SIZE OF PIPE, LENGTH OF LONGEST RUN, | | NUMBER OF APPLIANCES, AND BTU'S OF | | EACH AND TOTAL BTU'S. | | | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 659-8096 EXT. 8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2000-12-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2000-12-08 |
Time |
16:37 |
Rev Time |
1.00 |
Received By |
jleech |
Date |
2000-12-08 |
Time |
16:37 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | DENIED; | | | | 1.SHUTOFF VALVE REQUIRED FOR COLD WATER | | SUPPLY AT BUILDING. | | | | 2.SHOW COLD WATER TO WATER HEATER ON | | WATER RISER. | | | | 3.GRAB BARS REQUIRED BEHIND WATER | | CLOSETS. | | | | 4.DRINKING FOUNTAIN REQUIRED. SPC 407 | | | | 5.MINIMUM PLUMBING FIXTURES ARE 2 W/C | | FOR MALE 2 W/C FOR FEMALE AND 1 LAV | | IN EACH BATHROOM. | | | | 6.DRINKING FOUNTAIN SHALL COMPLY WITH | | FACBC 4.1.3.10A | | | | 7.SUBMIT GAS DRAWINGS FOR GAS RANGE. | | | | 8.PRIVATE BATHROOM SHALL BE ADAPTABLE | | PER. FACBC SEC. 4.1.3.11. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT.8377 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2000-08-05 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-08-05 |
Time |
13:58 |
Rev Time |
0.75 |
Received By |
tlarge |
Date |
2000-08-05 |
Time |
13:38 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | 1)A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407.BOTTLED WATER IS NOT PERMITTED | | IN LIEU OF THE DRINKING FOUNTAIN. | | | | 2)WATER SUPPLY CONTROL SHALL COMPLY W/ | | SPC SEC.610.4.1,610.4.2. | | | | 3)OCCUPANT LOAD SHALL BE DETERMINED FROM | | SPC TABLE 407.SEE SEC.407.1.3.FOR | | ALLOWED DEDUCTIBLE AREAS.PLEASE NOTE | | CORRECT OCCUPANT LOAD ON PLAN. | | | | 4)GRAB BARS ARE REQD.BEHIND THE WATER | | CLOSETS PER FACBC SEC.4.16.4. | | | | 5)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | SEC.4.1.3.(100(A). | | | | 6)SUBMIT SANITARY RISER THAT COMPLIES W/ | | SPC.WATER CLOSETS NOT PERMITTED ON WET | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | SEC.911.1.1. | | | | 7)SUBMIT GAS DRAWING FOR GAS RANGE.SEE | | ATTACHED FOR GAS REQS. | | | | 8)PRIVATE BATHROOM SHALL BE ADAPTABLE | | PER FACBC SEC.4.1.3.(11). | | | | IF YOU HAVE ANY QUESTIONS CALL | | 561-659-8096,EXT.8377. | | | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2000-04-30 |
|
|
Cont ID |
|
Sent By |
tlarge |
Date |
2000-04-30 |
Time |
11:04 |
Rev Time |
0.70 |
Received By |
tlarge |
Date |
2000-04-30 |
Time |
11:04 |
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD FOR THIS AREA AND | | TOTAL OCCUPANT LOAD FOR THIS BUILDING. | | SUBMIT NUMBER OF EXISTING PLUMBING | | FIXTURES AND TYPE TO ENSURE COMPLIANCE | | W/TABLE 407 OF SPC FOR ADDED HABITABLE | | FLOOR SPACE. | | | | FIXTURE CLEARANCES FOR ACCESSIBLE TOILET | | ROOMS SHALL COMPLY W/FACBC FIG.28. | | | | FLOOR DRAINS ARE REQD.IN THE TOILET | | ROOMS PER SPC SEC.409.4.1.1. | | | | DRAIN FOR 2ND.FLR TOILETS CANNOT CONNECT | | TO 1ST.FLR.VENT PER S[C SEC.904.1. | | | | SIZE OF SHOWER SHALL COMPLY W/COUNTYWIDE | | AMENDMENTS SEC.409.8.2.1. | | | | FLOOR AND WALLS IN TOILET ROOM SHALL BE | | NONABSORBENT TO A HEIGHT OF 4'PER SBC | | SEC.1204.2. | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407.(DEPENDING UPON EXIST.FIXTURES | | AND OCCUPANT LOAD.) | | | | CLARIFY EXTENT OF PLUMBING WORK ON 1ST. | | FLOOR.INDICATE IF ANY NEW WORK IS BEING | | DONE OR IF EXISTING. | | | | SUBMIT WATER SUPPLY RISER DIAGRAM FOR | | REVIEW.WATER SUPPLY CONTROL SHALL COMPLY | | W/SPC SEC.610.4.1.,610.4.2. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2000-02-07 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-02-07 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | NEEDS HISRORIC APPROVAL GVE TO SHERRY |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2000-02-01 |
|
|
Cont ID |
|
Sent By |
gjoyce |
Date |
2000-02-01 |
Time |
09:54 |
Rev Time |
0.25 |
Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2001-01-08 00:00:00 | GVE TO HISTORICS THEN JOE WILL REVIEW |
|
|