Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-12-15 Cont ID  
Sent By jwitmer Date 2000-12-15 Time 16:01 Rev Time 3.00
Received By jwitmer Date 2000-12-15 Time 14:01 Sent To  
Notes
2001-01-08 00:00:00BUILDING REVIEW 12/15/2000 J. WITMER
  
 1).503.3 GENERAL AREA MODIFICATION IN-
 CREASES TYPE 5 UNSPRINKLERED BLDG.
 ALLOWABLE AREA 8000 S.F. TOTAL FOOTAGE
 EXISTING STRUCTURE 5060 SQ.FT. ADDITION
 ANOTHER 598 S.F. TOTAL 5658 SQ. FT.
 ALLOWABLE AREA INCREASES NOT REQUIRED.
  
 2). 104.2.2 ADMINISTRATIVE CODE:
 A).PLEASE PROVIDE ADD INFORMATION, PAGE
 5 SHOWS A CROSS SECTION OF A 2ND
 STORY ADDITION. NO INFORMATION IS
 GIVEN ON THE 1ST FLOOR EXTERIOIR
 WALLS AND FOUNDATION FOR THE AREA
 WHERE THE ADDITION IS TO TAKE PLACE.
 B) TYPE 5 BUILDING, IS THIS BUILDING
 FIRE SPRINKLERED FULY OR PARTIALLY?
 C).DISCREPANCIES: SHEET 1 SHOWS THE 2ND
 FL. AS CLASSROOMS VS SHEET 4 AS
 MEETING ROOMS? CLASSROOMS AGE OF
 OCCUPANT?
 3). TABLE 500: A-2 SMALL ASSEMBLY
 TABLE 500 FOR A UNSPRINKLERED BUILD-
 ING ALLOWS FOR A TYPE 5 BUILDING 2
 STORIES. WOOD FRAME CAN ONLY BE A
 SINGLE STORY IF FRAME AND 5000 SF.
 4). 1001.1.3 (NORTH STAIRWAY) MEANS OF
 EGRESS SHALL NOT BE PERMITTED
 THROUGH KITCHENS, CLOSETS, RESTROOMS
 & SIMILAR AREAS NOR THROUGH ADJACENT
 TENANT SPACES.
 5). 1606.4/ 1707.4 MISSLE IMPACT RESIS-
 TANCE GLAZING.
 A).1606.4 GLAZING UNITS TO HAVE LARGE
 MISSLE IMPACT TESTING OR HAVE SHUT-
 TERS THAT HAVE BEEN TESTED & APPROVE
 B).1707.4 WINDOWS NEED TO BE TESTED 10
 SECONDS TO 11/2 THEIR DESIGN PRES.
 6).1606.2.6.2 COMPONENETS & CLADDING
 ROOFING SYSTEMS ARE TO BE TESTED FOR
 110 MPH WIND ZONE. A SBCCI REPORT OR
 DADE COUNTY REPORT ARE REQUIRED.
 7).ADM.CODE 104.2.2 ADDITIONAL INFO.
 REQUIRED, THE EAST WALL OF THE PASTORS
 OFFICE WILL REQUIRE SUPPORT (CBS CON).
 8).2405.2.1.2 GLAZING IN HAZARDOUS LOCA-
 TIONS, SHOWER ENCLOSURES.
 9).2309.6 ATTIC ACCESS REQUIRED, 22 X 36
 WHEN MECHANICAL EQUIPMENT INSTALLED IN
 THE ATTIC, IT SHALL BE IN ACCORDANCE
 WITH 304.4 OF THE MECHANICAL CODE.
 10).HURRICANE ANCHOR SCHEDULE FOR TRUSS
 SHOWING THE NATURE, LOCATION DIRECTION
 & MAGNITUDE OF LOADS TO BE RESISTED.
 11).ASCERTAIN SPECIFIC WINDOW AND DOOR
 BUCK CONNECTIONS FOR WIND RESISTANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-05 Cont ID  
Sent By lmartine Date 2000-09-05 Time 16:01 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:002ND REVIEW[BUILDING]
  
  
 1]SHOW WHERE #1 OPENS OUTSIDE.
 2]OK, SEE PROVISO ON PLANS.
 3]NOT PROVIDED.
 4]NOT PROVIDED.
 5]NOT PROVIDED.
  
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 659-8096#8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-05-02 Cont ID  
Sent By lmartine Date 2000-05-02 Time 13:56 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00****************************************
  
 1]ASSEMBLY OCCUPANCY REQUIRES TWO
 SEPERATE AND REMOTE EXITS FROM EACH
 STORY,SEE SECTIONS 1004.1.4AND1004.2,
 ALSO 1001.1.3,1997 SBC.
 2]SHEET 3 SHOWS A DEAD END HALLWAY,20'
 LONG NOT PERMITTED PER SECT.1005.2.
 3]PROVIDE DETAIL SPECIFYING OLD ROOF
 JOIST/NEW FLOOR JOIST SIZE AND SPACING
 LAYOUT.
 4]PLEASE CLERIFY PREFAB BEAM AND POST
 COMMENT ON SHEET 4[EXISTING,NEW,BEARIN
 POINTS].
 5]CERTIFY ADDITIONAL LOADS IMPOSED ON
 EXISTING ONE STORY CONSTRUCTION.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-12-14 Cont ID  
Sent By dpalmer Date 2000-12-14 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2000-12-14 Time 17:25 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
  
 1)NOTE: PLEASE NOTE THAT THE SAME PLANS
 FOR ELECTRICAL WERE SUBMITTED FOR REVIEW
 ????????????????????????????????????????
 NOTES FORM OTHER REVIEWS ARE STILL NOT
 ADDRESSED???
 THIS WILL BE THE FORTH ELEC PLAN REVIEW.
 PLEASE CALL TO GO OVER SETTING UP A TIME
 FOR A PLAN REVIEW MEETING WITH ME AND
 ANY OTHER REVIEWERS THAT STILL HAVE NOTE
 -S. THIS HAS BEEN ONGOING SINCE JAN,2000
 AND THE PLAN ISSUES NEED TO BE RESOLVED.
  
  
 PLEASE ADDRESS THE ABOVE AND CALL FOR
 FOR A MEETING. IF THERE ARE ANY QUESTION
 -S PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372
  
 LUIS MARTINEZ CHIEF PLAN REVIEWER.
 EXT 8456

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-08-11 Cont ID  
Sent By dpalmer Date 2000-08-11 Time 10:38 Rev Time 0.00
Received By dpalmer Date 2000-08-11 Time 10:38 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
  
 1)NOTE: ALL NOTES FROM PREVIOUS REVIEWS
 HAVE NOT BEEN ADDRESSED. PLEASE SEE
 ALL NOTES ATTACHED. SHOW ALL BRANCH
 CIRCUIT #`S ON PLANS!!!! AND CORRELATE
 WITH PANEL SCHEDULE.
  
 2)NOTE: LOAD CALCULATIONS HAVE BEEN
 SUBMITTED, BUT ALL CONTINUOUS LOADS
 TO BE SHOWN AT 125% (LIGHTING ETC)
 LOAD CALCULATION SUBMITTED IS UNCLEAR.
 YOU SHOW LOADS FOR FELLOWSHIP HALL AND
 NEW SECOND FLOOR AREA. WHAT ABOUT EXIST-
 -ING AREAS??? PLEASE CLARIFY
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-04-17 Cont ID  
Sent By dpalmer Date 2000-04-17 Time 20:45 Rev Time 0.00
Received By dpalmer Date 2000-04-17 Time 20:45 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT *****************
  
 I REVIEWED THE PLANS ONCE WITH A PROVISO
 THE ORIG. NOTES WERE NOTE ADDRESSED.
 PLEASE SEE THE ATTACHED NOTES.
  
 PLEASE SUBIMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.!!!!!

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-02-05 Cont ID  
Sent By dpalmer Date 2000-02-05 Time 10:14 Rev Time 0.00
Received By dpalmer Date 2000-02-05 Time 10:14 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE:NEED TO SUBMIT RISER DIAGRAM
 SHOWING EXISTING SERVICE/SIZE. PLEASE
 DIVIDE ALL OUTLETS AND LIGHTING CIRCUTS
 AND SHOW CIRCUT #`S ON PANEL SCHEDULE(S)
  
  
 ALL THE ABOVE INFORMATION NEEDS TO BE
 REVISED, RESUBMITTED FOR REVIEW AND
 APPROAVL BEFORE FIRST ROUGH ELECTRCIAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL 659-8096
 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2000-12-20 Cont ID  
Sent By mcarsill Date 2000-12-20 Time 12:53 Rev Time 0.00
Received By mcarsill Date 2000-12-20 Time 12:53 Sent To  
Notes
2001-01-08 00:00:00ON DECEMBER 20, 2000, WRITER MET WITH
 MR. MOTTLEY AT CITY HALL. SEVERAL
 QUESTIONS REGARDING THE PLANS WERE
 POSED TO HIM THAT MADE UNDERSTANDING THE
 PLANS MORE DIFFICULT. THE PLANS
 CONTINUE TO BE VERY CONFUSING AND THUS
 UNABLE TO APPROVE.
  
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-25 Cont ID  
Sent By mcarsill Date 2000-08-25 Time 10:25 Rev Time 0.00
Received By mcarsill Date 2000-08-25 Time 10:25 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE A PROTECTED MEANS
 OF EGRESS FROM THE SECOND FLOOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-04-13 Cont ID  
Sent By rturnque Date 2000-04-13 Time 10:45 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE PROTECTED SECOND MEANS OF EGRESS
 FROM THE SECOND FLOOR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-12-20 Cont ID  
Sent By ndenmark Date 2000-12-20 Time 13:29 Rev Time 0.33
Received By ndenmark Date 2000-12-20 Time 13:29 Sent To  
Notes
2001-01-08 00:00:00PROVIDE INFORMATION ON EQUIPMENT AND
 INSTALLATION DETAILS
 PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 SHOW LOCATION OF OUTSIDE AIR DUCT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-05-01 Cont ID  
Sent By cthirben Date 2000-05-01 Time 08:56 Rev Time 0.25
Received By cthirben Date 2000-05-01 Time 08:52 Sent To  
Notes
2001-01-08 00:00:00***************NOTES********************
 INSUFFICIENT INFORMATION ON A/C UNIT TO
 BE TIED IN TO THE ADDITION.
 CALLED CUSTOMER863.0156 ON 05.01.00.

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-12-11 Cont ID  
Sent By jleech Date 2000-12-11 Time 09:52 Rev Time 0.75
Received By jleech Date 2000-12-11 Time 09:52 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.TABLE 407 MINIMUM PLUMBING FIXTURES
 REQUIRED TWO W/C AND ONE LAV. IN BOTH
 MALE AND FEMALE BATHROOMS. ALSO
 REQUIRED IS TWO DRINKING FOUNTAINS
 HIGH LOW DRINKING FOUNTAIN WILL COUNT
 AS TWO FOUNTAINS.
  
 2.DRINKING FOUNTAIN TO MEET REQUIREMENTS
 OF FACBC 4.1.3(10).
  
 3.ICE MACHINE MUST INDIRECTLY DISCHARGE
 TO A FLOOR DRAIN.
  
 4.GAS DIAGRAM REQUIRED SHOWING; TYP. AND
 SIZE OF PIPE, LENGTH OF LONGEST RUN,
 NUMBER OF APPLIANCES, AND BTU'S OF
 EACH AND TOTAL BTU'S.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-12-08 Cont ID  
Sent By jleech Date 2000-12-08 Time 16:37 Rev Time 1.00
Received By jleech Date 2000-12-08 Time 16:37 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.SHUTOFF VALVE REQUIRED FOR COLD WATER
 SUPPLY AT BUILDING.
  
 2.SHOW COLD WATER TO WATER HEATER ON
 WATER RISER.
  
 3.GRAB BARS REQUIRED BEHIND WATER
 CLOSETS.
  
 4.DRINKING FOUNTAIN REQUIRED. SPC 407
  
 5.MINIMUM PLUMBING FIXTURES ARE 2 W/C
 FOR MALE 2 W/C FOR FEMALE AND 1 LAV
 IN EACH BATHROOM.
  
 6.DRINKING FOUNTAIN SHALL COMPLY WITH
 FACBC 4.1.3.10A
  
 7.SUBMIT GAS DRAWINGS FOR GAS RANGE.
  
 8.PRIVATE BATHROOM SHALL BE ADAPTABLE
 PER. FACBC SEC. 4.1.3.11.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-05 Cont ID  
Sent By tlarge Date 2000-08-05 Time 13:58 Rev Time 0.75
Received By tlarge Date 2000-08-05 Time 13:38 Sent To  
Notes
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.BOTTLED WATER IS NOT PERMITTED
 IN LIEU OF THE DRINKING FOUNTAIN.
  
 2)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1,610.4.2.
  
 3)OCCUPANT LOAD SHALL BE DETERMINED FROM
 SPC TABLE 407.SEE SEC.407.1.3.FOR
 ALLOWED DEDUCTIBLE AREAS.PLEASE NOTE
 CORRECT OCCUPANT LOAD ON PLAN.
  
 4)GRAB BARS ARE REQD.BEHIND THE WATER
 CLOSETS PER FACBC SEC.4.16.4.
  
 5)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(100(A).
  
 6)SUBMIT SANITARY RISER THAT COMPLIES W/
 SPC.WATER CLOSETS NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 7)SUBMIT GAS DRAWING FOR GAS RANGE.SEE
 ATTACHED FOR GAS REQS.
  
 8)PRIVATE BATHROOM SHALL BE ADAPTABLE
 PER FACBC SEC.4.1.3.(11).
  
 IF YOU HAVE ANY QUESTIONS CALL
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-04-30 Cont ID  
Sent By tlarge Date 2000-04-30 Time 11:04 Rev Time 0.70
Received By tlarge Date 2000-04-30 Time 11:04 Sent To  
Notes
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD FOR THIS AREA AND
 TOTAL OCCUPANT LOAD FOR THIS BUILDING.
 SUBMIT NUMBER OF EXISTING PLUMBING
 FIXTURES AND TYPE TO ENSURE COMPLIANCE
 W/TABLE 407 OF SPC FOR ADDED HABITABLE
 FLOOR SPACE.
  
 FIXTURE CLEARANCES FOR ACCESSIBLE TOILET
 ROOMS SHALL COMPLY W/FACBC FIG.28.
  
 FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 DRAIN FOR 2ND.FLR TOILETS CANNOT CONNECT
 TO 1ST.FLR.VENT PER S[C SEC.904.1.
  
 SIZE OF SHOWER SHALL COMPLY W/COUNTYWIDE
 AMENDMENTS SEC.409.8.2.1.
  
 FLOOR AND WALLS IN TOILET ROOM SHALL BE
 NONABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2.
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.(DEPENDING UPON EXIST.FIXTURES
 AND OCCUPANT LOAD.)
  
 CLARIFY EXTENT OF PLUMBING WORK ON 1ST.
 FLOOR.INDICATE IF ANY NEW WORK IS BEING
 DONE OR IF EXISTING.
  
 SUBMIT WATER SUPPLY RISER DIAGRAM FOR
 REVIEW.WATER SUPPLY CONTROL SHALL COMPLY
 W/SPC SEC.610.4.1.,610.4.2.

Review Stop Z ZONING
Rev No 2 Status F Date 2000-02-07 Cont ID  
Sent By gjoyce Date 2000-02-07 Time 14:08 Rev Time 0.00
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS HISRORIC APPROVAL GVE TO SHERRY

Review Stop Z ZONING
Rev No 1 Status P Date 2000-02-01 Cont ID  
Sent By gjoyce Date 2000-02-01 Time 09:54 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00GVE TO HISTORICS THEN JOE WILL REVIEW